| 2008-09-26 16:56:03 | 2004 FBC W/2007 REVISIONS |
| | ENCLOSE CARPORT |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT 2 COPIES OF A SURVEY OR SITE PLAN SHOWING THE |
| | DISTANCES FROM THE CARPORT WALLS TO THE PROPERTY LINES |
| | AND STRUCTURES ON ADJACENT PROPERTY IF LESS THAN SIX |
| | FEET TO PROPERTY LINES. FBC R302.1 AND R302.2 REQUIRES |
| | EXTERIOR WALLS TO BE ONE HOUR FIRE RATED WITH NO |
| | OPENINGS IF SEPARATED BY LESS THAN SIX FEET. |
| | |
| | 4) PLEASE LIST THE NAME AND CONTACT INFORMATION OF THE |
| | PERSON RESPONSIBLE FOR THE DRAWINGS ON THE PLANS. |
| | |
| | 5) SUBMIT TWO COPIES OF COMPETED AND SIGNED ENERGY |
| | CALCULATION FORMS ON THE PLANS. FBC 13-600 |
| | |
| | 6) SPECIFY THE WALL AND CEILING INSULATION ON THE |
| | PLANS. FBC 13-600. |
| | |
| | 7) PROVIDE A WALL SECTION OF THE NEW WALL ON THE PLANS. |
| | SPECIFY THE WALL FURRING, INSULATION, DRYWALL, EXTERIOR |
| | FINISH, ETC. R301 |
| | |
| | 8) PROVIDE DOOR AND WINDOW BUCK DETAILS ON THE PLANS. |
| | R613.6.1.1 |
| | |
| | 9) ON PAGE 3 OF THE PLANS THE C-2 COLUMNS ARE SPECIFIED |
| | AS CAST IN PLACE CONCRETE, BUT APPEAR TO BE REINFORCED |
| | FILLED CELL MASONRY. PLEASE CLARIFY. |
| | |
| | 10) ON PAGE 3 OF THE PLANS THE C-2 COLUMNS ARE |
| | SPECIFIED AS 4'-8" O.C. AND NOTE #2 SPECIFIES |
| | REINFORCING AT 48" (4') O.C. PLEASE CLARIFY. |
| | |
| | 11) THE C-1 COLUMNS ARE SPECIFIED AT 4'-8" O.C. BUT ARE |
| | ONLY LOCATED WHERE THE NEW MASONRY WALLS ATTACH TO THE |
| | EXISTING MASONRY WALLS. PLEASE CORRECT. |
| | |
| | 12) THE SIZE OF THE EXISTING FOOTINGS SUPPORTING THE |
| | NEW MASONRY WALLS SHALL BE CAPABLE OF ACCOMMODATING ALL |
| | LOADS AND TRANSMITTING THEM TO THE SOIL. FBC 403.1 |
| | |
| | 13) SPECIFY THE WINDOW AND DOOR SIZES AND TYPES ON THE |
| | PLANS. R301.2(2) & FAC RULE 9B-72 |
| | |
| | 14) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL |
| | EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE |
| | FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM) |
| | WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES |
| | (152 MM) ELSEWHERE. |
| | |
| | 15) PAGE 2 OF THE PLANS SPECIFY IMPACT WINDOWS AND THE |
| | PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| | NON-IMPACT AND REQUIRE IMPACT PROTECTION. PLEASE |
| | CORRECT. R301.2.1.2 |
| | |
| | 16) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR WINDOW |
| | MULLIONS. FAC RULE 9B-72 |
| | |
| | 17) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | IN-SWING METAL DOOR. FAC RULE 9B-72 |
| | |
| | 18) SUBMIT 2 COPIES OF A KEY PLAN AND AN INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS REQUIRED BY FBC |
| | R301.2.1.2, IF IMPACT RATED PRODUCTS ARE NOT TO BE |
| | INSTALLED. |
| | |
| | 19) SPECIFY THE APPLICABLE CODE AND WIND DESIGN |
| | INFORMATION ON THE PLANS. FBC R301 NOTE: THE CODE IS |
| | THE FBC 2004 WITH 2007 REVISIONS AND THE WINDSPEED IS |
| | 140 MPH (3 SECOND GUST) EXPOSURE CATEGORY B. |
| | |