| 2008-09-19 11:57:20 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEETS 1, 2 & 4 OF 4, THE POOL AND AUX. POOL ARE NOT |
| | COMPLIANT WITH FBC-2004 BUILDING CHAPTER 4 (PRIVATE |
| | SWIMMING POOLS), SECTION 424.2.6.6.4 SUCTION INLETS PER |
| | PUMP. A MINIMUM OF TWO SUCTION INLETS SHALL BE PROVIDED |
| | FOR EACH PUMP IN THE SUCTION INLET SYSTEM, SEPARATED BY |
| | A MINIMUM OF 3 FEET (914 MM) OR LOCATED ON TWO |
| | DIFFERENT PLANES; I.E., ONE ON THE BOTTOM AND ONE ON |
| | THE VERTICAL WALL, OR ONE EACH ON TWO SEPARATE VERTICAL |
| | WALLS. THESE SUCTION INLETS SHALL BE PLUMBED SUCH THAT |
| | WATER IS DRAWN THROUGH THEM SIMULTANEOUSLY THROUGH A |
| | COMMON LINE TO THE PUMP. WHEN A SKIMMER IS USED IN |
| | CONJUNCTION WITH A SINGLE MAIN OUTLET TO MEET THE |
| | REQUIREMENTS OF THIS SECTION, THE COMMON SUCTION LINE |
| | MUST BE IN COMPLIANCE WITH SECTION 424.2.6.6.3 SUCH |
| | THAT A VACUUM CANNOT BE DRAWN ON ANY SINGLE MAIN OUTLET |
| | OR SKIMMER. |
| | *NOTE: SHEET 1 OF 4, POOL PLAN ONLY INDICATES ONE 8" X |
| | 32" MAIN DRAIN FOR THE POOL AND AUX. POOL. SHEET 2 OF 4 |
| | MAIN DRAIN DETAIL INDICATES ONE 8" X 32" MAIN DRAIN |
| | (MIN. TWO REQUIRED SEPERATED A MIN. 3'), HOWEVER THE |
| | AUX. POOL SECTION IS INDICATING (2) 8" AUX. POOL DRAINS |
| | W. APPROVED GRATES SECURED W. SCREWS. SHEET 4 OF 4, |
| | SCHEMATICS FOR THE POOL AND SPA ARE INDICATING |
| | "MAINDRAINS" AS IF MORE THAN ONE MAIN DRAIN IS BEING |
| | INSTALLED. PLEASE CORRECT AND CORRELATE PLANS COMPLIANT |
| | WITH SECTION 424.2.6.6.4. |
| | |
| | 2. FBC-2004 SEC. 424.2.12.1, OR |
| | FBCR-2004 SEC. R4101.12.1 PRESSURE |
| | TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| | NO AIR TEST SHALL BE APPROVED FOR PVC |
| | PIPE AND FITTINGS. (ADD TO NOTES) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |