| 2008-10-16 16:33:00 | 2004 FBC W/2007 REVISIONS |
| | ENCLOSE CARPORT |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT 2 COMPLETE IDENTICAL SETS OF THE PLAN |
| | DRAWINGS. FBC 106.1* CITY AMENDMENTS |
| | |
| | 4) SUBMIT TWO COPIES OF COMPETED AND SIGNED ENERGY |
| | CALCULATION FORMS ON THE PLANS. FBC 13-600 SEE THE |
| | ATTACHED FORM. PLEASE COMPLETE AND SIGN IN TWO PLACES |
| | AS THE PREPARER AND OWNER. |
| | |
| | 5) THE CONCRETE BLOCK WALL IS REQUIRED TO HAVE |
| | INSULATION WITH A MINIMUM OF R-5. FBC 13-600. |
| | |
| | 6) PROVIDE DOOR AND WINDOW BUCK FASTENING DETAILS ON |
| | THE PLANS. R613.6.1.1 |
| | |
| | 7) THE NEW PLANS DO NOT SPECIFY WHAT THE C-1 AND C-2 |
| | COLUMNS ARE. THE OLD PLANS SHOW THE C-I AS A 8" X 16" |
| | WITH (2) #5 RE-BARS IN FILLED CELLS AND THE C-2 AS AN |
| | 8" X 8" FILLED CELL WITH (1) #5 RE-BAR. |
| | |
| | 8) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR THE |
| | IMPACT RATED WINDOWS. FAC RULE 9B-72 & FBC 106.1* CITY |
| | AMENDMENTS |
| | |
| | 9) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR IN-SWING METAL DOOR. FAC RULE 9B-72 & FBC |
| | 106.1* CITY AMENDMENTS |
| | |
| | NOTE: PLEASE REMOVE THE NON-IMPACT RATED WINDOW PRODUCT |
| | APPROVALS FROM THE SUBMITTALS. |
| | |