Plan Review Notes
Plan Review Notes For Permit 08090147
Permit Number 08090147
Review Stop M
Sequence Number 1
Notes
Date Text
2008-09-09 09:59:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) A/C SYSTEM MODEL NUMBERS C/U 24ANA136A003 WITH A/H
 FE4ANF005000 LISTED ON THE A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 2) SHOW ON PLAN HOW AND WERE CONDENSATE WATER WILL BE
 DISPOSED OF, PER 2004 FBC/R M1411.3 AND R320.7.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]