Plan Review Notes
Plan Review Notes For Permit 08090055
Permit Number 08090055
Review Stop B
Sequence Number 2
Notes
Date Text
2008-10-28 17:20:28RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FBC RESIDENTIAL WITH 2007 REVISIONS.
  
 1- ENERGY CALCULATIONS:
 A) ENGINEER WHO SIGNED AND SEALED ENERGY CALCULATIONS
 NEED TO PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 B) ENERGY CALCULATIONS FOR GARAGE/LIVING AREA STRUCTURE
 ARE NOT SIGNED AND SEALED AND THEY HAVE THE COPY OF THE
 ENGINEER SIGNATURE. THESE CALCULATIONS NEED TO HAVE
 ORIGINAL SIGNATURE-AND SEAL. AND PROVIDE ENGINEER'S
 INFORMATION AS REQUIRED BY SEC. 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 C) ENERGY CALCULATIONS FOR GARAGE/LIVING AREA STRUCTURE
 IS MISSING THE INFORMATION FOR GARAGE ADJACENT WALL
 AREA AND GARAGE ADJACENT CEILING AREA. PROVIDE COMPLETE
 INFORMATION AS REQUIRED.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS (TWO SETS. ONLY ONE SET WAS
 APPROVED AND STAMPED) AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 3- GUARDRAIL SYSTEM:
 A) DETAILS AND SPECIFICATIONS FOR ENGINEERED GUARDRAIL
 SYSTEM NEED TO HAVE ENGINEER'S ORIGINAL SEAL, SIGNATURE
 AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND
 SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 B) ENGINEER TO DESIGN THIS SYSTEM PER FBC 2004, WHICH
 IS THE CODE IN EFFECT. SPECIFY FBC 2004 WITH 2007
 REVISIONS ON BUILDING CODE DESIGN INFORMATION.
  
 C) ENGINEER TO IDENTIFY PROJECT ADDRESS.
  
 D) ENGINEER TO CLEARLY IDENTIFY ALL DESIGN INFORMATION
 INFORMATION THAT IS SPECIFIC TO THIS PROJECT. EG: GLASS
 THICKNESS, RAILING HEIGHT, WIND EXPOSURE, ETC. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SECTIONS . R301, R311.5 AND R312 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 4- CHIMNEY FLUE:
 A) REVISED DRAWING SHOWS THREE FLUES. THERE IS ONLY ONE
 APPLIANCE. COMPLY WITH SEC. R1001.10 OF 2004 FLORIDA
 RESIDENTIAL CODE. THIS SECTION ONLY ALLOWS TWO FLUES
 PER APPLIANCE.
  
 B) REVISE SIZE OF FLUE. SEE SEC. R1001.12.2. SIZE SHOWN
 ON DRAWINGS DON'T COMPLY. ALSO, PROVIDE CALCULATIONS
 SHOWING HOW FLUE SIZE WAS OBTAINED. INCLUDE FLUE HEIGHT
 MEASURED FROM FLOOR OF COMBUSTION CHAMBER TO TOP OF
 FLUE. SEE FIGURE R1001.12.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 C) REVIEW ISOKERN SPECIFICATIONS FOR FLUE LINING
 SUBMITTED. THEY DON'T PROVIDE INFORMATION FOR FLUE TO
 BE SPLIT INTO TWO (OR THREE AS SHOWN ON DRAWINGS).
 REVISE AS REQUIRED TO MATCH.
  
 5- NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF
 BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13
 FLORIDA STATUTE. PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT.
 ***NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT
 PICK UP TO AVOID EXPIRATION OF IT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712