| Date |
Text |
| 2008-09-18 16:17:49 | 2004 FBC W/2007 REVISIONS |
| | NEW SFD |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |
| | 3) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING |
| | REQUIRED. |
| | WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE |
| | CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS |
| | SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED |
| | SPACE DOES NOT EXCEED 1,000 SQUARE FEET. DRAFTSTOPPING |
| | SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY |
| | EQUAL AREAS. WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR |
| | MEMBRANE ABOVE AND A CEILING MEMBRANE BELOW |
| | DRAFTSTOPPING SHALL BE PROVIDED IN FLOOR/CEILING |
| | ASSEMBLIES UNDER THE FOLLOWING CIRCUMSTANCES: |
| | 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. |
| | 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB |
| | OR PERFORATED MEMBERS. |
| | |
| | 4) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE 2 X 12 BEAMS AT THE REAR COVERED PORCH AND THE 2 X |
| | 10 BEAMS AT THE FRONT ENTRY TO THE CMU WALLS. FBC |
| | R301.1 |
| | |
| | 5) PROVIDE A STRUCTURAL DETAIL OF THE PIERS AT THE REAR |
| | SECOND FLOOR BALCONY THAT THE GUARDRAILS ATTACH TO. FBC |
| | TABLE R 301.5. |
| | |
| | 6) SPECIFY THE CONNECTORS THAT WILL BE USED AT THE BASE |
| | OF THE 6 X 6 WOOD COLUMNS AT THE COVERED BALCONY ABOVE |
| | THE ENTRY. SEE THE WALL SECTION ON SHEET 6. FBC R 301.1 |
| | |
| | 7) SHOW COMPLIANCE WITH FAC RULE 9B-3.0472 CARBON |
| | MONOXIDE PROTECTION. |
| | |
| | 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | CALCULATION FORM. FBC 13-600. |
| | |
| | 9) THE ENERGY CALCS. ARE INCORRECT. THE EXTERIOR WOOD |
| | FRAME WALLS ON THE SECOND FLOOR ARE NOT LISTED. THE CMU |
| | WALL ADJACENT TO THE GARAGE IS NOT LISTED. THE WALL |
| | SECTIONS ON SHEET 4 SPECIFY R-5 INSULATION AT THE |
| | MASONRY WALLS AND THE FORM LISTS R-4.2. THE CONDITIONED |
| | SPACE IS SPECIFIED AS 3790 SQFT ON SHEET 2 OF THE PLANS |
| | AND 3684 SQFT IS ON THE FORM. PLEASE CORRECT THE FORM. |
| | |
| | 10) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE METAL |
| | ROOFING (SLOPED) AND THE BUILT UP ROOFING (FLAT). DCA |
| | RULE 9B-72 |
| | |
| | 12) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE STEEL |
| | OUTSWING DOOR AT THE GARAGE AND THE INSWING DOOR AT THE |
| | POOL BATH. DCA RULE 9B-72 |
| | |
| | 13) THE NAN YA PLASTICS CORP. FIBERGLASS DOOR DOES NOT |
| | HAVE THE STATE OF FLORIDA PRODUCT APPROVAL OR A |
| | MIAMI-DADE NOA. SUBMIT A FLORIDA PRODUCT APPROVAL OR |
| | MIAMI-DADE NOA FOR ANOTHER DOOR OR APPLY FOR LOCAL |
| | PRODUCT APPROVAL. SEE DCA RULE 9B-72. |
| | |
| | 14) THE PLANS SPECIFY A STEEL DOOR AT THE ENTRY, NOT A |
| | FIBERGLASS ONE. PLEASE COORDINATE PRODUCT APPROVALS |
| | WITH THE PLANS, DCA RULE 9B-72. |
| | |