| 2009-01-26 12:44:36 | BUILDING PLAN REVIEW |
| | PERMIT: 08080664 |
| | ADD: 1801 N FLAGLER DR |
| | CONT: SEACREST SERVICES |
| | TEL: (561)346-8449 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | JAN.26/ 2009 |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) 2ND REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS, |
| | REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL |
| | REQUIRE A THRESHOLD BUILDING REQUIRING A THRESHOLD |
| | INSPECTOR THEN (3) THREE SETS OF ALL SAID DOCUMENTS |
| | WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* /2004 |
| | SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE |
| | CODE. |
| | |
| | 1C) COMPLIED. |
| | |
| | 1D)2 COMPLIED. |
| | |
| | 1E) 3RD REQUEST, PLANS FAIL TO INDICATE DESIGNED TO THE |
| | 2004 EXISTING BUILDING CODE, CHAPTER 9 ADDITIONS. |
| | |
| | 2) ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | |
| | B) COMPLIED. |
| | |
| | C) COMPLIED. |
| | |
| | D) 3RD REQUEST, THE RETURN COMMENTSINDICATE THAT NO |
| | FIRE SPRINKLERS WILL BE INSTALLED IN THE ADDITION. |
| | EXISSTING BUILDING CODE SECTION 902.3 AND 901.2 AN |
| | ADDITION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY. |
| | THIS BUILDING IS CONSIDERED A HIGH RISE AND SINCE THERE |
| | ARE FIRE SPRINKLERS WITHIN THE BUILDING THEN THE SYSTEM |
| | WILL NEED TO BE EXTENDED TO WITHIN THE ADDITION, PLEASE |
| | SHOW THE EXTENSION OF THE FIRE SPRINKLER LINE. |
| | |
| | E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED, YES |
| | HIGHRISE 2004 EXISTING BUILDING CODE 901.2/ 902.3 AND |
| | 2004 FBC403.2 AUTOMATIC FIRE SPRINKLER SYSTEMS. |
| | |
| | G-I) COMPLIED. |
| | . |
| | H |
| | 3) THIS BUILDING IS A 9 STORY BUILDING OR CONSIDERED A |
| | THRESHOLD BUILDING REQUIRING : |
| | FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 3A) 3RD REQUEST, THE THRESHOLD INSPECTION PLAN |
| | SUBMITTED IS NOT SIGNED NOR SEALED. THRESHOLD |
| | INSPECTION PLAN 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL |
| | INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| | STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE |
| | SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 3B)3RD REQUEST, THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN |
| | CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| | (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT |
| | MAY BE ISSUED. |
| | SEE ATTACHMENT FOR FORMS. |
| | |
| | 3C) COMPLIED. |
| | |
| | 4) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF |
| | WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS |
| | LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION |
| | CERTIFICATE WILL BE REQUIRED BEFORE A CERTIFICATE OF |
| | COMPLETION WILL BE AWARDED.. PLEASE INDICATE THE |
| | ELEVATION OF THE FLOOR SLAB. THE MINIMUM SLAB ELEVATION |
| | IS 7'-6". |
| | |
| | 5) SPOKE WITH THE ENGINEERS FIRM TODAY AND A SIGNED AND |
| | SEALED LETTER FROM THE SOILS ENGINEER WILL BE FORTH |
| | COMING FOR THE ONE STORY ADDITION. PLEASE PROVIDE 3 |
| | ORIGINAL SIGNED & SEALED SOILS REPORTS. 1802.2.1 |
| | QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF |
| | THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY |
| | INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY |
| | WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 6) COMPLIED. |
| | |
| | |
| | 7) 3RD REQUEST, SEMI-COMPLIED. THIS BUILDING TYPE WILL |
| | BE A MINIMUM OF TYPE IB PLEASE REVIEW COMBUSTIBLE/ |
| | NONCOMBUSTIBLES MATERIALS ALLOWED IN 603.1 FBC. WALL |
| | ASSEMBLIES ROOF FRAMING AND ROOF DECKS. |
| | ROOF DECKS THE PLANS DO SHOW TTHE FLAT DECK WITH B DECK |
| | GALVANIZED PANELS WWITH INSULATION AND A MANSARD STYLE |
| | PERMITERE WHICH TILE ARE ATTACHED. PLANS INDICATE THE |
| | USE OF 5/8" DENS-DECK FOR A SHEATHING, PLEASE NOTE THE |
| | PRODUCT APPROVAL METROTILE PAGES 4-4-7 ALL INDICATE THE |
| | USE ON 1/2 WOOD PLYWOOD OR WOOD PLANK. NOTE THERE IS NO |
| | GALVANIZED DECK THAT THE TILE ROOF SCREWS CAN PENETRATE |
| | TO ANCHOR THE ROOF TILE IN PLACE. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) 3D REQUEST, 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| | WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED "IN WRITING" ( SHOP DRAWING STAMP BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) FLAT ROOF REVIEW: THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | COMPLIED. __XX(1)_ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | ROOF HEIGHT IN FEET OF BUILDING NOT ADDITION..MEAN ROOF |
| | HEIGTH IS TAKEN FROM THE TOP OF THE HIGHRISE NOT THE |
| | ADDITION, NEGATIVE PRESSURES ARE TAKEN AT ROOF LEVEL, |
| | POSISTIVE PRESSURES BUILD UP FROM GRADE. |
| | |
| | __XX(2)__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO |
| | BE USED. NOTE THERE IS NO PRODUCT APPROVAL SUBMITTED |
| | FOR THE FLAT ROOF. |
| | |
| | _XX(3) ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR |
| | ZONE _2&3__ . AGAIN THERE IS NO PRODUCT APPROVAL FOR |
| | THE FLAT DECK. |
| | |
| | _XX__(4) THE SYSTEM PROVIDED STATES LIMITATION# 7, |
| | SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A |
| | REVISED FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | MAYBE NO SUBSYSTEM HIGHLIGHTED: |
| | _XX__ (5)THE SYSTEM PROVIDED INDICATES LIMITATION# 9, |
| | NO ENHANCED FASTENING ALLOWED. |
| | |
| | 12) ROOFING ASSEMBLIES, METROTILE MANUFACTURING WHICH |
| | SYSTEM NOT IDENTIFIED, NOR TYPE OF FASTENING |
| | SYSTEM.1609.6.2.2 COMPONENTS AND CLADDING. |
| | |
| | 13) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 14) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL |
| | BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 15) 3RD REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |