Plan Review Notes
Plan Review Notes For Permit 08090049
Permit Number 08090049
Review Stop B
Sequence Number 2
Notes
Date Text
2009-01-06 14:31:06RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED LATER ON AT TIME OF
 PERMIT PICK UP.
  
 2- SCOPE OF WORK SHOWN ON PERMIT APPLICATION DOESN'T
 MATCH SCOPE OF WORK SHOWN ON PLANS SUBMITTED. REVISE AS
 REQUIRED TO MATCH AND UPDATE VALUATION ON THE PERMIT
 APPLICATION AS REQUIRED. PERMIT VALUATION TO INCLUDE
 ALL WORK TO BE PERFORMED INCLUDING THE ENGINEER FEES.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: ALSO, UPDATE NAME OF OWNER. PERMIT APPLICATION
 SAYS ONE PERSON. PLANS AND PROPERTY APPRAISAL SAYS
 ANOTHER. CLARIFY/REVISE AS REQUIRED.
  
 3- PROVIDE AREA TABULATION SHOWING EXISTING AREAS AND
 NEW AREAS INCLUDING ENTRY AREA, REAR AREA AND STORAGE
 AREA FOR NEW GAS WATER HEATER.
 ***ALSO, BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE OR
 NOT. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.0 FBC 2004.
 NOTE: MAKE SURE CORRECT REVISED 2004 FORM IS USED AND
 COMPLETE INFORMATION IS PROVIDED, INCLUDING OWNER/AGENT
 SIGNATURE AND DATE.
  
 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FLAT ROOF. AND, CLEARLY IDENTIFY SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED AND SPECIFIC BASE SHEET
 FASTENING OPTION. PROVIDE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7. SEE GENERAL
 LIMITATIONS ON LAST PAGE OF DADE COUNTY NOA. IF RAS 117
 CALCULATIONS ARE REQUIRED TO BE SIGNED AND SEALED, THEN
 PROVIDE SIGNED AND SEALED CALCULATIONS.
  
 B) ROOF SHINGLES AS SHOWN ON SHEET S-5.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. THIS
 APPLIES TO STRUCTURAL CONNECTORS ONLY. OTHER PRODUCT
 APPROVALS REQUIRED COMPLETE REPORT.
  
 D) STORM SHUTTERS: PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. AND, ON NOA 08-0527.09
 SUBMITTED MARK SPECIFIC MOUNTING CONDITIONS (EG: WALL
 MOUNTED, BUILD OUT, ETC) AND SPECIFIC ANCHOR TYPE AND
 SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 E) SINGLE HUNG WINDOWS. CHECK WINDOW SIZES AND DESIGN
 PRESSURES SHOWN ON NOA 05-1003.10 SUBMITTED WITH SIZES
 AND DESIGN PRESSURES SHOWN ON PLANS. PRODUCT APPROVAL
 MAY NOT BE USED FOR PROPOSED SIZES.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVED IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- SHEET S-1: PROVIDE CLEAR DETAIL SHOWING HOW ARE THE
 NEW (2)2X12 BEAMS ANCHORED TO THE PEDESTAL AT CORNERS
 AND INTERMEDIATE SUPPORTS TO VERIFY COMPLIANCE WITH THE
 UPLIFT LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE. SEE COMMENTS ON PLANS. FLOOR FRAMING PLAN
 PROVIDED IS NOT CLEAR.
  
 8- SHEET S-2:
 A) CLARIFY WHY IS THERE AN AC UNIT BY THE KITCHEN AREA.
 PROVIDE COMPLETE LAYOUT OF KITCHEN AND BATHROOMS. NOTE
 REGARDING LAYOUT TO BE APPROVED BY HOMEOWNER IS NOT
 ACCEPTABLE. CLEARLY SHOW WHAT'S EXISTING AND WHAT'S NEW
 TO VERIFY COMPLIANCE WITH THE CODE REQUIREMENTS.
  
 B) REVISE ROOF FRAMING PLAN NOTE #3: ROOF ZONE 3
 REQUIRES 4" O.C. 8D RING SHANK NAILS IN ROOF ZONE 3. AS
 REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE. REVISE AS REQUIRED AND IDENTIFY ROOF ZONE #3.
  
 C) CLARIFY FRAMING PLAN NOTES: WHAT'S DOES N.G.V.D
 STATE ON NOTE #1 AND #3 STANDS FOR:.
  
 9- SHEET S-3:
 A) HOW IS ACCESS PROVIDED FOR THE NEW GAS WATER HEATER
 CLOSET. SEE CHAPTER 24 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR PROHIBITED LOCATIONS. ALSO, PROVIDE ALL THE
 PERTINENT INFORMATION FOR PLUMBING REVIEW.
  
 B) DESIGN PRESSURES SHOWN ON DOORS AND WINDOWS DON'T
 CORRESPOND TO EXPOSURE "C" AS SPECIFIED ON
 MISCELLANEOUS NOTE #5 ON SHEET S-0. PROVIDE
 CALCULATIONS FOR DESIGN PRESSURES IN EXPOSURE "C" AND
 REVISE AS REQUIRED.
  
 C) WHY IS THE AC UNIT IN THE KITCHEN. PROVIDE ACTUAL
 KITCHEN AND BATHROOM LAYOUT LAYOUT.
  
 D) REVISE NOTE REGARDING WINDOWS TO BE BY "BETTERBILT".
 SEE PRODUCT APPROVAL SUBMITTED.
  
 E) REVISE WINDOW SCHEDULE. THEY ARE ALL SH3740, BUT THE
 SIZE IS DIFFERENT IN ALL OF THEM. REVISE AS REQUIRED.
  
 F) REVISE WOOD HEADER SCHEDULE. THERE ARE NOT 2X8
 WALLS. REVISE NOTE UNDER BEAM HEADER.
  
 G) CLARIFY NAILING SCHEDULE. ARE THE STUDS TOE NAILED
 AT TOP AND BOTTOM?. PROVIDE CALCULATIONS SHOWING THAT
 SPECIFIED TOE NAILS WILL RESIST THE CALCULATED UPLIFT
 LOADS AND LATERAL LOADS FOR 140MPH WIND LOADS IN
 EXPOSURE "C". SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH THE DESIGN LOADS OF SEC. R301
 OF 2004 FLORIDA RESIDENTIAL CODE. CLARIFY WHY NOT USING
 HURRICANE STRAPS TO RESIST THE CALCULATED LOADS.
  
 H) SPECIFY SAFETY GLASS IN WINDOW NEXT TO THE DOOR IN
 NEW DEN AREA AND BY BATH TUB AREA. SEC. R308.4 2004
 FLORIDA RESIDENTIAL CODE.
  
 I) CLARIFY WHY WALL IN MASTER BATH AREA IS ABUTTING THE
 WINDOW?. SEE COMMENTS ON PLANS.
  
 J) SHOW THE EXTERIOR LANDINGS, STEPS AND RAILINGS TO
 VERIFY COMPLIANCE WITH SEC. R311.4.3, R311.5 AND R312
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 10- SHEET S-4:
 A) ALL THE ELEVATIONS SHOWN ON THIS SHEET DON'T MATCH
 FLOOR PLANS. REVISE AS REQUIRED.
  
 B) REVISE DOOR AND WINDOWS DESIGN PRESSURES. COORDINATE
 WITH ITEM 9B ABOVE.
  
 C) ARCHED WINDOW IN FRONT ELEVATION DOESN'T MATCH
 WINDOW SCHEDULE SHOWN ON SHEET S-3. REVISE WINDOW
 SCHEDULE TO MATCH ELEVATION.
  
 D) CLARIFY WHAT'S THE HATCHED LINES SHOWN ON WINDOWS ON
 THE TOP RIGHT CORNER. IF THEY ARE AWNINGS, THEN NEED TO
 PROVIDE COMPLETE DESIGN AND STRUCTURAL INFORMATION TO
 SHOW COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE. 140MPH IN EXPOSURE "C".
  
 11- SHEET S-5:
 A) WALL SECTIONS AND DETAILS DON'T MATCH FLOOR PLANS
 AND EXTERIOR ELEVATIONS. REVISE AS REQUIRED.
  
 B) WALLS SECTIONS TO SPECIFY DOUBLE LAYER OF WATER
 RESISTANT BARRIER AS REQUIRED BY SEC. R703.6.3 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 C) WALL SECTIONS TO SHOW CONTINUOUS LOAD PATH BETWEEN
 FOUNDATIONS, WALLS AND ROOF AS REQUIRED BY SEC. R601.2
 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY ALL FASTENERS
 THAT WILL PROVIDE THE CONTINUOUS TRANSFER OF LOADS FROM
 TOP TO BOTTOM.
  
 D) SPECIFY ROOF CROSS VENTILATION IN WALL SECTIONS AS
 REQUIRED BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 E) SPECIFY CEILING INSULATION AND WALL INSULATION ON
 WALLS SECTIONS. COORDINATE WITH THE ENERGY
 CALCULATIONS. ALSO, REVISE R-VALUE SHOWN ON WALL
 SECTIONS. EG: R-30 DOESN'T FIT IN A 2X6 FRAMED WALL.
  
 F) WALL SECTIONS: SPECIFY HOW IS THE LEDGER (2X8 AND
 2X6) THAT IS RECEIVING THE JOISTS OR RAFTERS ATTACHED
 TO VERIFY COMPLIANCE WITH THE DESIGN LOADS OF SEC. R301
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 G) TYP. PARAPET WALL SECTION 1: * SPECIFY TYPE OF WOOD
 USED TO COMPLY WITH THE PROTECTION AGAINST DECAY SEC.
 R319 OF 2004 FLORIDA RESIDENTIAL CODE.
 ** SPECIFY UNDER FLOOR SPACE VENTILATION SIZE AND
 LOCATION AS REQUIRED BY SEC. R408 OF 2004 FLORIDA
 RESIDENTIAL CODE. SPECIFY LOCATION AND SIZE ON FLOOR
 PLANS.
 *** SPECIFY UNDER FLOOR SPACE ACCESS AS REQUIRED BY
 SEC. R408.3 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 H) SECTION 2: SPECIFY HOW IS THE 2X8 LEDGER ATTACHED.
 SEC. R301. ALSO, CLARIFY WHAT'S THE NEW 1 3/4" X 11
 1/2" M-L. IS THIS ADDITIONAL TO THE LEDGER? DRAWING IS
 NOT CLEAR.
  
 I) STAIR SECTIONS AND DETAILS:
 * PROVIDE COMPLETE INFORMATION FOR RAILINGS AND STEPS
 TO VERIFY COMPLIANCE WITH TABLE R301.5 AND SECTIONS
 R311.4.3, R311.5 AND R312 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 ** COORDINATE ALL DETAILS TO MATCH BETWEEN THEMSELVES
 AND TO MATCH FLOOR PLANS.
  
 *** SPECIFY ALL CONNECTORS AND MAKE SURE WOOD MEMBER
 SIZE IS THE SAME IN ALL DRAWINGS. EG: SOME DETAILS SHOW
 4X4 POST AND OTHERS 4X6 POST.
  
 J) REVISE ROOF SHEATHING NAILING NOTE ON TYPICAL WALL
 SECTIONS. ROOF ZONE #3 TO HAVE 8D RING SHANK NAILS AT
 4"O.C. AS REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 K) CLARIFY WHERE ARE THE NUMBER OF JACK AND KING STUDS
 TAKEN FROM TO RESIST THE LOADS DEPENDING ON OPENING
 SIZE AND WIND LOADS OF 140MPH IN EXPOSURE "C". PROVIDE
 CALCULATIONS TO SHOW THAT ONLY ONE AS SHOWN ON DETAILS
 ARE ADEQUATE FOR LARGE OPENINGS.
 NOTE: SAME COMMENT APPLIES TO WINDOW SILL DETAIL. WHY
 IS THERE ONLY ONE 2X MEMBER ADEQUATE. AND, IS THIS
 ADEQUATE ALSO TO RECEIVE STORM PANELS?. SEC. 106.1.2
 CITY AMENDMENT SOT FBC 2004 TO VERIFY COMPLIANCE WITH
 THE DESIGN LOADS OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 L) TYP. 2X4 AND 2X6 WALL SECTIONS DON'T MATCH EXTERIOR
 ELEVATIONS AND PLANS. REVISE AS REQUIRED.
  
 M) SEE COMMENTS ON REVIEWED SET OF PLANS AND RETURN
 REDLINED SET AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712