Plan Review Notes
Plan Review Notes For Permit 08090018
Permit Number 08090018
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-12 16:06:44 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT PLANS WITH MINIMUM CLARITY AND
 INFORMATION IN DRAFTSMAN QUALITY. THE PLANS NEED TO
 SHOW ALL ASPECTS OF CONSTRUCTION TO CONFORM TO THE
 MINIMUM BUILDING CODE ALONG WITH OTHER ADOPTED CODES BY
 FLORIDA STATUES 553.73
 FBC 106.1, 106.1.1, 106.1.2, 106.3.5.4.
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS WHICH WILL
 COORDINATE WITH A SUBMITTED FLOOR PLAN. FOR EXAMPLE THE
 ELECTRICAL LAYOUT AS SUBMITTED DOES NOT COORDINATE WITH
 THE HAND DRAWN ELEVATION PLANS. THE ELEVATION PLANS
 SHOW WALLS AND WINDOWS WHICH ARE NOT THE SAME AS
 ELECTRICAL.
 PLEASE SUBMIT ELECTRICAL PLANS WHICH ARE UNDER THE
 MINIMUM DESIGN OF THE 2005 NATIONAL ELECTRICAL CODE.
 PLEASE SEE SOME OF THE FOLLOWING.
 LOAD CALCULATIONS FOR ADDING LOAD TO EXISTING SERVICE.
 220.87
 GROUNDING ELECTRODE SYSTEM AT DETACHED STRUCTURES PER
 250.32, 250.50.
 DISCONNECTING MEANS AT DETACHED STRUCTURES PER
 225.31-225.39.
 CONDUCTOR SIZES PER 310.16
 PANEL SCHEDULE PER 408.4
 BREAKER SIZE(S). 310.16, 240.4, 210.19, 210.20 ETC
  
  
 *** BASED ON PLANS AT THIS TIME THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  