Plan Review Notes
Plan Review Notes For Permit 08080678
Permit Number 08080678
Review Stop P
Sequence Number 2
Notes
Date Text
2008-10-10 11:19:30PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS AS WELL
 AS THE DESIGNER'S RESPONSE'S FOR THE PURPOSE OF
 CONTINUITY. NEW COMMENTS WILL BE SO NOTED FOLLOWING THE
 PREVIOUSE REVIEW COMMENTS.
  
 1. SHEET 4, FOUNDATION PLAN: PLEASE CORRECT THE
 FOLLOWING MISIDENTIFIED 2" AND 3" VENTS FOR BATH 2,
 BATH 3 AND BATH 4, TO BE THE FOLLOWING. PER FBC-2004
 PLUMBING SECTION 701.1 SCOPE.
  
 A} BATH 3, THE 2" VENT SHOULD BE INDICATED AS A 2"
 WASTE STACK.
  
 B} BATH 3, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL
 STACK.
  
 C} BATH 4, THE 2" VENT SHOULD BE INDICATED AS A 2"
 WASTE STACK.
  
 D} BATH 4, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL
 STACK.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENTS
 1A, B, C, AND D HAVE NOT BEEN ADDRESSED ON THE
 RESUBMITTAL.
  
 2. SHEET 4, SANITARY RISER DIAGRAM AND FOUNDATION PLAN
 UNDERGROUND PLUMBING PLAN: AT A MINIMUM THE SANITARY
 RISER DIAGRAM SHOULD REFLECT THE FOUNDATION PLAN
 UNDERGROUND PLUMBING PLAN. PLEASE CORRELATE THE
 FOLLOWING BATHROOMS PER FBC-2004 PLUMBING SECTION 701.1
 SCOPE.
  
 A} MASTER BATH WHIRPOOL TUB AND WATER CLOSET.
  
 B} BATH 2.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENTS 2A
 AND B HAVE NOT BEEN ADDRESSED ON THE RESUBMITTAL.
  
 3. SHEET 4, SANITARY RISER DIAGRAM: THE MASTER BATH 1,
 SHOWER REQUIRES A VENT. PLEASE KNOW THAT ONE IS
 INDICATED ON THE FOUNDATION PLAN, HOWEVER IT IS NOT
 BEING INDICATED ON THE RISER DIAGRAM. PER FBC-2004
 PLUMBING SECTION 901.2.1 VENTING REQUIRED.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER. THE
 RESUBMITTED MASTER BATH 1 DOES INDICATE A VENT HOWEVER
 AND THE RESUBMITTED MASTER BATH 1, SHOWER DOES NOT
 REFLECT THE FOUNDATION PLAN. AT A MINIMUM THE RISER
 DIAGRAM AND THE FOUNDATION PLAN INDICATING THE
 UNDERGROUND PLUMBING SHOULD BE CORRELATED.
  
 4. SHEET 4, SANITARY RISER DIAGRAM POWDER ROOM BATH:
 ONLY FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE
 SAME FLOOR ARE PERMITTED TO BE VENTED BY A WET VENT.
 ANY ADDITIONAL FIXTURES (KITCHEN SINK, LAUNDRY SINK,
 WASHER, AND BATH #3) SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. EPR FBC-2004 PLUMBING SECTION 909.1 WET VENT
 PERMITTED.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT
 HAS NOT BEEN ADDRESSED.
  
 5. SHEET 2, GROUND FLOOR PLAN, POWDER ROOM: CLEARLY
 INDICATE THE WATER CLOSET AND LAVATORY SPACING FROM THE
 SIDE WALLS. A WATER CLOSET AND LAVATORY SHALL NOT BE
 SET CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE
 WALL. PER FBC-2004 PLUMBING SECTION 405.3.1 WATER
 CLOSETS, URINALS, LAVATORIES AND BIDETS.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND THE
 RESUMMITED PLAN SHEET INDICATES THE REQUESTED SPACING
 FOR THE FRONT OF THE WATER CLOSET, HOWEVER WITH THE
 WATER CLOSET BEING SET AT 45 DEGREES THE BACK OF THE
 WATER CLOSET IS NOT COMPLIANT. THE RESUBMITTED PLAN
 SHEET IS NOT INDICATING THE REQUESTED SPACING FOR THE
 LAVATORY.
  
 6. "OK" COMMENT ADDRESSED.
  
 7. "OK" COMMENT ADDRESSED..
  
 8. "OK" COMMENT ADDRESSED.
  
 9. "OK" COMMENT ADDRESSED.
  
 10. "OK" COMMENT ADDRESSED.
  
 11. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING IS A NEW COMMENT DUE THE RESUBMITTED
 SANITARY RISER.
  
 12. SHEET 4 SANITARY RISER DIAGRAM: DELETE SOIL AND
 WASTE STACK IN THE FOLLOWING BATHROOM VENT LOCATIONS.
 MASTER BATH, POOL BATH, BATH 3, AND BATH 4. PER
 FBC-2004 PLUMBING SECTON 701.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved