| 2008-09-10 11:59:44 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 4, FOUNDATION PLAN: PLEASE CORRECT THE |
| | FOLLOWING MISIDENTIFIED 2" AND 3" VENTS FOR BATH 2, AND |
| | BATH 3, TO BE THE FOLLOWING. PER FBC-2004 PLUMBING |
| | SECTION 701.1 SCOPE. |
| | |
| | A} BATH 3, THE 2" VENT SHOULD BE INDICATED AS A 2" |
| | WASTE STACK. |
| | |
| | B} BATH 3, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL |
| | STACK. |
| | |
| | C} BATH 4, THE 2" VENT SHOULD BE INDICATED AS A 2" |
| | WASTE STACK. |
| | |
| | D} BATH 4, THE 3" VENT SHOULD BE INDICATED AS A 3" SOIL |
| | STACK. |
| | |
| | 2. SHEET 4, SANITARY RISER DIAGRAM AND FOUNDATION PLAN |
| | UNDERGROUND PLUMBING PLAN: AT A MINIMUM THE SANITARY |
| | RISER DIAGRAM SHOULD REFLECT THE FOUNDATION PLAN |
| | UNDERGROUND PLUMBING PLAN. PLEASE CORRELATE THE |
| | FOLLOWING BATHROOMS PER FBC-2004 PLUMBING SECTION 701.1 |
| | SCOPE. |
| | |
| | A} MASTER BATH WHIRPOOL TUB AND WATER CLOSET. |
| | |
| | B} BATH 2. |
| | |
| | 3. SHEET 4, SANITARY RISER DIAGRAM: THE MASTER BATH 1, |
| | SHOWER REQUIRES A VENT. PLEASE KNOW THAT ONE IS |
| | INDICATED ON THE FOUNDATION PLAN, HOWEVER IT IS NOT |
| | BEING INDICATED ON THE RISER DIAGRAM. PER FBC-2004 |
| | PLUMBING SECTION 901.2.1 VENTING REQUIRED. |
| | |
| | 4. SHEET 4, SANITARY RISER DIAGRAM POWDER ROOM BATH: |
| | ONLY FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE |
| | SAME FLOOR ARE PERMITTED TO BE VENTED BY A WET VENT. |
| | ANY ADDITIONAL FIXTURES (KITCHEN SINK, LAUNDRY SINK, |
| | WASHER, AND BATH #3) SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. EPR FBC-2004 PLUMBING SECTION 909.1 WET VENT |
| | PERMITTED. |
| | |
| | 5. SHEET 2, GROUND FLOOR PLAN, POWDER ROOM: CLEARLY |
| | INDICATE THE WATER CLOSET AND LAVATORY SPACING FROM THE |
| | SIDE WALLS. A WATER CLOSET AND LAVATORY SHALL NOT BE |
| | SET CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE |
| | WALL. PER FBC-2004 PLUMBING SECTION 405.3.1 WATER |
| | CLOSETS, URINALS, LAVATORIES AND BIDETS. |
| | |
| | 6. SHEET 4, SANITARY RISER DIAGRAM: CLEARLY INDICATE |
| | THE REQUIRED CLEANOUTS AT THE BASE OF THE FOLLOWING |
| | STACKS. PER FBC-2004 PLUMBING SCTION 708.3.4. |
| | |
| | A} BATH 3, 3" SOIL AND 2" WASTE STACKS. |
| | |
| | B} BATH 4, 3" SOIL AND 2" WASTE STACK. |
| | |
| | 7. SHEET 4, SANITARY RISER DIAGRAM: CLEARLY INDICATE |
| | THE REQUIRED CLEANOUT FOR THE WASHING MACHINE WASTE |
| | STACK A FOUR FEET ABOVE FINISH FLOOR (4' A.F.F.). PRE |
| | FBC-2004 PLUMBING SECTION 708.9 ACCESS. |
| | |
| | 8. SHEET 4, SANITARY RISER DIAGRAM: CLEARLY INDICATE |
| | THE CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND |
| | BUILDING SEWER AS BEING A TWO-WAY CLEANOUT. PER |
| | FBC-2004 PLUMBING SECTION 708.3.5. |
| | |
| | 9. SHEET 4, FOUNDATION PLAN PLUMBING UNDERGROUND: |
| | CLEARLY IDENTIFY THE CLEANOUT OUTSIDE OF THE LAUNDRY |
| | ROOM BY THE DRYER VENT. PER FBC-2004 PLUMBING SECTION |
| | 701.1 SCOPE. |
| | |
| | 10. SUBMITTED ENERGY CALCULATIONS ARE INDICATING A 50 |
| | GAL. ELECTRIC WATER HEATER, HOWEVER SUBMITTED PLAN |
| | SHEET 2, ARE INDICATING TWO TANKLESS WATER HEATERS. |
| | PLEASE CORRELATE THIS ON THE RESUBMITTAL. PER FBC-2004 |
| | BUILDING CHAPTER 13, SECTION 13-100.2 INTENT. |
| | |
| | 11. SUBMITTED ENERGY CALCULATION NEED TO BE SIGNED BY |
| | OWNER/AGENT. PER FBC-2004 BUILDING CHAPTER 13, SECTION |
| | 13-103.3 BUILDING PERMITS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |