 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET #7, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} NOTE #1 REFERENCES THE WRONG CODE CYCLE FOR NFPA-72,
 CURRENTLY THE 2002 CYCLE IS REFERENCED BY THE FBC.106.5
 FBC,
  
 2} INDICATE THE SIZE AND NUMBER OF CONDUCTORS FEEDING
 THE MAIN DISCONNECT FROM THE METER. 215.5.
  
 3} 210.11 (C) (1)DWELLING UNITS
 (1) SMALL-APPLIANCE BRANCH CIRCUITS IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE
 OUTLETS SPECIFIED BY 210.52(B).*** ONLY ONE IS LISTED
 IN THE PANEL SCHEDULE.ALSO SEE 210.52(B)(1) FOR DINING
 ROOM AND BREAKFAST ROOM REQUIREMENTS.
  
 4} THERE IS ONE WATER HEATER ON THE PANEL SCHEDULE AND
 TWO TANKLESS SHOWN ON THE PLAN, CORRELATE SAME. ALSO
 CHECK THE MANUFACTURERS SPEC'S FOR KW RATINGS AND OCP.
 MOST TANKLESS MODELS HAVE A MUCH HIGHER RATING THAN 30
 AMPS. ADJUST THE LOAD CALCULATIONS ACCORDINGLY.
  
 5} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THE MASTER BATH NEEDS
 ANOTHER RECEPTACLE TO MEET COMPLIANCE.
  
 6} THE "GREAT ROOM" NEEDS ANOTHER RECEPTACLE TO MEET
 SPACING REQUIREMENTS OF 210.52(A)(1)
  
 7} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.*** THE
 ISLAND RECEPTACLES MUST BE GFI AND THE COUNTERTOP
 SPACING IS NOT COMPLIANT.
  
  
 8} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY-NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.
 NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE
 TO THE COMMENTS MADE IN THIS REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  