Plan Review Notes
Plan Review Notes For Permit 08090055
Permit Number 08090055
Review Stop P
Sequence Number 2
Notes
Date Text
2008-10-24 10:30:59PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS
 THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. "OK" COMMENT ADDRESSED.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. SHEET A400 PLUMBING FIXTURE SCHEDULE: PLEASE KNOW
 THAT THE FIXTURES IN THE SCHEDULE REQUIRE THIRD-PARTY
 TESTING AND CERTIFICATION. PLEASE KNOW THAT FIXTURES
 LISTED IN THE SCHEDULE ARE NOT COMMONLY USED FIXTURES
 SUCH AS KOHLER OR AMERICAN STANDARD AND AN ONLINE
 SEARCH BY THIS PLANS EXAMINER FAILED TO COME UP WITH
 THE REQUIRED THIRD PARTY TESTING AND CERTIFICATIONS.
 PROVIDE MANUFACTURE SPECIFICATION SHEETS WITH THIS
 INFORMATION. PER FBC-2004 PLUMBING SECTION 303.4
 THIRD-PARTY TESTING AND CERTIFICATION.
 NOTE: THE FOLLOWING IS A LIST OF FIXTURES AND COMPLIANT
 THIRD-PARTY TESING AND CERTIFICATION STANDARDS
 MANUFACTURE SHEETS MUST INDICATE PER THE FBC-2004
 PLUMBING CODE SECTIONS.
  
 A} BATHTUBS= SECTION 407.1 APPROVAL. BATHTUBS SHALL
 CONFORM TO ANSI Z124.1, ASME A112.19.1M, ASME
 A112.19.4M, ASME A112.19.9M, CSA B45.2, CSA B45.3 OR
 CSA B45.5.
  
 B} LAVATORIES= SECTION 416.1 APPROVAL. LAVATORIES SHALL
 CONFORM TO ANSI Z124.3, ASME A112.19.1M, ASME
 A112.19.2M, ASME A112.19.3M, ASME A112.19.4M, ASME
 A112.19.9M, CSA B45.1, CSA B45.2, CSA B45.3 OR CSA
 B45.4. GROUP WASH-UP EQUIPMENT SHALL CONFORM TO THE
 REQUIREMENTS OF SECTION 402 . EVERY 20 INCHES (508 MM)
 OF RIM SPACE SHALL BE CONSIDERED AS ONE LAVATORY.
 SECTION 416.2 CULTURED MARBLE LAVATORIES. CULTURED
 MARBLE VANITY TOPS WITH AN INTEGRAL LAVATORY SHALL
 CONFORM TO ANSI Z124.3 OR CSA B45.5.
  
 C} SHOWER= SECTION 417.1 APPROVAL. PREFABRICATED
 SHOWERS AND SHOWER COMPARTMENTS SHALL CONFORM TO ANSI
 Z124.2, ASME A112.19.9M OR CSA B45.5. SHOWER VALVES FOR
 INDIVIDUAL SHOWERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION 424.4 .
  
 D} WATER CLOSET= SECTION 420.1 APPROVAL. WATER CLOSETS
 SHALL CONFORM TO THE WATER CONSUMPTION REQUIREMENTS OF
 SECTION 604.4 AND SHALL CONFORM TO ANSI Z124.4, ASME
 A112.19.2M, CSA B45.1, CSA B45.4 OR CSA B45.5. WATER
 CLOSETS SHALL CONFORM TO THE HYDRAULIC PERFORMANCE
 REQUIREMENTS OF ASME A112.19.6. WATER CLOSET TANKS
 SHALL CONFORM TO ANSI Z124.4, ASME A112.19.2, ASME
 A112.19.9M, CSA B45.1, CSA B45.4 OR CSA B45.5.
 ELECTRO-HYDRAULIC WATER CLOSETS SHALL COMPLY WITH ASME
 A112.19.13.
  
 E} FAUCETS AND OTHER FIXTURE FITTINGS SECTION 424.1
 APPROVAL. FAUCETS AND FIXTURE FITTINGS SHALL CONFORM TO
 ASME A112.18.1 OR CSA B125. FAUCETS AND FIXTURE
 FITTINGS THAT SUPPLY DRINKING WATER FOR HUMAN INGESTION
 SHALL CONFORM TO THE REQUIREMENTS OF NSF 61, SECTION 9.
 FLEXIBLE WATER CONNECTORS EXPOSED TO CONTINUOUS
 PRESSURE SHALL CONFORM TO THE REQUIREMENTS OF SECTION
 605.6 .
  
 F} SECTION 424.1.1 FAUCETS AND SUPPLY FITTINGS. FAUCETS
 AND SUPPLY FITTINGS SHALL CONFORM TO THE WATER
 CONSUMPTION REQUIREMENTS OF SECTION 604.4 .
  
 G} SECTION 424.1.2 WASTE FITTINGS. WASTE FITTINGS SHALL
 CONFORM TO ONE OF THE STANDARDS LISTED IN TABLES 702.1
 AND 702.4 FOR ABOVE-GROUND DRAINAGE AND VENT PIPE AND
 FITTINGS, OR THE WASTE FITTINGS SHALL BE CONSTRUCTED OF
 TUBULAR STAINLESS STEEL WITH A MINIMUM WALL THICKNESS
 OF 0.012 INCH (0.30 MM), TUBULAR COPPER ALLOY HAVING A
 MINIMUM WALL THICKNESS OF 0.027 INCH (0.69 MM) OR
 TUBULAR PLASTIC COMPLYING WITH ASTM F 409.
  
 H} SECTION 424.2 HAND SHOWERS. HAND-HELD SHOWERS SHALL
 CONFORM TO ASSE 1014 OR CSA B125.
  
 I} SECTION 424.3 SHOWER VALVES. SHOWER AND TUB-SHOWER
 COMBINATION VALVES SHALL BE BALANCED PRESSURE,
 THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016 OR CSA B125. SHOWER AND
 TUB-SHOWER COMBINATION VALVES AND MASTER THERMOSTATIC
 MIXING VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 J} SECTION 424.4 HOSE-CONNECTED OUTLETS. FAUCETS AND
 FIXTURE FITTINGS WITH HOSE-CONNECTED OUTLETS SHALL
 CONFORM TO ASME A112.18.3M.
  
 K} SECTION 424.5 TEMPERATURE-ACTUATED, FLOW REDUCTION
 VALVES FOR INDIVIDUAL FIXTURE FITTINGS.
 TEMPERATURE-ACTUATED, FLOW REDUCTION DEVICES, WHERE
 INSTALLED FOR INDIVIDUAL FIXTURE FITTINGS, SHALL
 CONFORM TO ASSE 1062. SUCH VALVES SHALL NOT BE USED
 ALONE AS A SUBSTITUTE FOR THE BALANCED PRESSURE,
 THERMOSTATIC OR COMBINATION SHOWER VALVES REQUIRED IN
 SECTION 424.3 .
  
 L} SECTION 424.6 TRANSFER VALVES. DECK-MOUNTED
 BATH/SHOWER TRANSFER VALVES CONTAINING AN INTEGRAL
 ATMOSPHERIC VACUUM BREAKER SHALL CONFORM TO THE
 REQUIREMENTS OF ASME A112.18.7.
  
 **RESPONSE NOTED, HOWEVER THE FOLLOWING ITEMS LISTED ON
 THE "PUMBING FIXTURE SCHDULE" ON SHEET NO. A400 WERE
 NOT LISTED IN THE REQUESTED MANUFACTURE SHEETS. PLEASE
 PROVIDE THE MANUFACTURE SHEETS AS REQUESTED OR REVISE
 THE PLUMBING FIXTURE SCHDULE. PLEASE KNOW THAT CLEARLY
 MARKED MANUFACTURE SHEETS WITH THE MODEL NUMBER OF THE
 FIXTURES BEING USED WOULD GREATLY HELP IN PLAN REVIEW
 TIME. PLEASE KNOW THAT ALL ITEMS WILL REMAIN ON THIS
 COMMENT AS SOME ITEMS ARE LISTED AS SPAREPARTS WITH NO
 EXPLANATION AS TO WHAT THEY ARE.
  
 **DORNBRACHT, 28011979-00, TARA HANDSHOWER SET.
 **DORNBRACHT, 09110311-00, TARA SPAREPARTS.
 **DORNBRACHT, 09.14.10.026.90, TARA SPAREPARTS-SEAL.
 **DORNBRACHT, 092722003-00, TARA SPAREPARTS. **LACAVA,
 5057-001, TWIN UNDERMOUNT SINK. **LACAVA, 7100-11-CR,
 POLISHED CHROME P-TRAP. **TOTO MS854114SL, WH ULTRAMAX
 TOILET ADA.
  
 4. "OK" COMMENT ADDRESSED.
  
 5. "OK" COMMENT ADDRESSED.
  
 6. "OK" COMMENT ADDRESSED.
  
 7. "OK" COMMENT ADDRESSED.
  
 8. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 **PLEASE CALL IF THERE ARE ANY QUESTIONS.
  