Plan Review Notes
Plan Review Notes For Permit 08090055
Permit Number 08090055
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-22 14:01:24** DENIED REVIEW**
  
 1) NOTE: THERE IS ONE MINOR COMMENT HOWEVER PLANS ARE
 COMING BACK FOR COMMENTS FROM OTHER TRADES. AS A NEW
 GUTTER IS BEING INSTALLED FROM THE METER TO THE TWO
 EXISTING MAINS, PLEASE PROVIDE THE SIZE OF THE
 CONDUCTOR WHICH WILL BE NEW INSTALLED FROM METER TO
 GUTTER AND FROM GUTTER TO EACH MAIN.
 240.4,310.16,230.70.
  
 ** A CALL WAS PLACED TO TEELE AND ASSOCIATES AND LEFT
 MESSAGE ON DAN'S VOICEMAIL.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  