Plan Review Notes
Plan Review Notes For Permit 08090007
Permit Number 08090007
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-02 14:32:032004 FBC W/2007 REVISIONS
 REROOF
  
 DENIED BY BUILDING
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE THAT
 WILL BE REROOFED. FBC R301.2.1
  
 2) SUBMIT 2 COPIES OF THE NOA FOR THE JOHN MANSVILLE
 MODIFIED SYSTEM (FL 1046). ONLY THE COVERSHEETS WERE
 SUBMITTED. SPECIFY WHICH ONE OF THE APPROVED
 ASSEMBLIES, FASTENING OPTION AND DESIGN PRESSURE LISTED
 IN THE NOA WILL BE INSTALLED. FAC RULE 9B-72
  
 3) SUBMIT 2 COPIES OF SIGNED AND SEALED RAS 117
 CALCULATIONS FROM AN ARCHITECT, ENGINEER OR REGISTERED
 ROOF CONSULTANT FOR THE ENHANCED FASTENING AS REQUIRED
 BY LIMITATION #7 OF THE NOA.
  
 4) VALUE OF WORK ON APPLICATION IS TOO LOW. ACCORDING
 TO MARSHALL AND SWIFT VALUATION THE AVERAGE COST FOR
 600 SQFT OF A MODIFIED REROOF IS $ 3180.00. THE FEES
 HAVE BEEN ADJUSTED AND AN ADDITIONAL $13.60 IS DUE. FBC
 108.3* CITY AMENDMENTS.
  
 5) THE ADJUSTED VALUE REQUIRES A NOTICE OF
 COMMENCEMENT. FS 713
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]