| 2008-09-10 11:30:29 | PLAN REVIEW DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SINCE THE SHELL BUILDING HAS NOT BEEN COMPLETED, AND |
| | NO CERTIFICATE OF OCCUPANCY HAS BEEN ISSUED, BUT DESIGN |
| | TEAM OF THE SHELL BUILDING SHALL REVIEW THE PLANS FOR |
| | THE BUILD-OUT AND IF APPROVED, SHALL THEN STAMP THE |
| | PLANS AS REVIEWED AND ACCEPTED WITH A SHOP DRAWING |
| | STAMP OF APPROVAL. |
| | |
| | 2. THE ADDRESS AND SPACE NUMBER SHALL BE INDICATED IN |
| | THE TITLE BLOCK OF EACH SHEET. SECTION 106.1.1. |
| | |
| | 3. SHT A0.00 CODES & STANDARDS SHALL READ 2004 BUILDING |
| | CODE WITH 2005, 2006 & 2007 REVISIONS. SECTION 106.1.2. |
| | |
| | 4. SHT A0.01 OCCUPANCY & EGRESS ANALYSIS INDICATES |
| | ASSEMBLY OCCUPANCY - UNCONSENTRATED NET SF 15. PER |
| | TABLE 1004.1.2 IT CALLS FOR TABLES & CHAIRS. PLEASE |
| | SHOW THE TABLES & CHAIRS ON THE FLOOR PLAN FOR THE |
| | ASSEMBLY OCCUPANCY. |
| | |
| | 5. SHT A0.02 LOUNGE ROOM 2.24 DOES NOT REFLECT |
| | INFORMATION SHOWN ON SHT P2.1. A SINK IS SHOWN ON THE |
| | PLUMBING SHEET BUT NOT ON THE ARCHITECTURAL SHEET. |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 6. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS. |
| | SHOW THE CLEAR FLOOR SPACE ON THE FLOOR PLAN. CABINET |
| | DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| | |
| | 7. SHT P2.1 A WATER HAMMER ARRESTOR IS REQUIRED ON THE |
| | WATER SUPPLY LINE TO THE REF. SECTION 604.9. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |