2009-01-16 14:56:05** DENIED PLANS**
  
 **THIRD REVIEW**
  
  
  
  
 1) NOTE: THE TITLE BLOCKS ARE STILL MISSING THE
 REQUIRED LICENSING PER FS 471.023 AND FAC 61G15-23.002.
 THE CERTIFICATE # AS SHOWN FOR KING STRUCTURAL GROUP IS
 IN FACT THE PE LICENSE NUMBER. A CERTIFICATE OF
 AUTHORIZATION NUMBER IS REQUIRED BY STATE STATUTES.
 THIS HAS BEEN NOTED THREE TIMES WITH NO CORRECTION FOR
 LICENSING. PLANS MAY BE RETAINED FOR REVIEW FROM THE
 FLORIDA BOARD OF ENGINEERS LEGAL COUNSEL.
  
 2) NOTE: PLEASE SEE ALL PREVIOUS NOTES. LIGHTING
 CONTROLS DO NOT COMPLY TO 13-415.1.ABC.1, .1.1, .1.2.
 A MANUAL SWITCH IS NOT THE ONLY REQUIREMENT.
 MUST CONTAIN AN AUTOMATIC MEANS OF SHUTTING OFF THE
 LIGHTING.
  
 3) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED AS
 REQUESTED ON ALL PREVIOUS REVIEWS. THE RESPONSE
 MENTIONS THE CIRCUITING WAS ADDED HOWEVER THESE ARE
 BLANK ON PLANS.
 PLEASE PROVIDE LOADS ON THE EXISTING PANEL WHICH IS
 BEING NOTED WITH THE NEW LOADS ADDED.
 THE LOAD ON THE CIRCUIT FOR THE A/C IS SHOWN AT 2500VA
 WHICH FAR EXCEEDS THE RATING OF A 1-POLE 20AMP BRANCH
 CIRCUIT.
 240.4,310.16,408.4, 220.87, 215.5 ETC
  
 4) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE RESPONSE MENTIONS THIS *ADDITION CONTAINS A SINGLE
 INDEPENDENTLY OPERATED LIGHTING SYSTEM*
 THIS OFFICE DOES NOT KNOW WHAT THIS RESPONSE IS FOR???
 THE ABOVE SECTIONS GIVEN SINCE THE BEGINNING OF THE
 REVIEW PROCESS IS FOR MINIMUM LIGHTING PERFORMANCE
 CALCULATIONS PER THE SECTIONS ABOVE FROM THE FLORIDA
 BUILDING CODE. THERE IS NO EXCEPTION FOR INDEPENDENT
 SYSTEMS WHICH EXEMPTS LIGHTING PERFORMANCE CALCULATIONS
 AND ENERGY COMPLIANCE WITH FBC CHAPTER 13.
  
 5) NOTE: THE ELECTRICAL SHEET WAS REVISED TO INDICATE
 CODES HOWEVER THE NFPA-70 DOES NOT SHOW ANY YEAR
 EDITION.
 PLANS MAY NOT STATE LATEST EDITION AS THE CODES ARE
 ALWAYS BEING REVISED. THE CODES ARE BASED ON THE TIME
 OF PERMIT APPLICATION PER FS 553.73.
  
 6) NOTE: PER NOTICE GIVEN ON PREVIOUS REVIEW A FEE HAS
 NOW BEEN ASSESSED PER FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THERE ARE SEVERAL
 SECTIONS OF CODES WHICH WERE REPEATED. THE AMOUNT OF
 $672 IS DUE BEFORE THE FOLLOWING RESUB. THE RESUB FEE
 WILL NOT BE REQUIRED.
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II