| 2008-10-28 17:20:28 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FBC RESIDENTIAL WITH 2007 REVISIONS. |
| | |
| | 1- ENERGY CALCULATIONS: |
| | A) ENGINEER WHO SIGNED AND SEALED ENERGY CALCULATIONS |
| | NEED TO PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER |
| | 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | B) ENERGY CALCULATIONS FOR GARAGE/LIVING AREA STRUCTURE |
| | ARE NOT SIGNED AND SEALED AND THEY HAVE THE COPY OF THE |
| | ENGINEER SIGNATURE. THESE CALCULATIONS NEED TO HAVE |
| | ORIGINAL SIGNATURE-AND SEAL. AND PROVIDE ENGINEER'S |
| | INFORMATION AS REQUIRED BY SEC. 61G15-23.002 FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | C) ENERGY CALCULATIONS FOR GARAGE/LIVING AREA STRUCTURE |
| | IS MISSING THE INFORMATION FOR GARAGE ADJACENT WALL |
| | AREA AND GARAGE ADJACENT CEILING AREA. PROVIDE COMPLETE |
| | INFORMATION AS REQUIRED. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS (TWO SETS. ONLY ONE SET WAS |
| | APPROVED AND STAMPED) AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 3- GUARDRAIL SYSTEM: |
| | A) DETAILS AND SPECIFICATIONS FOR ENGINEERED GUARDRAIL |
| | SYSTEM NEED TO HAVE ENGINEER'S ORIGINAL SEAL, SIGNATURE |
| | AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND |
| | SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | B) ENGINEER TO DESIGN THIS SYSTEM PER FBC 2004, WHICH |
| | IS THE CODE IN EFFECT. SPECIFY FBC 2004 WITH 2007 |
| | REVISIONS ON BUILDING CODE DESIGN INFORMATION. |
| | |
| | C) ENGINEER TO IDENTIFY PROJECT ADDRESS. |
| | |
| | D) ENGINEER TO CLEARLY IDENTIFY ALL DESIGN INFORMATION |
| | INFORMATION THAT IS SPECIFIC TO THIS PROJECT. EG: GLASS |
| | THICKNESS, RAILING HEIGHT, WIND EXPOSURE, ETC. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY |
| | COMPLIANCE WITH SECTIONS . R301, R311.5 AND R312 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- CHIMNEY FLUE: |
| | A) REVISED DRAWING SHOWS THREE FLUES. THERE IS ONLY ONE |
| | APPLIANCE. COMPLY WITH SEC. R1001.10 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. THIS SECTION ONLY ALLOWS TWO FLUES |
| | PER APPLIANCE. |
| | |
| | B) REVISE SIZE OF FLUE. SEE SEC. R1001.12.2. SIZE SHOWN |
| | ON DRAWINGS DON'T COMPLY. ALSO, PROVIDE CALCULATIONS |
| | SHOWING HOW FLUE SIZE WAS OBTAINED. INCLUDE FLUE HEIGHT |
| | MEASURED FROM FLOOR OF COMBUSTION CHAMBER TO TOP OF |
| | FLUE. SEE FIGURE R1001.12.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | C) REVIEW ISOKERN SPECIFICATIONS FOR FLUE LINING |
| | SUBMITTED. THEY DON'T PROVIDE INFORMATION FOR FLUE TO |
| | BE SPLIT INTO TWO (OR THREE AS SHOWN ON DRAWINGS). |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | 5- NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF |
| | BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13 |
| | FLORIDA STATUTE. PROVIDE RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | ***NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT |
| | PICK UP TO AVOID EXPIRATION OF IT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |