| 2008-09-11 10:18:46 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | THE FOLLOWING COMMENTS HAVE BEEN GENERATED BASED ON THE |
| | REVIEW OF THE SUBMITTED PLANS AND SPECIFICATIONS UNDER |
| | THESE CODES: |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. IN ACCORDANCE WITH THE REQUIREMENTS FOR A LEVEL 2 |
| | ALTERATION, AS DECLARED ON PAGE LS.1, ALL RECONFIGURED |
| | SPACES INTENDED FOR OCCUPANCY IN ANY WORK AREA SHALL BE |
| | PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR |
| | EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL. SEE FBCEB 609.1. PROVIDE SPACE BY SPACE |
| | VENTILATION CALCULATIONS WITH OCCUPANCY CLASSIFICATION, |
| | OCCUPANT LOAD, VENTILATION REQUIRED AND VENTILATION |
| | PROVIDED IN ACCORDANCE WITH FBCM TABLE 403.3 OR SECTION |
| | 403.4. THE METHOD OF VENTILATION SHALL BE DECLARED ON |
| | THE PLANS. |
| | |
| | 2. PROVIDE DESIGN CFM ON THE PLANS FOR ALL AIR |
| | DISTRIBUTION DEVICES TO FACILITATE A TEST AND BALANCE |
| | OF THE SYSTEMS IN ACCORDANCE WITH FBCB |
| | 13-410.1.ABC.4.1. THIS IS ALSO NECESSARY TO CONFIRM |
| | VENTILATION RATES AS REQUIRED IN COMMENT #1 ABOVE AND |
| | TO SATISFY SPECIFICATIONS SECTION 15990 ON PAGE M0.1. |
| | |
| | 3. FIRE DAMPERS LOCATED WITHIN AIR DISTRIBUTION SYSTEMS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS |
| | OF THE MANUFACTURER?S INSTALLATION INSTRUCTIONS AND |
| | LISTING IN ACCORDANCE WITH FBCM 607.2. MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE ON THE JOB |
| | SITE AT THE TIME OF INSPECTION IN ACCORDANCE WITH THIS |
| | SECTION AND FBCM 304.1. |
| | |
| | 4. A MINIMUM OF TWO SETS OF PLANS SHALL BE SUBMITTED |
| | FOR REVIEW IN ACCORDANCE WITH FBCB 106.1. |
| | |
| | PLEASE RESPOND TO EACH COMMENT IN WRITING TO ASSIST IN |
| | FACILITATING A TIMELY REVIEW. PROVIDE A DESCRIPTION OF |
| | HOW EACH COMMENT WAS ADDRESSED AS WELL AS WHERE THE |
| | REQUESTED INFORMATION CAN BE FOUND. |
| | |