| 2008-09-11 16:30:13 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON ELECTRICAL PLANS. |
| | 2004 FBC W/ 2007 REVISIONS |
| | 2004 RESIDENTIAL CODE |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE VERIFY THE SMOKE DETECTION DEVICES. THE |
| | PLANS CALL FOR *SMOKE DETECTORS* WHICH BY DEFINITION IN |
| | NFPA-72 ARE DEVICES WHICH WILL DETECT HOWEVER NOT SOUND |
| | AN ALARM. SMOKE ALARM (SA)DEVICES ARE DEVICES WHICH |
| | DETECT AND SOUND AN ALARM. PLEASE SEE FBC 907, |
| | RESIDENTIAL CODE R313 AND NFPA-72 11.5.1.1, 11.8.3. |
| | IF THESE DEVICES ARE INDEED SMOKE DETECTORS PLEASE |
| | COMPLETE WITH FIRE ALARM PANEL, HORNS/SOUNDING DEVICES |
| | ETC. |
| | |
| | 3) NOTE: PLEASE SEE THE HALLWAY UPSTAIRS AND DOWN |
| | STAIRS WILL REQUIRE SOME SORT OF LIGHTING FIXTURES FOR |
| | EGRESS. |
| | THIS IS ALSO FOR ROOMS 210 AND 201. EITHER HALF SWITCH |
| | RECEPTACLE OR SOME SORT OF LISTED LIGHT FIXTURE. |
| | 210.70, LS 101 7.8 |
| | |
| | 4) NOTE: PLEASE PLACE NOTE ON FIXTURE LEGEND FOR THE |
| | TYPE OF RECESSED LIGHTS TO MEET FBC 13-606.1.ABC.1.2.4 |
| | |
| | 5) NOTE: PLEASE CLARIFY THE DINING AREA/BREAKFAST AREA |
| | IF ANY ON PLANS. PLEASE SEE 210.52B1, 210.11C1 AND |
| | 220.52 FOR CIRCUITING AND LOADS TO BE FIGURED FOR THE |
| | RECEPTACLES CIRCUITS IN THESE AREAS. |
| | |
| | 6) NOTE: PLEASE CLARIFY THE 125AMP 42 MLO. PLEASE |
| | VERIFY THAT THIS PANEL IS 42CIRCUITS AT 125AMP RATED. |
| | 110.3, 90.7. |
| | |
| | 7) NOTE: PLEASE COORDINATE INFORMATION ON PANEL |
| | SCHEDULE *A* FOR PANEL *B*. PLEASE SEE PANEL *B* |
| | SCHEDULE AS THIS INDICATES THE FEEDERS AS #3'S YET THE |
| | PANEL SCHEDULE ON PANEL *A* INDICATES #6 ON A 100AMP |
| | RATED BREAKER. |
| | 240.4,310.16, 215.5 ETC |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 8) NOTE: PLEASE COORDINATE RISER AND FEEDERS FOR PANEL |
| | *G1* AS THE RISER INDICATES #3'S IN AN 1 1/4 INCH |
| | CONDUIT YET THE PANEL *G1* NOTES FEEDERS AS #1'S AND 1 |
| | 1/2 INCH CONDUIT. |
| | 240.4, 310.16, 215.5 |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 9) NOTE: PLEASE LIST ALL OF THE REQUIRED ARC FAULT |
| | PROTECTED CIRCUITS. THE PANEL SCHEDULE(S) LIST AFCI |
| | PROTECTION FOR RECEPTACLES HOWEVER BASED ON THE 2002 |
| | NEC AND 2005 NEC 210.12 REQUIRES PROTECTION ON ALL |
| | OUTLETS IN THESE AREAS. THIS INCLUDES RECEPTACLES, |
| | LIGHTS FANS , SMOKE ALARMS (120V) ETC. ALL OUTLETS. |
| | |
| | 10) NOTE: PLEASE ADJUST PANEL SCHEDULES SO THE |
| | CIRCUITING IS SPECIFIC TO ROOMS AND AREAS IN WHICH THEY |
| | FEED. THE USE OF *GENERAL RECEPTACLES* GENERAL |
| | LIGHTING* IS NOT ACCEPTABLE. PLEASE SEE THIS WAS A |
| | CHANGE IN THE 2005 NEC WHICH REQUIRES SPECIFIC. THE |
| | FOLLOWING IS TEXT TAKEN DIRECTLY FROM THE NEC. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 11) NOTE: PLEASE SEE 210.70 FOR AREAS IN WHICH AIR |
| | HANDLER UNITS ARE LOCATED WHICH APPEAR TO ABOVE |
| | CEILING(S) IN ATTIC AREAS WHICH REQUIRED SERVICE |
| | LIGHTS. |
| | AN EXAMPLE WOULD BE AHU #2. |
| | |
| | 12) NOTE: PLEASE SEE 410.8 FOR ASSUMED SHELVING AREAS |
| | IN CLOSETS AND MINIMUM REQUIRED CLEARANCES FOR FIXTURES |
| | FROM COMBUSTIBLES. PLEASE SEE LINEN CLOSET 212 FOR |
| | EXAMPLE AS BASED ON THE SIZE OF THE CLOSET AND THE |
| | ASSUMED DISTANCE FOR SHELVING IN THE NEC, THIS FIXTURE |
| | ABOVE THE DOOR APPEARS IT MAY BE TOO CLOSE. PLEASE |
| | VERIFY THIS AND PROVIDE INFORMATION. |
| | IF THIS HAD BEEN THE ONLY COMMENT IT WOULD HAVE BEEN |
| | REDLINED AND VIF. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |