| 2008-09-16 17:02:56 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND 2004 FBC |
| | WITH 2007 REVISIONS. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N JOG RD. |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE FOR THE |
| | CHANGE OF USE ON THE FIRST FLOOR OF GARAGE BUILDING. |
| | BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF |
| | FEES ARE DUE. |
| | |
| | 2- HOUSE IS LOCATED IN FLOOD ZONE A5 WITH BASE FLOOD |
| | ELEVATION OF 7.0'. NEED TO ELEVATE FINISH FLOOR |
| | BUILDING ON BOTH BUILDINGS UP TO 7.5' MINIMUM AS |
| | REQUIRED BY CITY ORDINANCE SEC. 94-546(B)(1). SURVEY |
| | SUBMITTED STATES FINISH FLOOR ELEVATION OF 6.89' FOR |
| | GARAGE BUILDING AND 7.42' FOR MAIN HOUSE. THESE FINISH |
| | FLOOR ELEVATIONS NEED TO BE RAISED. |
| | ***NOTE: ELEVATION CERTIFICATE WILL BE REQUIRED TO |
| | VERIFY FINISH FLOOR ELEVATION. |
| | |
| | 3- PROVIDE COMPLETE SPECIFICATIONS FOR OUTDOOR |
| | FIREPLACE AND PROVIDE DOCUMENTATION TO CLARIFY WHY |
| | CHIMNEY IS NOT REQUIRED FOR THIS TYPE OF FIREPLACE. |
| | |
| | 4- WINDERS IN GARAGE STAIRS NEED TO COMPLY WITH SEC. |
| | R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL CODE. COMPLY |
| | WITH THE MIN. 6" WINDERS AT NARROWER END. SEE ATTACHED |
| | PICTURE FROM COMMENTARY CODE. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) INSWING ENTRY DOORS WITH SIZE AS SHOWN ON PLANS. |
| | |
| | B) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS. |
| | ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED |
| | TO SUBMIT COMPLETE REPORT. |
| | |
| | C) CLARIFY WHERE IS DOOR WITH FLORIDA PRODUCT APPROVAL |
| | FL3030-R2 GOING TO BE INSTALLED. AND, CHECK DESIGN |
| | PRESSURES WITH THOSE CALCULATED BY THE ENGINEER OF |
| | RECORD TO MAKE SURE THEY WILL BE OK FOR THIS PROJECT. |
| | |
| | D) CLARIFY WHERE IS DOOR WITH FLORIDA PRODUCT APPROVAL |
| | FL4940 GOING TO BE INSTALLED. IF IT'S FOR GARAGE SIDE |
| | DOOR, THEN NEED TO PROVIDE ANOTHER PRODUCT APPROVAL |
| | BECAUSE THIS ONE DOESN'T MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER. |
| | |
| | E) GARAGE OVERHEAD DOORS: FLORIDA PRODUCT APPROVAL |
| | FL1652 SUBMITTED DOESN'T RESIST THE CALCULATED DESIGN |
| | PRESSURES. |
| | |
| | 6- ROLLADEN ROLL SHUTTERS: |
| | A) PROVIDE COMPLETE INSTALLATION SCHEDULE AS REQUIRED |
| | BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS |
| | IMPACT PROTECTION. SEE ATTACHED COPY. |
| | B) COMPLETE INFORMATION ON SHEET 21 OF 21 OF NOA |
| | 08-0313.07 SUBMITTED. |
| | C) CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC CHARTS TO |
| | BE USED TO VERIFY COMPLIANCE WITH PRODUCT APPROVAL AND |
| | PROPOSED INSTALLATION. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- ENERGY CALCULATIONS: |
| | A) COMPLETE INFORMATION ON TOP. INCLUDING BUILDER |
| | INFORMATION. |
| | B) THIS IS NOT NEW CONSTRUCTION OR ADDITION, BUT |
| | EXISTING. ENERGY CALCULATIONS FOR MAIN HOUSE AND GARAGE |
| | BUILDING NEED TO BE REVISED ACCORDINGLY. |
| | C) CLARIFY WHY THE WALL R-VALUE IS R=2.0 FOR GARAGE |
| | BUILDING. |
| | |
| | 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW |
| | HANDRAILS AND FOR NEW BALCONY GLASS GUARDRAILS TO |
| | VERIFY COMPLIANCE WITH TABLE R301.5, SEC. R311.5 AND |
| | SEC. R312 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 10- PROVIDE COMPLETE DOCUMENTATION SHOWING HOW CHIMNEY |
| | FLUE COMPLIES WITH FIGURE R1001.12.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 11- SPECIFY HOW IS THE ROOF TILE GOING TO BE FASTENED |
| | AS REQUIRED BY SEC. 106.1.1.2 OF CITY AMENDMENTS TO FBC |
| | 2004. CHECK PRODUCT APPROVAL FOR PROPER PRODUCT TO BE |
| | USED TO RESIST THE CALCULATED UPLIFT LOADS. IF USING |
| | ANY TYPE OF ADHESIVE THEN PROVIDE SUCH PRODUCT |
| | APPROVAL. IF USING SCREWS, THEN SPECIFY SIZE AND NUMBER |
| | OF THEM. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |