| Plan Review Notes For Permit 08090007 |
| Permit Number |
08090007 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-02 14:32:03 | 2004 FBC W/2007 REVISIONS | | | REROOF | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE THAT | | | WILL BE REROOFED. FBC R301.2.1 | | | | | | 2) SUBMIT 2 COPIES OF THE NOA FOR THE JOHN MANSVILLE | | | MODIFIED SYSTEM (FL 1046). ONLY THE COVERSHEETS WERE | | | SUBMITTED. SPECIFY WHICH ONE OF THE APPROVED | | | ASSEMBLIES, FASTENING OPTION AND DESIGN PRESSURE LISTED | | | IN THE NOA WILL BE INSTALLED. FAC RULE 9B-72 | | | | | | 3) SUBMIT 2 COPIES OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FROM AN ARCHITECT, ENGINEER OR REGISTERED | | | ROOF CONSULTANT FOR THE ENHANCED FASTENING AS REQUIRED | | | BY LIMITATION #7 OF THE NOA. | | | | | | 4) VALUE OF WORK ON APPLICATION IS TOO LOW. ACCORDING | | | TO MARSHALL AND SWIFT VALUATION THE AVERAGE COST FOR | | | 600 SQFT OF A MODIFIED REROOF IS $ 3180.00. THE FEES | | | HAVE BEEN ADJUSTED AND AN ADDITIONAL $13.60 IS DUE. FBC | | | 108.3* CITY AMENDMENTS. | | | | | | 5) THE ADJUSTED VALUE REQUIRES A NOTICE OF | | | COMMENCEMENT. FS 713 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|