Plan Review Notes
Plan Review Notes For Permit 08090049
Permit Number 08090049
Review Stop B
Sequence Number 3
Notes
Date Text
2009-03-26 17:04:55RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 SECOND CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED LATER AT TIME OF PERMIT
 PICK UP.
  
 2- A) PERMIT VALUATION DECLARED IN THE PERMIT
 APPLICATION IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO
 FBC. UPDATE VALUATION TO INCLUDE ALL SCOPE OF WORK
 SHOWN ON PLANS AND INCLUDE ENGINEER PROFESSIONAL FEES
 ALSO. (REPEAT COMMENT. NOT ADDRESSED AT ALL).
  
 B) UPDATE NAME OF OWNER. PERMIT APPLICATION SAYS ONE
 PERSON. PLANS AND PROPERTY APPRAISAL SAYS ANOTHER.
 CLARIFY/REVISE AS REQUIRED. (REPEAT COMMENT. NOT
 ADDRESSED AT ALL).
  
 3- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. (REPEAT
 COMMENT).
  
 B) ACCORDING TO FORM 600A-2004R SUBMITTED THE ENTIRE
 HOUSE IS COMPLYING WITH THE ENERGY CODE. SEE SQUARE
 FOOTAGE SHOWN ON ITEM #6. CLARIFY AND PROVIDE PROOF
 THAT ENTIRE BUILDING COMPLIES WITH THE CODE. OTHERWISE
 CONCENTRATE ON ADDITION AND NEW COMPONENTS TO BE
 INSTALLED ONLY. NOTE: A DIFFERENT PRESCRIPTIVE FORM FOR
 SMALL ADDITIONS MAY BE USED ALSO.
  
 ***NOTE: READ SEC. 13-600.2.A.3.1. AND SEC.
 13-600.2.A.3.2 OF FBC 2004 TO SEE WHICH METHOD WILL BE
 PROVIDED TO COMPLY WITH CHAPTER 13 FBC.
  
 C) IF ITEM #7B IS USING SHGC=0.5 ON DOOR AND WINDOWS,
 THEN NEED TO PROVIDE PROOF THAT GLASS ON WINDOWS/DOORS
 PROVIDE THAT SHGC FACTOR. OTHERWISE, USE THE DEFAULT
 FACTOR OF THE ENERGY CALCULATIONS PROGRAM.
  
 D) REVISE CEILING TYPE ON ITEM #10A. THIS HOUSE HAS A
 FLAT CEILING. FLAT CEILING DOESN'T PROVIDE UNDER ATTIC
 AREA. REVISE AS REQUIRED. SEE CHAPTER 13 FBC 2004 FOR
 PROPER TYPE OF CEILING TO BE SPECIFIED.
  
 E) IF TAKING THE CEILING FAN CREDIT ON ITEM #15, THEN
 CEILING FANS MUST BE INSTALLED ON ALL ROOMS AS REQUIRED
 BY TABLE 13-607.1.A.1 FBC 2004.
  
 F) REVISE OWNER INFORMATION. COORDINATE WITH PERMIT
 APPLICATION AND PLANS. ALSO, PROVIDE COMPLETE
 INFORMATION ON TOP OF FORM.
  
 G) REVISE ITEM #3. THIS IS NOT A MULTIFAMILY.
  
 4- ENERGY CALCULATIONS SUBMITTED ARE TAKEN THE CEILING
 FAN CREDIT. SEE ITEM #15. NEED TO SPECIFY ON PLANS SIZE
 OF CEILING FAN ON EACH ROOM TO COMPLY WITH THE
 REQUIREMENTS OF TABLE 13-607.1.A.1 OF FBC 2004.
  
 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FLAT ROOF. AND, CLEARLY IDENTIFY SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED AND SPECIFIC BASE SHEET
 FASTENING OPTION. PROVIDE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7. SEE GENERAL
 LIMITATIONS ON LAST PAGE OF DADE COUNTY NOA. IF RAS 117
 CALCULATIONS ARE REQUIRED TO BE SIGNED AND SEALED, THEN
 PROVIDE SIGNED AND SEALED CALCULATIONS. (REPEAT
 COMMENT. NOT ADDRESSED AT ALL).
  
 B) ROOF SHINGLES AS SHOWN ON SHEET S-5. (REPEAT
 COMMENT. NOT ADDRESSED AT ALL).
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. THIS
 APPLIES TO STRUCTURAL CONNECTORS ONLY. OTHER PRODUCT
 APPROVALS REQUIRED COMPLETE REPORT. (REPEAT COMMENT).
 INFORMATION SUBMITTED ON CONNECTOR SCHEDULE ON SHEET
 S-2 MAKES NO SENSE. THERE ARE NOT NOA'S OR FLORIDA
 PRODUCT APPROVALS AS SPECIFIED ON THIS SCHEDULE. WHERE
 ARE F22, IL8, L9 F16, F6 AND F8 TAKEN FROM?
  
 D) STORM SHUTTERS: PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. AND, ON NOA 08-0527.09
 SUBMITTED MARK SPECIFIC MOUNTING CONDITIONS (EG: WALLL
 MOUNTED, BUILD OUT, ETC) AND SPECIFIC ANCHOR TYPE AND
 SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE. (REPEAT COMMENT. NOT ADDRESSED AT ALL). PRODUCT
 APPROVAL WAS NOT SUBMITTED THIS TIME AND THE REST OF
 THE INFORMATION WAS NOT PROVIDED AT ALL.
  
 E) SINGLE HUNG WINDOWS. CHECK WINDOW SIZES AND DESIGN
 PRESSURES SHOWN ON NOA 05-1003.10 SUBMITTED WITH SIZES
 AND DESIGN PRESSURES SHOWN ON PLANS. PRODUCT APPROVAL
 CAN NOT BE USED FOR PROPOSED SIZES. (REPEAT COMMENT).
 NOA 05-1003.10 SUBMITTED IS MISSING SHEET 1 OF 4. THIS
 SHEET SHOWS THE DESIGN PRESSURES AND SIZE OF WINDOWS.
 THIS PRODUCT APPROVAL IS NOT GOOD FOR SIZE OF WINDOWS
 SHOWN ON WINDOW SCHEDULE. PROVIDE PRODUCT APPROVAL THAT
 COVER SIZE OF WINDOWS AS SPECIFIED ON PLANS.
  
 F) ENTRY DOOR. SEE EXTERIOR ELEVATIONS. NO PRODUCT
 APPROVAL SUBMITTED THIS TIME.
  
 G) REAR FRENCH DOORS. SEE EXTERIOR ELEVATIONS. NO
 PRODUCT APPROVAL SUBMITTED THIS TIME.
  
 H) REAR DOOR BY DEN AREA. SEE EXTERIOR ELEVATIONS. NO
 PRODUCT APPROVAL SUBMITTED THIS TIME.
  
 I) WINDOW MULLIONS. NO PRODUCT APPROVAL SUBMITTED THIS
 TIME. ALSO, MARK ON PRODUCT APPROVAL DRAWINGS SPECIFIC
 SIZE AND FASTENERS TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 J) EXTERIOR DOOR FOR WATER HEATER STORAGE AREA.
  
 K) ARCHED WINDOW AS SHOWN ON FRONT ELEVATION. NO
 PRODUCT APPROVAL SUBMITTED.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVED IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT). ENGINEER PROVIDED LETTER STATING "THE
 PRODUCT APPROVALS FOR ALL THE WINDOWS AND DOORS FOR
 THIS RESIDENCE HAVE BEEN REVIEWED AND ARE IN ACCORDANCE
 WITH THE 2004 FLORIDA BUILDING CODE, INCLUDING THE 2006
 AMENDMENTS". THIS LETTER IS NOT ACCEPTABLE. THIS
 STATEMENT IS TOO GENERAL AND IT DOESN'T IDENTIFY WHICH
 SPECIFIC PRODUCT APPROVALS HE REVIEWED. THERE ARE EVEN
 PRODUCT APPROVALS THAT CONTRACTOR DIDN'T SUBMIT WITH
 PERMIT PACKAGE. ALSO, THERE ARE OTHER PRODUCT APPROVALS
 LIKE SHINGLES, MULLIONS, STRUCTURAL CONNECTORS,
 SHUTTERS, FLAT ROOF ASSEMBLY THAT ENGINEER DOESN'T EVEN
 MENTION. ENGINEER OF RECORD NEED TO REVIEW AND APPROVE
 IN WRITING (NOT SIGNING AND SEALING) EACH INDIVIDUAL
 PRODUCT APPROVAL. IF USING LETTER TO IDENTIFY PRODUCT
 APPROVALS, THEN LIST ALL THE PRODUCT APPROVALS NUMBERS
 AND SPECIFIC MODEL/TYPE REVIEWED. AN STANDARD REVIEW
 STAMP ON EACH PRODUCT APPROVAL MAY BE USED ALSO.
  
 7- SHEET S-2:
 A) REVISE ROOF FRAMING PLAN NOTE #3: ROOF ZONE 3
 REQUIRES 4" O.C. 8D RING SHANK NAILS IN ROOF ZONE 3. AS
 REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE. REVISE AS REQUIRED AND IDENTIFY ROOF ZONE #3.
 (REPEAT COMMENT). ROOF ZONE 3 REQUIRES 8D RING SHANK
 NAILS AT 4"O.C. MIN. ALSO, CLEARLY IDENTIFY ROOF ZONE
 3.
 ***NOTE: REVISE CARPENTRY NOTE #12 ON SHEET S-0 AS
 WELL.
  
 B) REVISE SIZE OF ROOF MEMBER AND LEDGERS TO MATCH
 SIZES SHOWN ON DETAIL SECTIONS 5 AND 6 OF SHEET S-5.
 SEE ROOF FRAMING PLANS AND DETAILS AND COORDINATE AS
 REQUIRED TO MATCH.
  
 C) REVISE CONNECTOR SCHEDULE. WHERE ARE THE NOA NUMBERS
 TAKEN FROM?. THERE ARE NOT F22, IL8, L9, F6, F16 OR F8
 NUMBERS.
  
 8- SHEET S-3:
 A) HOW IS ACCESS PROVIDED FOR THE NEW GAS WATER HEATER
 CLOSET. SEE CHAPTER 24 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR PROHIBITED LOCATIONS. ALSO, PROVIDE ALL THE
 PERTINENT INFORMATION FOR PLUMBING REVIEW. (REPEAT
 COMMENT). FLOOR PLANS DON'T SHOW ANY DOOR, BUT EXTERIOR
 ELEVATIONS SHOW AN EXTERIOR DOOR. REVISE PLANS AS
 REQUIRED TO MATCH AND PROVIDE PRODUCT APPROVAL FOR
 DOOR.
  
 B) PROVIDE ACTUAL CALCULATIONS FOR THE DESIGN PRESSURES
 OF DOORS AND WINDOWS TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE. DESIGN PRESSURES PROVIDED ARE THE
 SAME FOR OPENINGS LOCATED ON INTERIOR OR END ZONE.
 OPENINGS ON END ZONES HAVE HIGHER DESIGN PRESSURES.
 CLEARLY IDENTIFY OPENINGS ON END ZONES AND PROVIDE
 CORRESPONDING DESIGN PRESSURES.
  
 C) SPECIFY SAFETY GLASS IN WINDOW NEXT TO THE DOOR IN
 NEW DEN AREA AND BY BATH TUB AREA. SEC. R308.4 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). ENGINEER
 RESPONDED THAT WINDOW TO HAVE IMPACT GLASS. PRODUCT
 APPROVAL SUBMITTED IS FOR NON-IMPACT GLASS. CLARIFY
 REVISE AS REQUIRED.
  
 D) SHOW THE EXTERIOR LANDINGS, STEPS AND RAILINGS TO
 VERIFY COMPLIANCE WITH SEC. R311.4.3, R311.5 AND R312
 OF 2004 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
 ENGINEER RESPONSE WAS THAT DETAILS WERE ON SHEET S-5.
 DETAILS ON SHEET S-5 ARE STILL NO PROVIDING ALL THE
 REQUIRED INFORMATION.
 **ALSO, FLOOR PLANS NEED TO SHOW THE LOCATION AND
 DIMENSIONS FOR THE STAIRS. PLANS SUBMITTED DON'T
 PROVIDE THIS INFORMATION.
  
 9- SHEET S-4:
 A) ALL THE ELEVATIONS SHOWN ON THIS SHEET DON'T MATCH
 FLOOR PLANS. REVISE AS REQUIRED. (REPEAT COMMENT).
 ENGINEER RESPONDED THAT PHOTOS HAVE BEEN SUBSTITUTED
 FOR ELEVATIONS. PHOTOS WERE NOT SUBMITTED BUT
 REGARDLESS ELEVATIONS AND FLOOR PLANS NEED TO MATCH
 ANYWAY.
  
 B) REVISE DOOR AND WINDOWS DESIGN PRESSURES. COORDINATE
 WITH ITEM 8B ABOVE. (REPEAT COMMENT). NEED CORRECT
 DESIGN PRESSURES FOR END AND INTERIOR ZONES.
  
 C) ARCHED WINDOW IN FRONT ELEVATION DOESN'T MATCH
 WINDOW SCHEDULE SHOWN ON SHEET S-3. REVISE WINDOW
 SCHEDULE TO MATCH ELEVATION. (REPEAT COMMENT).
 FRONT ELEVATION SHOWS ARCHED WINDOW. THIS TYPE OF
 WINDOW NEEDS PRODUCT APPROVAL ALSO.
  
 10- SHEET S-5:
 A) WALL SECTIONS AND DETAILS DON'T MATCH FLOOR PLANS
 AND EXTERIOR ELEVATIONS. REVISE AS REQUIRED. (REPEAT
 COMMENT). COORDINATE ALL WOOD MEMBERS SIZES TO MATCH.
 EG: SIZE OF LEDGERS, SIZE OF ROOF RAFTERS, ETC.
  
 B) WALLS SECTIONS TO SPECIFY DOUBLE LAYER OF WATER
 RESISTANT BARRIER AS REQUIRED BY SEC. R703.6.3 OF 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT). SECTIONS 5
 AND 6 OF SHEET S-5 ARE MISSING THIS INFORMATION.
  
 C) WALL SECTIONS TO SHOW CONTINUOUS LOAD PATH BETWEEN
 FOUNDATIONS, WALLS AND ROOF AS REQUIRED BY SEC. R601.2
 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY ALL FASTENERS
 THAT WILL PROVIDE THE CONTINUOUS TRANSFER OF LOADS FROM
 TOP TO BOTTOM. (REPEAT COMMENT). SECTIONS 5 AND 6 DON'T
 PROVIDE COMPLETE INFORMATION. ALSO, WALL SECTION 1
 DOESN'T PROVIDE SPECIFICATIONS FOR PARAPET TOP PLATE
 ATTACHMENT TO WALL STUD.
 CLARIFY HOW IS THE (2)2X8 LEDGER ATTACHED TO WALL STUDS
 ON EACH SIDE WITH HUC28-2 CONNECTORS IF NAILS ARE GOING
 TO BE CONFLICTING WITH EACH OTHER ON EACH SIDE. PROVIDE
 DETAIL SHOWING PROPOSED INSTALLATION.
  
 D) SPECIFY ROOF CROSS VENTILATION IN WALL SECTIONS AS
 REQUIRED BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT). ENGINEER'S RESPONSE "TO MATCH
 EXISTING" DOESN'T ANSWER THE QUESTION.
  
 E) SPECIFY CEILING INSULATION. COORDINATE WITH THE
 ENERGY CALCULATIONS. (REPEAT COMMENT). NO INSULATION
 SPECIFIED ON WALL SECTIONS. ENGINEER'S RESPONSE "TO
 MATCH EXISTING" DOESN'T ANSWER THE QUESTION.
  
 F) WALL SECTIONS: SPECIFY HOW IS THE LEDGER (2X8 AND
 2X6) THAT IS RECEIVING THE JOISTS OR RAFTERS ATTACHED
 TO VERIFY COMPLIANCE WITH THE DESIGN LOADS OF SEC. R301
 OF 2004 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
 WALL SECTIONS 5 AND 6 DON'T HAVE ANY SPECIFICATIONS TO
 ADDRESS THIS ISSUE.
  
 G) TYP. PARAPET WALL SECTION 1: * SPECIFY TYPE OF WOOD
 USED TO COMPLY WITH THE PROTECTION AGAINST DECAY SEC.
 R319 OF 2004 FLORIDA RESIDENTIAL CODE.
 ** SPECIFY UNDER FLOOR SPACE VENTILATION SIZE AND
 LOCATION AS REQUIRED BY SEC. R408 OF 2004 FLORIDA
 RESIDENTIAL CODE. SPECIFY LOCATION AND SIZE ON FLOOR
 PLANS.
 *** SPECIFY UNDER FLOOR SPACE ACCESS AS REQUIRED BY
 SEC. R408.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 H) STAIR SECTIONS AND DETAILS (REPEAT COMMENT. NOT
 ADDRESSED):
 * PROVIDE COMPLETE INFORMATION FOR RAILINGS AND STEPS
 TO VERIFY COMPLIANCE WITH TABLE R301.5 AND SECTIONS
 R311.4.3, R311.5 AND R312 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 ** COORDINATE ALL DETAILS TO MATCH BETWEEN THEMSELVES
 AND TO MATCH FLOOR PLANS.
  
 *** SPECIFY ALL CONNECTORS AND MAKE SURE WOOD MEMBER
 SIZE IS THE SAME IN ALL DRAWINGS. EG: SOME DETAILS SHOW
 4X4 POST AND OTHERS 4X6 POST.
  
 I) REVISE ROOF SHEATHING NAILING NOTE ON ALL TYPICAL
 WALL SECTIONS. ROOF ZONE #3 TO HAVE 8D RING SHANK NAILS
 AT 4"O.C. AS REQUIRED BY SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
  
 J) WINDOWS/DOORS DETAILS 3 AND 4 DON'T MATCH DETAILS
 SHOWN ON SHEET S-3.
  
 K) WAL SECTION #6 SHOWS R-16 INSULATION ON WALLS. THIS
 DOESN'T MATCH THE ENERGY CALCULATIONS AND R-16
 INSULATION DOESN'T FIT ON 2X4 WALL. REVISE AS REQUIRED.
  
 L) SEE COMMENTS ON REVIEWED SET OF PLANS.
  
 11- PLEASE RETURN REVIEWED SET OF PLANS AFTER ORIGINAL
 DRAWINGS ARE REVISED.
  
 12- ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE
 SEC. 553.80(2)(B) REGARDING FEES FOR MULTIPLE REVIEWS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER