| 2008-09-24 14:53:42 | BUILDING PLAN REVIEW |
| | PERMIT: 08090142 (PLAN REVIEW) |
| | ADD: 401 CLEMATIS ST. SUITE # . |
| | CONT: (PLAN REVIEW) CONTACT: TED DAVIS |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS.THE COVER SHEEET |
| | NEGLECTS THE 2007 SUPPLEMENTS TO THE 2004 FBC, PLEASE |
| | CORRECT. 106.1.2 ADDITIONAL INFORMATION REQUIRED, |
| | 553.73FL S S . |
| | |
| | 1D) THIS TENANT SPACE IS LEASEABLE SPACE AND WILL |
| | REQUIRE A SUITE ADDRESS, TO BE PROVIDED BY ADDRESS |
| | TECHNITION JAMES JUDGE, AND WILL NEED TO BE ON THE |
| | PERMIT APPLICATIONAS WELL AS PLANS. |
| | |
| | 2) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED |
| | THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING |
| | DESIGNER WILL NEED TO REVIEW THE SUBMITTED PLANS AND |
| | AFFIX THEIR SHOP DRAWING STAMP ON THE PLANS. THE PLANS |
| | SUBMITTED MAY EFFECT THEIR ENERGY CALCULATION |
| | ASSUMPTIONS. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 3) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED |
| | THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING |
| | CONTRACTOR SHALL PROVIDE A NOTIRIZED LETTER INDICATING |
| | ALLOWING THE CONTRACTOR OF THE TENANT SPACE TO START |
| | WORK BEFORE THE CERTIFICATE OF COMPLETION OF THE BASE |
| | BUILDING HAS BEEN ACHIEVED. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 4) SHEET A0.01 THE FIRST FLOOR INDICATES AN ASSEMBLY |
| | OCCUPANCY WITH A 15 SQ FT PERSON, UNCONCENTRATED, |
| | PLEASE PROVIDE A FLOOR PLAN WITH TABLE AND CHAIRS AS |
| | WELL AS FOR COMMON PATH OF TRAVEL. SHEET A1.00 ALSO IS |
| | MISSING A LAYOUT OF FURNATURE. TABLE 1004.1.2 & 1013.3. |
| | |
| | 5) SHEET A1.00 PLEASE PROVIDE THE TENANT SEPERATION |
| | WALLS AND WALL RATINGS AS WELL AS THE COMMON AREAS, |
| | ALSO NOTE THE MECHANICAL MEZZANINE LEVEL WILL NEED TO |
| | SHOW WHERE THE TENANT SEPERATION WALL WILL BE LOCATED. |
| | SECTION 708.1. FIRE PARTITIONS, & TABLE 715.3. THIS |
| | SHEET DOES INDICATE THE WALL RATING OF THE TENANT WALL |
| | THAT DIVIDES THE PHOTO SHOP FROM THE MUSEUM BUT THE |
| | NORTH WALLS OF THE MUSEUM ARE NOT INDICATED ON THE |
| | PLANS. |
| | |
| | 6) SHEET A0.01 IT APPEARS THAT THE CORRIDOR OR HALL |
| | (1.07) IS AN EXIT ACCESS CORRIDOR SINCE THERE ARE EXIT |
| | SIGNS LEADING IN THE DIRECTION OF A 2HR RATED EXIT |
| | PASSAGEWAY THAT LEADS FROM THE STAIRWELL. NOTE THE |
| | CORRIDOR THAT LEADS BACK INTO THE CITY HALL PORTION OF |
| | THIS BUILDING IS NOT REQUIRED TO BE RATED, FIRE OR |
| | SMOKE, PER TABLE 1016.1. FOR A BUSINESS OCCUPANCY. BUT |
| | THE ASSEMBLY OCCUPANCY THAT IS NOW BEING DIRECTEDED |
| | INTO THIS CORRIDOR WILL REQUIRE A 1 HR FIRE RATING PER |
| | TABLE 1016.1. |
| | |
| | 7) SHEET A1.00 THE PHOTO SHOP ROOMS 1.12, 1.13 & 1.14 |
| | ALL NEED TO MEET THE REQUIREMENTS OF 1014.2.1 EXCEPTION |
| | (2). THE DOORS ARE TO BE NOT LESS THAN 1/3RD OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED. |
| | |
| | 8) SHEET A0.01, A1.00 OR A1.01 IDENTIFY THE DOOR |
| | OPENING NOR THE DOOR SIZE.106.1.2 / 715.3 & 1008.1.1. |
| | |
| | 9) SHEET A1.01 INDICATES THE CORRIDOR WALLS OR TENANT |
| | SEPERATION WALLS AS 1 HR RATED PARTITIONS BY OTHERS, |
| | THE CITY HALL APPROVED SET OF PLANS SHEET A1-2.2 DATE |
| | STAMPED MAY 8, 2008 IS THE LATEST REVISION OF THIS AREA |
| | AND DOES NOT INDICATE THESE WALLS. PLEASE COORDINATE |
| | PLANS WITH THE BASE BUILDING DESIGNER AS TO WHO WILL |
| | TAKE RESPONSIBILITY FOR THE DESIGN OF THIS AREA. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | 708.1 FIRE PARTITIONS, TENANT SEPERATION WALLS. |
| | |
| | 10) SHEET A1.01 THE EXISTING WALL LINE LOCATED ALONG |
| | SECTION LINE #5 ON THE BASE BUILDING SET OF PLANS WAS |
| | CONSIDERED NON-RATED, NON SEPERATED USE. NOW WITH A NEW |
| | TENANT THIS WALL WILL BECOME A TENANT SEPERATION WALL |
| | REQUIRING A 1 HOUR FIRE RATING, SEE SECTION 708.1. |
| | |
| | 11) SHEET A1.01 NOTE ON THE LEFT SIDE OF PLANS IT |
| | APPEARS TO BE A DISCREPANCY WITH THE WALL LEGEND ON THE |
| | RIGHT SIDE OF PAGE. THIS NOTE IS DIRECTED TO 1 HR FIRE |
| | RATING ON ALL TENANT SEPERATION WALLS BUT IS DIRECTED |
| | TO A INTERIOR WALL LOCATED WITHIN THE TENANT SPACE. |
| | DISCREPANCY. |
| | |
| | 12) SHEET A1.01 WITHIN THE PHOTORAPHY STUDIO THE PLANS |
| | INDICATE USE OF A SELF -SUPPORTING FOLDING PARTITION, |
| | NO STRUCTURAL MODIFICATIONS REQUIRED, PLEASE PROVIDE |
| | PRODUCT INFORMATION ON SUCH A SYSTEM, |
| | IS THIS SYSTEM SUPPORTED HOW? ADDITIONAL INFORMATION |
| | REQUIRED106.1.2 . |
| | |
| | 13) SHEET A1.01 ROOM# 2.21 THE PHOTOGRAPHY STUDIO |
| | SQUARE FOOTAGE IS 1711 SQ FT. THIS AREA APPEARS TO BE |
| | AN ASSEMBLY OCCUPANCY WHEN THE FOLDING PARTITION IS NOT |
| | IN USE. CLASSROOMS WTIH 20SQ FT PER |
| | OCCUPANT PUTS A LOAD OF 86 OCCUPANTS, WHERE AS IF THE |
| | USEAGE OF THE ROOM IS MORE IN LINE WITH A VOCATIONAL |
| | SHOP THE SQUARE FOOTAGE USED PER OCCUPANT OF 50 WOULD |
| | CREATE AN OCCUPANT LOAD OF 35. |
| | TABLE 1016.1 WOULD REQUIRE UNDER AN ASSEMBLY OCCUPANCY |
| | WHEN THE OCCUPANT LOAD IS EQUAL TO OR GREATER THAN 50 |
| | WOULD REQUIRE 1 HR RATED CORRIDORS.TABLE 1016.1 PLEASE |
| | PROVIDE A CODE ANYLISIS FOR THE SECOND FLOOR AS THE |
| | FIRST FLOOR. |
| | |
| | 14) SHEET A1.01 ROOM 2.21 THE LOUNGE INDICATES WHAT |
| | APPEARS TO BE A KITCHEN TYPE SINK, THERE ARE NO |
| | ELEVATIONS OF THIS CABINETRY, PLEASE VARIFY COMPLIANCE |
| | WITH: |
| | 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE |
| | COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH |
| | FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION |
| | 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW |
| | FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND |
| | SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH |
| | THE SINK. |
| | |
| | 15) SHEET A4.00 DETAIL GYPSUM SOFFITS, THE PLANS DO NOT |
| | DECLAIR WHAT TYPE OF FASTENER, OR FREQUENCY OF ANCHOR |
| | THE VARIOUS WIDTH SOFFITS TO THE STRUCTURAL DECK ABOVE? |
| | 106.1.2/ 2506.2 STANDARDS, |
| | TABLE 2506.2 & 1604.3.6 DEFLECTION LIMITATIONS. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |