Plan Review Notes
Plan Review Notes For Permit 08090049
Permit Number 08090049
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-24 14:33:15DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 EXISTING BUILDING
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT S-0 MISC. NOTE #3 TO INCLUDE THE 2007 AMENDMENTS
 TO THE FBC-2004. THIS SHALL ALSO BE INCLUDED TO THE
 STRUCTURAL REQUIREMENTS, THE PROJECT DESIGN CRITERIA &
 THE EXISTING BUILDING CODE INDICATED AT THE LOWER
 CENTER OF SHEET. SECTION 106.1.1.
  
 2. SHT S-0 INDICATES AN ADDITION. THIS IS NOT INDICATED
 ON THE APPLICATION. PLEASE CLARIFY. THE APPLICATION
 STATES "DESCRIBE PROJECT IN DETAIL". NO MENTION OF
 ADDITION ON APPLICATION.
  
 3. SHT S-2 NEW DIMENSIONAL FLOOR PLAN HAS A NOTE THAT
 STATES, " BATH LAYOUTS ARE A REPRESENTATION OF BASIC
 CONTENTS. ACTUAL CONFIG. SHALL BE APPROVED BY
 HOMEONER". THIS INDICATES THERE MAY BE PLUMBING WORK.
 SUBMIT AN EXISTING FLOOR PLAN TO VERIFY THE EXTENT OF
 THE WORK BEING DONE. IF THERE IS PLUMBING ALTERATION,
 THEN A SANITARY ISOMETRIC RISER DIAGRAM WILL BE
 REQUIRED SHOWING ALL NEW WORK WITH THE PIPE SIZES,
 TRAPS, VENTS ETC SHOWN ON THE ISO. SECTION 106.3.5.1.3.
  
 4. SHT S-2 SHOWS A GAS WATER HEATER. WILL THERE BE GAS
 WORK ON THIS PROJECT. PLEASE CLARIFY. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  