| Plan Review Notes For Permit 08090189 |
| Permit Number |
08090189 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-11 11:54:06 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. THE SUBMITTED IRRIGATION PLANS ARE NOT INDICATING | | | THE REQUIRED RAIN SHUT OFF DEVICE (RAIN SENSOR). THIS | | | DEVICE MUST BE CLEARLY INDICATED ON THE IRRIGATION | | | PLANS AS WELL AS ITS SYMBOL ON THE IRRIGATION LEGEND. | | | THE AUTOMATIC IRRIGATION CONTROLLER SHALL BE CAPABLE OF | | | INCORPORATING A RAIN SHUT OFF DEVICE TO OVERRIDE THE | | | IRRIGATION CYCLE WHEN ADEQUATE RAINFALL HAS OCCURED, AS | | | REQUIRED BY FLORIDA STATUTES, SECTION 373.62. THE RAIN | | | SWITCH SHALL BE PLACED ON A STATIONARY STRUCTURE | | | MINIMUM OF 5-FOOT (1524MM) CLEARANCE FROM OTHER OUTDOOR | | | EQUIPMENT, FREE AND CLEAR OF ANY TREE CANOPY OR OTHER | | | OVERHEAD OBSTRUCTIONS, AND ABOVE THE HEIGHT OF THE | | | SPRINKLER COVERAGE. | | | | | | 2. CLEARLY INDICATE THAT THE 1" BACKFLOW PREVENTER FOR | | | THE IRRIGATION SUPPLY IS BEING INSTALLED BY A LICENSED | | | PLUMBING CONTRACTOR. PER FLORIDA STATUTES 489.105 | | | (3)(M) PLUMBING CONTRACTOR. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|