| Plan Review Notes For Permit 08090055 |
| Permit Number |
08090055 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-10-22 14:01:24 | ** DENIED REVIEW** | | | | | | 1) NOTE: THERE IS ONE MINOR COMMENT HOWEVER PLANS ARE | | | COMING BACK FOR COMMENTS FROM OTHER TRADES. AS A NEW | | | GUTTER IS BEING INSTALLED FROM THE METER TO THE TWO | | | EXISTING MAINS, PLEASE PROVIDE THE SIZE OF THE | | | CONDUCTOR WHICH WILL BE NEW INSTALLED FROM METER TO | | | GUTTER AND FROM GUTTER TO EACH MAIN. | | | 240.4,310.16,230.70. | | | | | | ** A CALL WAS PLACED TO TEELE AND ASSOCIATES AND LEFT | | | MESSAGE ON DAN'S VOICEMAIL. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|