| 2008-09-11 16:56:19 | BUILDING PLAN REVIEW |
| | PERMIT: 08090087 |
| | ADD: 412 NORTHWOOD ROAD |
| | CONT: K.D.N. CONSTRUCTION |
| | TEL: (561)662-1002 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | SEPT. 11,2008 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C ) INFORMATIONAL FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, 2004 |
| | EXISTING BUILDING CODE, CHPTER 9 |
| | ADDITIONS. EXIST FBC 903.1 ADDITIONS TO EXISTING |
| | BUILDINGSOR STRUCTURES ARE NEW CONSTRUCTION AND SHALL |
| | COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2) PLEASE REVIEW INFORMAL CODE INTERPRETATION FROM THE |
| | 2001 FBC DEALING WITH CARPORTS AND THERE CLOSENESS TO |
| | PROPERTY LINES AND AMOUNT OF OPEN AREA OR OPENING |
| | LIMITATION. THE 2004 FBC TABLE 602 AND TABLE 704.8 |
| | FOOTNOTE"C" OPEN PARKING STRUCTURES WITH A FIRE |
| | SEPERATION DISTANCE GREATER THAN 10'-0" OPENINGS SHALL |
| | NOT BE LIMITED. WHEN IN THE CONSIDERATION OF REDESIGN |
| | THIS MAY BECOME A ENCLOSED |
| | GARAGE NEEDING TO MEET THE REQUIREMENTS OF 406.4 AND |
| | THE PERCENTAGE OF ALLOWABLE OPENINGS IN THE WALL NEXT |
| | TO THE ALLEYWAY. |
| | |
| | 3) PLEASE PROVIDE WIND DESIGN CRITERIA: 1603.1.4 WIND |
| | DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND |
| | LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS |
| | GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM |
| | OF THE BUILDING:MISSING INFORMATION: THE APPLICABLE |
| | ENCLOSURE CLASSIFICATIONS AND, IF DESIGNING WITH ASCE |
| | 7, INTERNAL PRESSURE COEFFICIENT. NOTE THIS IS NOT AN |
| | ENCLOED STRUCTURE. |
| | |
| | 4) SHEET A-3: |
| | |
| | 4A) DETAIL# 1 INDICATES FLOOR SLAB BUT THERE IS NO |
| | MENTION OF A VAPOR BARRIER NOR TERMITE TREATMENT . |
| | 1816.1(1-7). |
| | |
| | 4B) WEDGE ANCHORS- PLEASE PROVIDE PRODUCT APPROVAL |
| | SHOWING APPLICATION INTO HOLLOW BLOCK. DETAIL# 2 DOES |
| | NOT INDICATE THAT THE CONCRETE BLOCK ARE TO BE FILLED |
| | CELL.RULE 9B-72. WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 4C) SECTION# 1 NOR A2 INDICATE THE ROOF LIVE LOADS, |
| | DEFLECTION, SPECIES AND GRADE OF 2X10'S NOTE TWO LAYERS |
| | OF ROOF SHEATHING ARE ALSO INVOLVED. TABLE |
| | 2308.10.3(2). |
| | |
| | 5) ROOFING PRODUCT APPROVAL FL 735-R2 / NOA 07-0111.03 |
| | SUBSYSTEM INDICATED SYSTEMTYPE E WOOD NON-INSULATED |
| | DECK WITH TWO FASTENING OPTIONS OPTION#1 -52.5 PSF, |
| | GENERAL LIMITATION #7 AND OPTION |
| | # 2 -60.0PSF, WITH GENERAL LIMITATION # 7. |
| | 5A) PLEASE HIGHLIGHT AND OR CIRCLE WHICH SYSTEM SHALL |
| | BE INSTALLED. |
| | 5B) AS INDICATED ON SHEET A2 DETAIL "C" INDICATES IN |
| | ZONE 2 A -53 AND IN ZONE 3 A -89. DEPENDING ON WHICH |
| | SUBSYSTEM IS CHOSEN ZONE TWO MAY NEED ENHANCED |
| | FASTENING AND ZONE 3 WILL DEFINATELY NEED ENHANCED |
| | FASTENING. PLEASE PROVIDE RAS 117 CALCULATIONS |
| | INDICATING THE ENHANCED FASTENING FOR THESE ZONES. |
| | TABLE 1609.6.2.1(2). |
| | |
| | 6) NOTE: NO IMPACT FEES ARE REQUIRED. |
| | |
| | 7) STATE RADON FEES $6.42. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |