Plan Review Notes
Plan Review Notes For Permit 08090055
Permit Number 08090055
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-11 16:30:13 
  
  
  
 ** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS.
 2004 FBC W/ 2007 REVISIONS
 2004 RESIDENTIAL CODE
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE VERIFY THE SMOKE DETECTION DEVICES. THE
 PLANS CALL FOR *SMOKE DETECTORS* WHICH BY DEFINITION IN
 NFPA-72 ARE DEVICES WHICH WILL DETECT HOWEVER NOT SOUND
 AN ALARM. SMOKE ALARM (SA)DEVICES ARE DEVICES WHICH
 DETECT AND SOUND AN ALARM. PLEASE SEE FBC 907,
 RESIDENTIAL CODE R313 AND NFPA-72 11.5.1.1, 11.8.3.
 IF THESE DEVICES ARE INDEED SMOKE DETECTORS PLEASE
 COMPLETE WITH FIRE ALARM PANEL, HORNS/SOUNDING DEVICES
 ETC.
  
 3) NOTE: PLEASE SEE THE HALLWAY UPSTAIRS AND DOWN
 STAIRS WILL REQUIRE SOME SORT OF LIGHTING FIXTURES FOR
 EGRESS.
 THIS IS ALSO FOR ROOMS 210 AND 201. EITHER HALF SWITCH
 RECEPTACLE OR SOME SORT OF LISTED LIGHT FIXTURE.
 210.70, LS 101 7.8
  
 4) NOTE: PLEASE PLACE NOTE ON FIXTURE LEGEND FOR THE
 TYPE OF RECESSED LIGHTS TO MEET FBC 13-606.1.ABC.1.2.4
  
 5) NOTE: PLEASE CLARIFY THE DINING AREA/BREAKFAST AREA
 IF ANY ON PLANS. PLEASE SEE 210.52B1, 210.11C1 AND
 220.52 FOR CIRCUITING AND LOADS TO BE FIGURED FOR THE
 RECEPTACLES CIRCUITS IN THESE AREAS.
  
 6) NOTE: PLEASE CLARIFY THE 125AMP 42 MLO. PLEASE
 VERIFY THAT THIS PANEL IS 42CIRCUITS AT 125AMP RATED.
 110.3, 90.7.
  
 7) NOTE: PLEASE COORDINATE INFORMATION ON PANEL
 SCHEDULE *A* FOR PANEL *B*. PLEASE SEE PANEL *B*
 SCHEDULE AS THIS INDICATES THE FEEDERS AS #3'S YET THE
 PANEL SCHEDULE ON PANEL *A* INDICATES #6 ON A 100AMP
 RATED BREAKER.
 240.4,310.16, 215.5 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 8) NOTE: PLEASE COORDINATE RISER AND FEEDERS FOR PANEL
 *G1* AS THE RISER INDICATES #3'S IN AN 1 1/4 INCH
 CONDUIT YET THE PANEL *G1* NOTES FEEDERS AS #1'S AND 1
 1/2 INCH CONDUIT.
 240.4, 310.16, 215.5
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 9) NOTE: PLEASE LIST ALL OF THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS. THE PANEL SCHEDULE(S) LIST AFCI
 PROTECTION FOR RECEPTACLES HOWEVER BASED ON THE 2002
 NEC AND 2005 NEC 210.12 REQUIRES PROTECTION ON ALL
 OUTLETS IN THESE AREAS. THIS INCLUDES RECEPTACLES,
 LIGHTS FANS , SMOKE ALARMS (120V) ETC. ALL OUTLETS.
  
 10) NOTE: PLEASE ADJUST PANEL SCHEDULES SO THE
 CIRCUITING IS SPECIFIC TO ROOMS AND AREAS IN WHICH THEY
 FEED. THE USE OF *GENERAL RECEPTACLES* GENERAL
 LIGHTING* IS NOT ACCEPTABLE. PLEASE SEE THIS WAS A
 CHANGE IN THE 2005 NEC WHICH REQUIRES SPECIFIC. THE
 FOLLOWING IS TEXT TAKEN DIRECTLY FROM THE NEC.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 11) NOTE: PLEASE SEE 210.70 FOR AREAS IN WHICH AIR
 HANDLER UNITS ARE LOCATED WHICH APPEAR TO ABOVE
 CEILING(S) IN ATTIC AREAS WHICH REQUIRED SERVICE
 LIGHTS.
 AN EXAMPLE WOULD BE AHU #2.
  
 12) NOTE: PLEASE SEE 410.8 FOR ASSUMED SHELVING AREAS
 IN CLOSETS AND MINIMUM REQUIRED CLEARANCES FOR FIXTURES
 FROM COMBUSTIBLES. PLEASE SEE LINEN CLOSET 212 FOR
 EXAMPLE AS BASED ON THE SIZE OF THE CLOSET AND THE
 ASSUMED DISTANCE FOR SHELVING IN THE NEC, THIS FIXTURE
 ABOVE THE DOOR APPEARS IT MAY BE TOO CLOSE. PLEASE
 VERIFY THIS AND PROVIDE INFORMATION.
 IF THIS HAD BEEN THE ONLY COMMENT IT WOULD HAVE BEEN
 REDLINED AND VIF.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  