Plan Review Notes
Plan Review Notes For Permit 08090018
Permit Number 08090018
Review Stop E
Sequence Number 2
Notes
Date Text
2009-03-24 09:05:13** PLANS DENIED **
  
 THE ELECTRICAL PLANS DO NOT MEET THE MINIMUM NATIONAL
 ELECTRICAL CODE. PLEASE SEE THE FOLLOWING COMMENTS.
 THESE COMMENTS ARE BASED ON THE 2005 NFPA-70
  
 1) NOTE: THE ELECTRICAL RISER SUBMITTED DOES NOT MEET
 MINIMUM CODE. THE RISER INDICATES A 200AMP DISCONNECT
 FEEDING CONDUCTORS ONLY RATED FOR 150AMPS PER 310.15B6.
 THIS RISER ALSO INDICATES A SECONDARY FEEDER FROM THE
 MAIN TO THE PANEL. WHICH IS CORRECT?
  
 2) NOTE: PLEASE SEE NEC 225.31-225.39 REQUIRED
 DISCONNECTING MEANS NOT SHOWN. REQUIRED GROUPING ETC.
  
 3) NOTE: PLEASE SEE 250.32, 250.50 AS THE REQUIRED
 IDENTIFICATION OF THE GROUNDING ELECTRODE SYSTEM IS NOT
 SHOWN.
  
 4) NOTE: PLEASE BE SURE TO STATE THE ADOPTED MINMUM
 CODE EDITIONS ON PLANS AS REQUIRED PER FS 553.73.
 2004 FBC (RESIDENTIAL AND 2005 NFPA-70
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  