2008-09-10 11:59:44PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 4, FOUNDATION PLAN: PLEASE CORRECT THE
 FOLLOWING MISIDENTIFIED 2" AND 3" VENTS FOR BATH 2, AND
 BATH 3, TO BE THE FOLLOWING. PER FBC-2004 PLUMBING
 SECTION 701.1 SCOPE.
  
 A} BATH 3, THE 2" VENT SHOULD BE INDICATED AS A 2"
 WASTE STACK.
  
 B} BATH 3, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL
 STACK.
  
 C} BATH 4, THE 2" VENT SHOULD BE INDICATED AS A 2"
 WASTE STACK.
  
 D} BATH 4, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL
 STACK.
  
 2. SHEET 4, SANITARY RISER DIAGRAM AND FOUNDATION PLAN
 UNDERGROUND PLUMBING PLAN: AT A MINIMUM THE SANITARY
 RISER DIAGRAM SHOULD REFLECT THE FOUNDATION PLAN
 UNDERGROUND PLUMBING PLAN. PLEASE CORRELATE THE
 FOLLOWING BATHROOMS PER FBC-2004 PLUMBING SECTION 701.1
 SCOPE.
  
 A} MASTER BATH WHIRPOOL TUB AND WATER CLOSET.
  
 B} BATH 2.
  
 3. SHEET 4, SANITARY RISER DIAGRAM: THE MASTER BATH 1,
 SHOWER REQUIRES A VENT. PLEASE KNOW THAT ONE IS
 INDICATED ON THE FOUNDATION PLAN, HOWEVER IT IS NOT
 BEING INDICATED ON THE RISER DIAGRAM. PER FBC-2004
 PLUMBING SECTION 901.2.1 VENTING REQUIRED.
  
 4. SHEET 4, SANITARY RISER DIAGRAM POWDER ROOM BATH:
 ONLY FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE
 SAME FLOOR ARE PERMITTED TO BE VENTED BY A WET VENT.
 ANY ADDITIONAL FIXTURES (KITCHEN SINK, LAUNDRY SINK,
 WASHER, AND BATH #3) SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. EPR FBC-2004 PLUMBING SECTION 909.1 WET VENT
 PERMITTED.
  
 5. SHEET 2, GROUND FLOOR PLAN, POWDER ROOM: CLEARLY
 INDICATE THE WATER CLOSET AND LAVATORY SPACING FROM THE
 SIDE WALLS. A WATER CLOSET AND LAVATORY SHALL NOT BE
 SET CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE
 WALL. PER FBC-2004 PLUMBING SECTION 405.3.1 WATER
 CLOSETS, URINALS, LAVATORIES AND BIDETS.
  
 6. SHEET 4, SANITARY RISER DIAGRAM: CLEARLY INDICATE
 THE REQUIRED CLEANOUTS AT THE BASE OF THE FOLLOWING
 STACKS. PER FBC-2004 PLUMBING SCTION 708.3.4.
  
 A} BATH 3, 3" SOIL AND 2" WASTE STACKS.
  
 B} BATH 4, 3" SOIL AND 2" WASTE STACK.
  
 7. SHEET 4, SANITARY RISER DIAGRAM: CLEARLY INDICATE
 THE REQUIRED CLEANOUT FOR THE WASHING MACHINE WASTE
 STACK A FOUR FEET ABOVE FINISH FLOOR (4' A.F.F.). PRE
 FBC-2004 PLUMBING SECTION 708.9 ACCESS.
  
 8. SHEET 4, SANITARY RISER DIAGRAM: CLEARLY INDICATE
 THE CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER AS BEING A TWO-WAY CLEANOUT. PER
 FBC-2004 PLUMBING SECTION 708.3.5.
  
 9. SHEET 4, FOUNDATION PLAN PLUMBING UNDERGROUND:
 CLEARLY IDENTIFY THE CLEANOUT OUTSIDE OF THE LAUNDRY
 ROOM BY THE DRYER VENT. PER FBC-2004 PLUMBING SECTION
 701.1 SCOPE.
  
 10. SUBMITTED ENERGY CALCULATIONS ARE INDICATING A 50
 GAL. ELECTRIC WATER HEATER, HOWEVER SUBMITTED PLAN
 SHEET 2, ARE INDICATING TWO TANKLESS WATER HEATERS.
 PLEASE CORRELATE THIS ON THE RESUBMITTAL. PER FBC-2004
 BUILDING CHAPTER 13, SECTION 13-100.2 INTENT.
  
 11. SUBMITTED ENERGY CALCULATION NEED TO BE SIGNED BY
 OWNER/AGENT. PER FBC-2004 BUILDING CHAPTER 13, SECTION
 13-103.3 BUILDING PERMITS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  