| Date |
Text |
| 2008-10-10 11:19:30 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND |
| | WITH THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS AS WELL |
| | AS THE DESIGNER'S RESPONSE'S FOR THE PURPOSE OF |
| | CONTINUITY. NEW COMMENTS WILL BE SO NOTED FOLLOWING THE |
| | PREVIOUSE REVIEW COMMENTS. |
| | |
| | 1. SHEET 4, FOUNDATION PLAN: PLEASE CORRECT THE |
| | FOLLOWING MISIDENTIFIED 2" AND 3" VENTS FOR BATH 2, |
| | BATH 3 AND BATH 4, TO BE THE FOLLOWING. PER FBC-2004 |
| | PLUMBING SECTION 701.1 SCOPE. |
| | |
| | A} BATH 3, THE 2" VENT SHOULD BE INDICATED AS A 2" |
| | WASTE STACK. |
| | |
| | B} BATH 3, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL |
| | STACK. |
| | |
| | C} BATH 4, THE 2" VENT SHOULD BE INDICATED AS A 2" |
| | WASTE STACK. |
| | |
| | D} BATH 4, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL |
| | STACK. |
| | |
| | **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENTS |
| | 1A, B, C, AND D HAVE NOT BEEN ADDRESSED ON THE |
| | RESUBMITTAL. |
| | |
| | 2. SHEET 4, SANITARY RISER DIAGRAM AND FOUNDATION PLAN |
| | UNDERGROUND PLUMBING PLAN: AT A MINIMUM THE SANITARY |
| | RISER DIAGRAM SHOULD REFLECT THE FOUNDATION PLAN |
| | UNDERGROUND PLUMBING PLAN. PLEASE CORRELATE THE |
| | FOLLOWING BATHROOMS PER FBC-2004 PLUMBING SECTION 701.1 |
| | SCOPE. |
| | |
| | A} MASTER BATH WHIRPOOL TUB AND WATER CLOSET. |
| | |
| | B} BATH 2. |
| | |
| | **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENTS 2A |
| | AND B HAVE NOT BEEN ADDRESSED ON THE RESUBMITTAL. |
| | |
| | 3. SHEET 4, SANITARY RISER DIAGRAM: THE MASTER BATH 1, |
| | SHOWER REQUIRES A VENT. PLEASE KNOW THAT ONE IS |
| | INDICATED ON THE FOUNDATION PLAN, HOWEVER IT IS NOT |
| | BEING INDICATED ON THE RISER DIAGRAM. PER FBC-2004 |
| | PLUMBING SECTION 901.2.1 VENTING REQUIRED. |
| | |
| | **NO COMMENT RESPONSE FROM THE DESIGNER. THE |
| | RESUBMITTED MASTER BATH 1 DOES INDICATE A VENT HOWEVER |
| | AND THE RESUBMITTED MASTER BATH 1, SHOWER DOES NOT |
| | REFLECT THE FOUNDATION PLAN. AT A MINIMUM THE RISER |
| | DIAGRAM AND THE FOUNDATION PLAN INDICATING THE |
| | UNDERGROUND PLUMBING SHOULD BE CORRELATED. |
| | |
| | 4. SHEET 4, SANITARY RISER DIAGRAM POWDER ROOM BATH: |
| | ONLY FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE |
| | SAME FLOOR ARE PERMITTED TO BE VENTED BY A WET VENT. |
| | ANY ADDITIONAL FIXTURES (KITCHEN SINK, LAUNDRY SINK, |
| | WASHER, AND BATH #3) SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. EPR FBC-2004 PLUMBING SECTION 909.1 WET VENT |
| | PERMITTED. |
| | |
| | **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT |
| | HAS NOT BEEN ADDRESSED. |
| | |
| | 5. SHEET 2, GROUND FLOOR PLAN, POWDER ROOM: CLEARLY |
| | INDICATE THE WATER CLOSET AND LAVATORY SPACING FROM THE |
| | SIDE WALLS. A WATER CLOSET AND LAVATORY SHALL NOT BE |
| | SET CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE |
| | WALL. PER FBC-2004 PLUMBING SECTION 405.3.1 WATER |
| | CLOSETS, URINALS, LAVATORIES AND BIDETS. |
| | |
| | **NO COMMENT RESPONSE FROM THE DESIGNER AND THE |
| | RESUMMITED PLAN SHEET INDICATES THE REQUESTED SPACING |
| | FOR THE FRONT OF THE WATER CLOSET, HOWEVER WITH THE |
| | WATER CLOSET BEING SET AT 45 DEGREES THE BACK OF THE |
| | WATER CLOSET IS NOT COMPLIANT. THE RESUBMITTED PLAN |
| | SHEET IS NOT INDICATING THE REQUESTED SPACING FOR THE |
| | LAVATORY. |
| | |
| | 6. "OK" COMMENT ADDRESSED. |
| | |
| | 7. "OK" COMMENT ADDRESSED.. |
| | |
| | 8. "OK" COMMENT ADDRESSED. |
| | |
| | 9. "OK" COMMENT ADDRESSED. |
| | |
| | 10. "OK" COMMENT ADDRESSED. |
| | |
| | 11. "OK" COMMENT ADDRESSED. |
| | |
| | **THE FOLLOWING IS A NEW COMMENT DUE THE RESUBMITTED |
| | SANITARY RISER. |
| | |
| | 12. SHEET 4 SANITARY RISER DIAGRAM: DELETE SOIL AND |
| | WASTE STACK IN THE FOLLOWING BATHROOM VENT LOCATIONS. |
| | MASTER BATH, POOL BATH, BATH 3, AND BATH 4. PER |
| | FBC-2004 PLUMBING SECTON 701.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |