| 2009-02-25 09:40:55 | ** NOTE: ONE SET OF ELECTRICAL PLANS HAVE BEEN REMOVED |
| | FROM SETS AND WILL BE RETAINED BY THIS OFFICE. |
| 2009-02-25 09:38:19 | ** DENIED 2ND REVIEW ** |
| | |
| | 1ST REVIEW UNDER PERMIT APPLICATION. |
| | 2ND REVIEW. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE TO ADJUST CODES AND DESIGNS FOR |
| | THE FOLLOWING. THE PERMIT APPLICATION HAS ONLY NOW BEEN |
| | MADE. PER FAC 69A-60.004 AND .003 NFPA-1 AND NFPA-101 |
| | HAS BEEN REVISED TO THE 2006 EDITIONS OF EACH. |
| | THIS IS A SEPARATE ADOPTED RULING FROM THE STATE AND IS |
| | NOT BASED ON THE NEW CODE ADOPTIONS OF MARCH 1ST 2009. |
| | PLEASE REVISE ANY NEEDED DESIGNS AND REVISED CODE |
| | REFERENCES ON PLANS. |
| | |
| | 2) NOTE: AS STATED ON PREVIOUS REVIEWS. THE BASE |
| | BUILDING DOES NOT CONTAIN A CERTIFICATE OF OCCUPANCY. |
| | ALL PLANS SHALL GO BACK TO THE BASE BUILDING DESIGNERS |
| | OF RECORD FOR *SHOP DRAWING REVIEW STAMP* AND SIGNATURE |
| | FROM EACH INDIVIDUAL DESIGNER OF RECORD. |
| | THIS BUILDING IS UNDER THE RESPONSIBILITY OF EACH OF |
| | THOSE DESIGNERS UNTIL SUCH TIME THE BUILDING IS |
| | COMPLETE BASED ON PERMITTED SCOPE OF WORK ON PLANS FOR |
| | C OF O, C OF C, ETC. |
| | FS 471,481 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS. NO NEW |
| | SERVICE WITH SEPARATE METER WILL BE GRANTED. IN SEVERAL |
| | MEETINGS HELD BEFORE PLANS WERE RESUBMITTED THE REQUEST |
| | WAS MADE FOR THE SEPARATE MAIN IN ORDER FOR ALL |
| | ELECTRICAL IN THE TENANT SPACE TO BE FED SEPARATELY SO |
| | THAT THE TENANT COULD BE METERED SEPARATELY FROM FPL |
| | AND PAY THEIR OWN ELECTRIC BILL. |
| | IN THE MEETINGS HELD IT WAS AGREED TO REMOVE COMMON |
| | AREAS WHICH WERE BEING FED FROM TENANT MAIN AND TO HAVE |
| | ACTUAL TENANT SEPARATION. |
| | THIS WAS ALSO BASED ON THE EGRESS LIGHTING IN TENANT |
| | SPACE BEING FED FROM BATTERY BACK UP FIXTURES IN ORDER |
| | TO EXIT OCCUPANTS FROM THE BUILDING IN THE EVENT OF |
| | POWER FAILURE/EMERGENCY. |
| | THE PLANS HAVE NOW BEEN COMPLETELY REVISED TO SHOW A |
| | SUBSTANTIAL AMOUNT OF *GENERAL LIGHTING* WHICH HAPPENS |
| | TO BE BATTERY BACK UP FIXTURES ALSO BEING FED FROM THE |
| | CITY'S ELECTRICAL SERVICE MAIN WHICH IS PART OF THE |
| | CITY'S METERING AND BILLING. THIS IS NOT WHAT WAS GONE |
| | OVER IN THE MEETINGS AND MANY DISCUSSIONS. THIS IS |
| | COMPLETELY OPPOSITE FROM THE REASON A SEPARATE |
| | SERVICE/MAIN WAS REQUESTED IN ORDER TO METER SEPARATELY |
| | FOR TENANT. ESSENTIALLY BASED ON THE ELECTRICAL SHOWN |
| | MUCH OF THE ELECTRICAL LIGHTING IS FED FROM THE CITY'S |
| | ELECTRICAL SERVICE WHICH WOULD NOW AFFECT THE 700 AND |
| | 701 SYSTEMS FOR SELECTIVE COORDINATION. |
| | THE TENANT BATH ROOMS AND OTHER AREAS ARE ALSO STILL |
| | BEING SHOWN BEING FED FROM THE BASE BUILDING'S |
| | ELECTRICAL SYSTEM. THIS BATHROOM IS LOCATED IN THE |
| | TENANT SPACE ALONG WITH SHIPPING AND RECEIVING. THIS |
| | WOULD ELECTRICAL SYSTEMS CROSSED INTO THE TENANT SPACE. |
| | THIS WILL ALSO NOT BE PERMITTED. |
| | THE TENANT MAY GO BACK TO THE BASE BUILDING ELECTRICAL |
| | SERVICE AS THERE IS SPACE, LOAD AND DESIGN FOR THE |
| | TENANT. |
| | 230.2, 700.27, 700.18, 700.12F, 240.12 ETC. |
| | |
| | 4) NOTE: AS NOTED ON PREVIOUS REVIEW. PLEASE SUBMIT |
| | COMPLETE LIGHTING PERFORMANCE CALCULATIONS BASED ON |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | PLEASE SEE SECTION AS NOTED FOR TRACK LIGHTING. THE |
| | WATTAGE MUST BE BASED ON THE RATING OF THE FIXTURE |
| | TIMES THE NUMBER OF FIXTURES, OR 30WATTS PER FOOT WHICH |
| | EVER IS GREATER. |
| | |
| | AN EXAMPLE: THE WATTAGE PER SQ FT SHOWN FOR MUSEUM AREA |
| | IS 1.7. THE CODE IN TABLE *B* ALLOWS 1.0 AND THEN ONLY |
| | THE ADDITIONAL FOR THE ACTUAL DISPLAY OR ACCENT |
| | LIGHTING IS EXEMPT. THIS IS NOT AN AREA FOR RESTORATION |
| | WORK WHICH IS WHAT SEEMS TO BE THE ALLOWANCE SHOWN. |
| | |
| | THE WATTAGE MUST BE BASED ON FIXTURE/BALLAST VA. SEE |
| | FIXTURES A AND B FOR EXAMPLE. IN THE CALCULATIONS THE |
| | COMPLETE FIXTURE WATTAGE IS SHOWN AT 30WATTS. HOW IS |
| | THIS POSSIBLE WHEN EACH OF THESE FIXTURES CONTAIN |
| | 2-32WATT BULBS BASED ON THE FIXTURE LEGEND? EVEN WITH |
| | SOME OF THE MOST EFFICIENT BALLAST AVAILABLE ON THE |
| | MARKETS, THE WATTAGE WOULD NOT BE CUT INTO LESS THAN |
| | HALF. BASE ON THE CALCULATIONS AND DERIVED WATTAGE |
| | THERE SEEMS TO BE SOME SORT OF MISPRINT OF ACTUAL |
| | FIXTURE WATTAGE. |
| | |
| | ANOTHER EXAMPLE WOULD BE SPACE 1.14 WHICH SHOWS A |
| | FIXTURE WATTAGE FIGURED INTO THE CALCULATIONS OF 30 |
| | WATTS HOWEVER BASED ON THE MAXIMUM WATTAGE PER FIXTURE |
| | AS STATED ON THE FIXTURE LEGEND THE FIXTURES WOULD BE A |
| | MAXIMUM OF 37WATTS. THIS WOULD BE THE WATTAGE NEEDED TO |
| | BE FIGURED INTO THE CALCULATIONS. THIS IS ONLY THE |
| | WATTAGE *IF* THE TOTAL WATTAGE OF FIXTURES TIMES THE |
| | NUMBER OF FIXTURES IS LOWER THAN THE 30VA PER FT OF |
| | TRACK ON PLANS. (AS NOTED ABOVE). |
| | |
| | THERE ARE OTHER AREAS AND ROOMS SUCH AS COMPUTER LAB |
| | WHICH SHOWS A *0* WATTAGE IN DESIGN. THESE CALCULATIONS |
| | MUST BE BASED ON SPACE BY SPACE. HOW CAN THESE VALUES |
| | BE *0*? |
| | PLEASE SEE CODE SECTIONS AS NOTED ABOVE. |
| | THESE ARE ONLY SOME EXAMPLES AS IS NOT A LIST OF EACH |
| | ITEM NOT SHOWN FOR CODE COMPLIANCE AND COORDINATION. |
| | FBC 106.1.1,106.1.2, CLARITY AND COORDINATION. |
| | |
| | 5) NOTE: THERE SHALL BE NO STORAGE IN ELECTRICAL ROOMS |
| | WHICH CONTAIN ELECTRICAL PANELS, TRANSFORMERS AND OVER |
| | CURRENT PROTECTION. PLANS INDICATE COMPUTER STORAGE |
| | WHICH IS NOT PERMITTED IN ROOM 2.13. |
| | 408.17, 240.24, 110.26. |
| | SHALL ALSO CONTAIN SIGNAGE: ELECTRICAL ROOM, NO STORAGE |
| | PER FIRE MARSHAL OR WORDS TO THAT AFFECT. |
| | |
| | 6) NOTE: PLEASE SEE NEW WATER HEATER SHOWN UNDER |
| | COUNTER DOES NOT CONTAIN ANY CIRCUITING OR DISCONNECT. |
| | PLEASE COMPLETE SO THAT LOADS, CIRCUITING ETC MAY BE |
| | REVIEWED. |
| | 4220.30,4220.31,408.4, 310.16 |
| | FBC 106.1, 106.1.2 FOR CLARITY, ADDITIONAL INFORMATION. |
| | |
| | 7) NOTE: PLEASE SEE SHEET E1.03 WHICH REFERENCES THE |
| | 2007 FBC FOR ADA COMPLIANCE. THIS PROJECT HAS BEEN |
| | APPLIED FOR PERMIT UNDER THE 2004 FBC W/2007 REVISION. |
| | PLEASE REVISE. |
| | |
| | *** IT IS IMPORTANT TO KNOW AS THERE WILL BE |
| | SUBSTANTIAL CHANGES TO PLANS THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT |
| | THIS TIME. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |