2008-09-15 11:04:24GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
 NOTE: ALL COMMENTS ARE PER THE MAIN HOUSE GAS RISER
 DIAGRAM LOCATED ON SHEET P201.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS WITH NO
 CORRESPONDING LENGTHS INDICATED AND COMPLY ON THE
 RESUBMITTAL.
  
 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED ON THE RESUBMITTAL. PER FBC-2004 FUEL GAS
 SECTION 401.1 SCOPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1 AND COMPLY.
  
 4. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE LIVING
 ROOM (ROOM #108) GAS FIRE PLACE PER FBC-2004 FUEL GAS
 CODE SECTION 304.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: THE MP REGULATORS MANUFACTURER SHEETS SHALL
 CLEARLY INDICATE THE MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY AND A LISTING FROM A RECOGNIZED TESTING
 LABORATORY (LISTING EXAMPLES= CSA, AGA OR UL). THE
 SUBMITTED REAL-FYRE GAS LOG MANUFACTURE SHEETS DO NOT
 COMPLY WITH THE FOLLOWING. LOG LIGHTERS SHALL BE TESTED
 IN ACCORDANCE WITH CSA 8. PER FBC-2004 FUEL GAS CODE
 SECTION 603.1 GENERAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]