| Date |
Text |
| 2009-03-26 17:04:55 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | SECOND CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED LATER AT TIME OF PERMIT |
| | PICK UP. |
| | |
| | 2- A) PERMIT VALUATION DECLARED IN THE PERMIT |
| | APPLICATION IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO |
| | FBC. UPDATE VALUATION TO INCLUDE ALL SCOPE OF WORK |
| | SHOWN ON PLANS AND INCLUDE ENGINEER PROFESSIONAL FEES |
| | ALSO. (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | B) UPDATE NAME OF OWNER. PERMIT APPLICATION SAYS ONE |
| | PERSON. PLANS AND PROPERTY APPRAISAL SAYS ANOTHER. |
| | CLARIFY/REVISE AS REQUIRED. (REPEAT COMMENT. NOT |
| | ADDRESSED AT ALL). |
| | |
| | 3- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. (REPEAT |
| | COMMENT). |
| | |
| | B) ACCORDING TO FORM 600A-2004R SUBMITTED THE ENTIRE |
| | HOUSE IS COMPLYING WITH THE ENERGY CODE. SEE SQUARE |
| | FOOTAGE SHOWN ON ITEM #6. CLARIFY AND PROVIDE PROOF |
| | THAT ENTIRE BUILDING COMPLIES WITH THE CODE. OTHERWISE |
| | CONCENTRATE ON ADDITION AND NEW COMPONENTS TO BE |
| | INSTALLED ONLY. NOTE: A DIFFERENT PRESCRIPTIVE FORM FOR |
| | SMALL ADDITIONS MAY BE USED ALSO. |
| | |
| | ***NOTE: READ SEC. 13-600.2.A.3.1. AND SEC. |
| | 13-600.2.A.3.2 OF FBC 2004 TO SEE WHICH METHOD WILL BE |
| | PROVIDED TO COMPLY WITH CHAPTER 13 FBC. |
| | |
| | C) IF ITEM #7B IS USING SHGC=0.5 ON DOOR AND WINDOWS, |
| | THEN NEED TO PROVIDE PROOF THAT GLASS ON WINDOWS/DOORS |
| | PROVIDE THAT SHGC FACTOR. OTHERWISE, USE THE DEFAULT |
| | FACTOR OF THE ENERGY CALCULATIONS PROGRAM. |
| | |
| | D) REVISE CEILING TYPE ON ITEM #10A. THIS HOUSE HAS A |
| | FLAT CEILING. FLAT CEILING DOESN'T PROVIDE UNDER ATTIC |
| | AREA. REVISE AS REQUIRED. SEE CHAPTER 13 FBC 2004 FOR |
| | PROPER TYPE OF CEILING TO BE SPECIFIED. |
| | |
| | E) IF TAKING THE CEILING FAN CREDIT ON ITEM #15, THEN |
| | CEILING FANS MUST BE INSTALLED ON ALL ROOMS AS REQUIRED |
| | BY TABLE 13-607.1.A.1 FBC 2004. |
| | |
| | F) REVISE OWNER INFORMATION. COORDINATE WITH PERMIT |
| | APPLICATION AND PLANS. ALSO, PROVIDE COMPLETE |
| | INFORMATION ON TOP OF FORM. |
| | |
| | G) REVISE ITEM #3. THIS IS NOT A MULTIFAMILY. |
| | |
| | 4- ENERGY CALCULATIONS SUBMITTED ARE TAKEN THE CEILING |
| | FAN CREDIT. SEE ITEM #15. NEED TO SPECIFY ON PLANS SIZE |
| | OF CEILING FAN ON EACH ROOM TO COMPLY WITH THE |
| | REQUIREMENTS OF TABLE 13-607.1.A.1 OF FBC 2004. |
| | |
| | 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) FLAT ROOF. AND, CLEARLY IDENTIFY SPECIFIC APPROVED |
| | ASSEMBLY TO BE INSTALLED AND SPECIFIC BASE SHEET |
| | FASTENING OPTION. PROVIDE RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7. SEE GENERAL |
| | LIMITATIONS ON LAST PAGE OF DADE COUNTY NOA. IF RAS 117 |
| | CALCULATIONS ARE REQUIRED TO BE SIGNED AND SEALED, THEN |
| | PROVIDE SIGNED AND SEALED CALCULATIONS. (REPEAT |
| | COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | B) ROOF SHINGLES AS SHOWN ON SHEET S-5. (REPEAT |
| | COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. THIS |
| | APPLIES TO STRUCTURAL CONNECTORS ONLY. OTHER PRODUCT |
| | APPROVALS REQUIRED COMPLETE REPORT. (REPEAT COMMENT). |
| | INFORMATION SUBMITTED ON CONNECTOR SCHEDULE ON SHEET |
| | S-2 MAKES NO SENSE. THERE ARE NOT NOA'S OR FLORIDA |
| | PRODUCT APPROVALS AS SPECIFIED ON THIS SCHEDULE. WHERE |
| | ARE F22, IL8, L9 F16, F6 AND F8 TAKEN FROM? |
| | |
| | D) STORM SHUTTERS: PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. AND, ON NOA 08-0527.09 |
| | SUBMITTED MARK SPECIFIC MOUNTING CONDITIONS (EG: WALLL |
| | MOUNTED, BUILD OUT, ETC) AND SPECIFIC ANCHOR TYPE AND |
| | SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. (REPEAT COMMENT. NOT ADDRESSED AT ALL). PRODUCT |
| | APPROVAL WAS NOT SUBMITTED THIS TIME AND THE REST OF |
| | THE INFORMATION WAS NOT PROVIDED AT ALL. |
| | |
| | E) SINGLE HUNG WINDOWS. CHECK WINDOW SIZES AND DESIGN |
| | PRESSURES SHOWN ON NOA 05-1003.10 SUBMITTED WITH SIZES |
| | AND DESIGN PRESSURES SHOWN ON PLANS. PRODUCT APPROVAL |
| | CAN NOT BE USED FOR PROPOSED SIZES. (REPEAT COMMENT). |
| | NOA 05-1003.10 SUBMITTED IS MISSING SHEET 1 OF 4. THIS |
| | SHEET SHOWS THE DESIGN PRESSURES AND SIZE OF WINDOWS. |
| | THIS PRODUCT APPROVAL IS NOT GOOD FOR SIZE OF WINDOWS |
| | SHOWN ON WINDOW SCHEDULE. PROVIDE PRODUCT APPROVAL THAT |
| | COVER SIZE OF WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | F) ENTRY DOOR. SEE EXTERIOR ELEVATIONS. NO PRODUCT |
| | APPROVAL SUBMITTED THIS TIME. |
| | |
| | G) REAR FRENCH DOORS. SEE EXTERIOR ELEVATIONS. NO |
| | PRODUCT APPROVAL SUBMITTED THIS TIME. |
| | |
| | H) REAR DOOR BY DEN AREA. SEE EXTERIOR ELEVATIONS. NO |
| | PRODUCT APPROVAL SUBMITTED THIS TIME. |
| | |
| | I) WINDOW MULLIONS. NO PRODUCT APPROVAL SUBMITTED THIS |
| | TIME. ALSO, MARK ON PRODUCT APPROVAL DRAWINGS SPECIFIC |
| | SIZE AND FASTENERS TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | J) EXTERIOR DOOR FOR WATER HEATER STORAGE AREA. |
| | |
| | K) ARCHED WINDOW AS SHOWN ON FRONT ELEVATION. NO |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVED IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | (REPEAT COMMENT). ENGINEER PROVIDED LETTER STATING "THE |
| | PRODUCT APPROVALS FOR ALL THE WINDOWS AND DOORS FOR |
| | THIS RESIDENCE HAVE BEEN REVIEWED AND ARE IN ACCORDANCE |
| | WITH THE 2004 FLORIDA BUILDING CODE, INCLUDING THE 2006 |
| | AMENDMENTS". THIS LETTER IS NOT ACCEPTABLE. THIS |
| | STATEMENT IS TOO GENERAL AND IT DOESN'T IDENTIFY WHICH |
| | SPECIFIC PRODUCT APPROVALS HE REVIEWED. THERE ARE EVEN |
| | PRODUCT APPROVALS THAT CONTRACTOR DIDN'T SUBMIT WITH |
| | PERMIT PACKAGE. ALSO, THERE ARE OTHER PRODUCT APPROVALS |
| | LIKE SHINGLES, MULLIONS, STRUCTURAL CONNECTORS, |
| | SHUTTERS, FLAT ROOF ASSEMBLY THAT ENGINEER DOESN'T EVEN |
| | MENTION. ENGINEER OF RECORD NEED TO REVIEW AND APPROVE |
| | IN WRITING (NOT SIGNING AND SEALING) EACH INDIVIDUAL |
| | PRODUCT APPROVAL. IF USING LETTER TO IDENTIFY PRODUCT |
| | APPROVALS, THEN LIST ALL THE PRODUCT APPROVALS NUMBERS |
| | AND SPECIFIC MODEL/TYPE REVIEWED. AN STANDARD REVIEW |
| | STAMP ON EACH PRODUCT APPROVAL MAY BE USED ALSO. |
| | |
| | 7- SHEET S-2: |
| | A) REVISE ROOF FRAMING PLAN NOTE #3: ROOF ZONE 3 |
| | REQUIRES 4" O.C. 8D RING SHANK NAILS IN ROOF ZONE 3. AS |
| | REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. REVISE AS REQUIRED AND IDENTIFY ROOF ZONE #3. |
| | (REPEAT COMMENT). ROOF ZONE 3 REQUIRES 8D RING SHANK |
| | NAILS AT 4"O.C. MIN. ALSO, CLEARLY IDENTIFY ROOF ZONE |
| | 3. |
| | ***NOTE: REVISE CARPENTRY NOTE #12 ON SHEET S-0 AS |
| | WELL. |
| | |
| | B) REVISE SIZE OF ROOF MEMBER AND LEDGERS TO MATCH |
| | SIZES SHOWN ON DETAIL SECTIONS 5 AND 6 OF SHEET S-5. |
| | SEE ROOF FRAMING PLANS AND DETAILS AND COORDINATE AS |
| | REQUIRED TO MATCH. |
| | |
| | C) REVISE CONNECTOR SCHEDULE. WHERE ARE THE NOA NUMBERS |
| | TAKEN FROM?. THERE ARE NOT F22, IL8, L9, F6, F16 OR F8 |
| | NUMBERS. |
| | |
| | 8- SHEET S-3: |
| | A) HOW IS ACCESS PROVIDED FOR THE NEW GAS WATER HEATER |
| | CLOSET. SEE CHAPTER 24 OF 2004 FLORIDA RESIDENTIAL CODE |
| | FOR PROHIBITED LOCATIONS. ALSO, PROVIDE ALL THE |
| | PERTINENT INFORMATION FOR PLUMBING REVIEW. (REPEAT |
| | COMMENT). FLOOR PLANS DON'T SHOW ANY DOOR, BUT EXTERIOR |
| | ELEVATIONS SHOW AN EXTERIOR DOOR. REVISE PLANS AS |
| | REQUIRED TO MATCH AND PROVIDE PRODUCT APPROVAL FOR |
| | DOOR. |
| | |
| | B) PROVIDE ACTUAL CALCULATIONS FOR THE DESIGN PRESSURES |
| | OF DOORS AND WINDOWS TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. DESIGN PRESSURES PROVIDED ARE THE |
| | SAME FOR OPENINGS LOCATED ON INTERIOR OR END ZONE. |
| | OPENINGS ON END ZONES HAVE HIGHER DESIGN PRESSURES. |
| | CLEARLY IDENTIFY OPENINGS ON END ZONES AND PROVIDE |
| | CORRESPONDING DESIGN PRESSURES. |
| | |
| | C) SPECIFY SAFETY GLASS IN WINDOW NEXT TO THE DOOR IN |
| | NEW DEN AREA AND BY BATH TUB AREA. SEC. R308.4 2004 |
| | FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). ENGINEER |
| | RESPONDED THAT WINDOW TO HAVE IMPACT GLASS. PRODUCT |
| | APPROVAL SUBMITTED IS FOR NON-IMPACT GLASS. CLARIFY |
| | REVISE AS REQUIRED. |
| | |
| | D) SHOW THE EXTERIOR LANDINGS, STEPS AND RAILINGS TO |
| | VERIFY COMPLIANCE WITH SEC. R311.4.3, R311.5 AND R312 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). |
| | ENGINEER RESPONSE WAS THAT DETAILS WERE ON SHEET S-5. |
| | DETAILS ON SHEET S-5 ARE STILL NO PROVIDING ALL THE |
| | REQUIRED INFORMATION. |
| | **ALSO, FLOOR PLANS NEED TO SHOW THE LOCATION AND |
| | DIMENSIONS FOR THE STAIRS. PLANS SUBMITTED DON'T |
| | PROVIDE THIS INFORMATION. |
| | |
| | 9- SHEET S-4: |
| | A) ALL THE ELEVATIONS SHOWN ON THIS SHEET DON'T MATCH |
| | FLOOR PLANS. REVISE AS REQUIRED. (REPEAT COMMENT). |
| | ENGINEER RESPONDED THAT PHOTOS HAVE BEEN SUBSTITUTED |
| | FOR ELEVATIONS. PHOTOS WERE NOT SUBMITTED BUT |
| | REGARDLESS ELEVATIONS AND FLOOR PLANS NEED TO MATCH |
| | ANYWAY. |
| | |
| | B) REVISE DOOR AND WINDOWS DESIGN PRESSURES. COORDINATE |
| | WITH ITEM 8B ABOVE. (REPEAT COMMENT). NEED CORRECT |
| | DESIGN PRESSURES FOR END AND INTERIOR ZONES. |
| | |
| | C) ARCHED WINDOW IN FRONT ELEVATION DOESN'T MATCH |
| | WINDOW SCHEDULE SHOWN ON SHEET S-3. REVISE WINDOW |
| | SCHEDULE TO MATCH ELEVATION. (REPEAT COMMENT). |
| | FRONT ELEVATION SHOWS ARCHED WINDOW. THIS TYPE OF |
| | WINDOW NEEDS PRODUCT APPROVAL ALSO. |
| | |
| | 10- SHEET S-5: |
| | A) WALL SECTIONS AND DETAILS DON'T MATCH FLOOR PLANS |
| | AND EXTERIOR ELEVATIONS. REVISE AS REQUIRED. (REPEAT |
| | COMMENT). COORDINATE ALL WOOD MEMBERS SIZES TO MATCH. |
| | EG: SIZE OF LEDGERS, SIZE OF ROOF RAFTERS, ETC. |
| | |
| | B) WALLS SECTIONS TO SPECIFY DOUBLE LAYER OF WATER |
| | RESISTANT BARRIER AS REQUIRED BY SEC. R703.6.3 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). SECTIONS 5 |
| | AND 6 OF SHEET S-5 ARE MISSING THIS INFORMATION. |
| | |
| | C) WALL SECTIONS TO SHOW CONTINUOUS LOAD PATH BETWEEN |
| | FOUNDATIONS, WALLS AND ROOF AS REQUIRED BY SEC. R601.2 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY ALL FASTENERS |
| | THAT WILL PROVIDE THE CONTINUOUS TRANSFER OF LOADS FROM |
| | TOP TO BOTTOM. (REPEAT COMMENT). SECTIONS 5 AND 6 DON'T |
| | PROVIDE COMPLETE INFORMATION. ALSO, WALL SECTION 1 |
| | DOESN'T PROVIDE SPECIFICATIONS FOR PARAPET TOP PLATE |
| | ATTACHMENT TO WALL STUD. |
| | CLARIFY HOW IS THE (2)2X8 LEDGER ATTACHED TO WALL STUDS |
| | ON EACH SIDE WITH HUC28-2 CONNECTORS IF NAILS ARE GOING |
| | TO BE CONFLICTING WITH EACH OTHER ON EACH SIDE. PROVIDE |
| | DETAIL SHOWING PROPOSED INSTALLATION. |
| | |
| | D) SPECIFY ROOF CROSS VENTILATION IN WALL SECTIONS AS |
| | REQUIRED BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | (REPEAT COMMENT). ENGINEER'S RESPONSE "TO MATCH |
| | EXISTING" DOESN'T ANSWER THE QUESTION. |
| | |
| | E) SPECIFY CEILING INSULATION. COORDINATE WITH THE |
| | ENERGY CALCULATIONS. (REPEAT COMMENT). NO INSULATION |
| | SPECIFIED ON WALL SECTIONS. ENGINEER'S RESPONSE "TO |
| | MATCH EXISTING" DOESN'T ANSWER THE QUESTION. |
| | |
| | F) WALL SECTIONS: SPECIFY HOW IS THE LEDGER (2X8 AND |
| | 2X6) THAT IS RECEIVING THE JOISTS OR RAFTERS ATTACHED |
| | TO VERIFY COMPLIANCE WITH THE DESIGN LOADS OF SEC. R301 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). |
| | WALL SECTIONS 5 AND 6 DON'T HAVE ANY SPECIFICATIONS TO |
| | ADDRESS THIS ISSUE. |
| | |
| | G) TYP. PARAPET WALL SECTION 1: * SPECIFY TYPE OF WOOD |
| | USED TO COMPLY WITH THE PROTECTION AGAINST DECAY SEC. |
| | R319 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | ** SPECIFY UNDER FLOOR SPACE VENTILATION SIZE AND |
| | LOCATION AS REQUIRED BY SEC. R408 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. SPECIFY LOCATION AND SIZE ON FLOOR |
| | PLANS. |
| | *** SPECIFY UNDER FLOOR SPACE ACCESS AS REQUIRED BY |
| | SEC. R408.3 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | H) STAIR SECTIONS AND DETAILS (REPEAT COMMENT. NOT |
| | ADDRESSED): |
| | * PROVIDE COMPLETE INFORMATION FOR RAILINGS AND STEPS |
| | TO VERIFY COMPLIANCE WITH TABLE R301.5 AND SECTIONS |
| | R311.4.3, R311.5 AND R312 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | ** COORDINATE ALL DETAILS TO MATCH BETWEEN THEMSELVES |
| | AND TO MATCH FLOOR PLANS. |
| | |
| | *** SPECIFY ALL CONNECTORS AND MAKE SURE WOOD MEMBER |
| | SIZE IS THE SAME IN ALL DRAWINGS. EG: SOME DETAILS SHOW |
| | 4X4 POST AND OTHERS 4X6 POST. |
| | |
| | I) REVISE ROOF SHEATHING NAILING NOTE ON ALL TYPICAL |
| | WALL SECTIONS. ROOF ZONE #3 TO HAVE 8D RING SHANK NAILS |
| | AT 4"O.C. AS REQUIRED BY SEC. R803.2.3.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). |
| | |
| | J) WINDOWS/DOORS DETAILS 3 AND 4 DON'T MATCH DETAILS |
| | SHOWN ON SHEET S-3. |
| | |
| | K) WAL SECTION #6 SHOWS R-16 INSULATION ON WALLS. THIS |
| | DOESN'T MATCH THE ENERGY CALCULATIONS AND R-16 |
| | INSULATION DOESN'T FIT ON 2X4 WALL. REVISE AS REQUIRED. |
| | |
| | L) SEE COMMENTS ON REVIEWED SET OF PLANS. |
| | |
| | 11- PLEASE RETURN REVIEWED SET OF PLANS AFTER ORIGINAL |
| | DRAWINGS ARE REVISED. |
| | |
| | 12- ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE |
| | SEC. 553.80(2)(B) REGARDING FEES FOR MULTIPLE REVIEWS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |