| 2009-06-10 16:19:07 | ** DENIED 3RD REVIEW** |
| | |
| | |
| | ** ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE. |
| | MINIMUM CODE COMPLIANCE IS NOT BEING MET WITH REPEATED |
| | COMMENTS. FS 553.80(2)(B) MAY BE ASSESSED ON THE |
| | FOLLOWING REVIEW TO DESIGNER OF RECORD. |
| | |
| | ** PLANS ARE REVISED SHOWING A COMPLETELY DIFFERENT |
| | SERVICE FROM PREVIOUS SUBMITTED PLANS. SEE NOTES BELOW |
| | AS *MINIMUM* CODE COMPLIANCE IS NOT MET. |
| | IF PLANS ARE REVISED AND ARE NOT THE SAME AS PREVIOUSLY |
| | SUBMITTED THEN SOMETIMES THAT CAN CREATE NEW COMMENTS |
| | ** THIS REVIEWER HAS STATED ON BOTH PREVIOUS REVIEWS |
| | THAT IF THERE WERE QUESTIONS TO PLEASE CALL TO GO OVER |
| | COMMENTS. TO DATE NO CONTACT HAS BEEN MADE TO THIS |
| | OFFICE TO GO OVER COMMENTS. |
| | SEE ALL OF THE FOLLOWING NOTES. |
| | |
| | 1) NOTE: NEW RISER NOW SHOWS EXISTING 200AMP METER WITH |
| | NEW 4/0 ON RISER YET THE CONDUCTORS TO MAIN ARE 2/0. |
| | WHICH IS IT? 310.16, 310.15B6 |
| | |
| | 2) NOTE: THE RISER NOW SHOWS A NEW SERVICE MAIN WITH A |
| | 200AMP DISCONNECT AND A NEW 60 AMP DISCONNECT. AS SHOWN |
| | THIS IS A 260AMP SERVICE. CONDUCTORS AND METER ARE NOT |
| | RATED FOR MORE THAN 200AMPS. IS THIS A MAIN BREAKER |
| | PANEL WITH A SUB 60AMP BREAKER? |
| | |
| | 3) NOTE: PLEASE INDICATE AIC RATINGS FOR NEW MAIN PER |
| | 110.9 |
| | |
| | 4) NOTE: THE RISER NOW SHOWS NEW #1AWG CONDUCTORS FROM |
| | 60AMP BREAKER AS NEW FEEDERS TO SUB PANEL AT PLAYHOUSE. |
| | THIS IS NOT POSSIBLE. 110.14,110.3 |
| | |
| | 5) NOTE: THE RISER NOW SHOWS A NEW 60AMP SUB PANEL AT |
| | THE PLAYHOUSE YET THE EXISTING 200AMP PANEL STILL SHOWS |
| | TWO CIRCUITS TO THE NEW PLAYHOUSE. WHICH IS IT? |
| | IN EITHER CASE THE MEANS OF DISCONNECT REQUIRED PER |
| | 225.31-225.39 IS NOT SHOWN AS PREVIOUSLY REQUESTED ON |
| | BOTH PREVIOUS REVIEWS. |
| | |
| | 6) NOTE: THE GROUNDING ELECTRODE SYSTEM BASED ON |
| | 250.32, 250.50, 250.66 IS STILL NOT SHOWN. IF THERE IS |
| | A NEW PANEL PLEASE SHOW THE MINIMUM. IF THERE NEW |
| | CIRCUITS FROM EXISTING PANEL THEN PLEASE SHOW |
| | COMPLIANCE. FOR NOTES #5 AND #6. |
| | |
| | 7) NOTE: IF THERE IS GOING TO BE A NEW SUB PANEL INSIDE |
| | THE NEW PLAYHOUSE PLEASE SUBMIT THE PANEL SCHEDULE |
| | SHOWING MINIMUM CODE COMPLIANCE FOR CONDUCTOR SIZES, |
| | OVER CURRENT PROTECTION AND PANEL SCHEDULE. |
| | 240.4,408.4, 310.16 ETC |
| | |
| | |
| | |
| | |
| | |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |