| Plan Review Notes For Permit 08090188 |
| Permit Number |
08090188 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-10 15:35:53 | | | | | | | DENIED | | | | | | 1) PROVIDE PRODUCT APPROVAL COVER SHEETS, IF THIS IS A | | | STATEWIDE PRODUCT APPROVAL THE SHEETS FROM THE STATE | | | THAT USE THIS EVALUATION AND DRAWING ARE REQUIRED (FL # | | | 5351). | | | | | | 2) NO PRODUCT APPROVAL WAS SUBMITTED FOR THE LEXAN | | | PANELS. | | | | | | 3) PER SHEET 14 OF THE PRODUCT APPROVAL DIRECT MOUNTING | | | USING PANELMATES REQUIRES A MIN 2" FOR EDGE DISTANCE. | | | MAKE CHANGES TO REFLECT IN SHUTTER SCHEDULE. | | | | | | 4) PLEASE NOTE THAT THE PANEL SPAN IS THE OPENING SIZE | | | PLUS THE EDGE DISTANCE AT EACH END OF PANELS, THE | | | SHUTTER SCHEDULE STATES ONLY THE OPENING SIZE, IN THIS | | | CASE THE WIDTH FOR HORIZONTAL INSTALLATION. | | | | | | 5) PROVIDE 2 COPIES OF ALL CONSTRUCTION DOCUMENTS THIS | | | INCLUDES THE SHUTTER SCHEDULE. | | | | | | 6) COMPLETE SHUTTER SCHEDULE THE O/C SPACING OF THE | | | FASTENERS WERE NOT INCLUDED, ALSO ADD ADDITIONAL PAGES | | | WHEN REQUIRED NOTES ON THE BACK OF PAGES ARE NOT | | | ACCEPTABLE. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|