Plan Review Notes
Plan Review Notes For Permit 08080664
Permit Number 08080664
Review Stop B
Sequence Number 3
Notes
Date Text
2009-01-26 12:44:36BUILDING PLAN REVIEW
 PERMIT: 08080664
 ADD: 1801 N FLAGLER DR
 CONT: SEACREST SERVICES
 TEL: (561)346-8449
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 JAN.26/ 2009
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) 2ND REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS,
 REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHOLD BUILDING REQUIRING A THRESHOLD
 INSPECTOR THEN (3) THREE SETS OF ALL SAID DOCUMENTS
 WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) COMPLIED.
  
 1D)2 COMPLIED.
  
 1E) 3RD REQUEST, PLANS FAIL TO INDICATE DESIGNED TO THE
 2004 EXISTING BUILDING CODE, CHAPTER 9 ADDITIONS.
  
 2) ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
  
 B) COMPLIED.
  
 C) COMPLIED.
  
 D) 3RD REQUEST, THE RETURN COMMENTSINDICATE THAT NO
 FIRE SPRINKLERS WILL BE INSTALLED IN THE ADDITION.
 EXISSTING BUILDING CODE SECTION 902.3 AND 901.2 AN
 ADDITION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY.
 THIS BUILDING IS CONSIDERED A HIGH RISE AND SINCE THERE
 ARE FIRE SPRINKLERS WITHIN THE BUILDING THEN THE SYSTEM
 WILL NEED TO BE EXTENDED TO WITHIN THE ADDITION, PLEASE
 SHOW THE EXTENSION OF THE FIRE SPRINKLER LINE.
  
 E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED, YES
 HIGHRISE 2004 EXISTING BUILDING CODE 901.2/ 902.3 AND
 2004 FBC403.2 AUTOMATIC FIRE SPRINKLER SYSTEMS.
  
 G-I) COMPLIED.
 .
 H
 3) THIS BUILDING IS A 9 STORY BUILDING OR CONSIDERED A
 THRESHOLD BUILDING REQUIRING :
 FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) 3RD REQUEST, THE THRESHOLD INSPECTION PLAN
 SUBMITTED IS NOT SIGNED NOR SEALED. THRESHOLD
 INSPECTION PLAN 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 3B)3RD REQUEST, THRESHOLD INSPECTOR: WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT
 MAY BE ISSUED.
 SEE ATTACHMENT FOR FORMS.
  
 3C) COMPLIED.
  
 4) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE A CERTIFICATE OF
 COMPLETION WILL BE AWARDED.. PLEASE INDICATE THE
 ELEVATION OF THE FLOOR SLAB. THE MINIMUM SLAB ELEVATION
 IS 7'-6".
  
 5) SPOKE WITH THE ENGINEERS FIRM TODAY AND A SIGNED AND
 SEALED LETTER FROM THE SOILS ENGINEER WILL BE FORTH
 COMING FOR THE ONE STORY ADDITION. PLEASE PROVIDE 3
 ORIGINAL SIGNED & SEALED SOILS REPORTS. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) COMPLIED.
  
  
 7) 3RD REQUEST, SEMI-COMPLIED. THIS BUILDING TYPE WILL
 BE A MINIMUM OF TYPE IB PLEASE REVIEW COMBUSTIBLE/
 NONCOMBUSTIBLES MATERIALS ALLOWED IN 603.1 FBC. WALL
 ASSEMBLIES ROOF FRAMING AND ROOF DECKS.
 ROOF DECKS THE PLANS DO SHOW TTHE FLAT DECK WITH B DECK
 GALVANIZED PANELS WWITH INSULATION AND A MANSARD STYLE
 PERMITERE WHICH TILE ARE ATTACHED. PLANS INDICATE THE
 USE OF 5/8" DENS-DECK FOR A SHEATHING, PLEASE NOTE THE
 PRODUCT APPROVAL METROTILE PAGES 4-4-7 ALL INDICATE THE
 USE ON 1/2 WOOD PLYWOOD OR WOOD PLANK. NOTE THERE IS NO
 GALVANIZED DECK THAT THE TILE ROOF SCREWS CAN PENETRATE
 TO ANCHOR THE ROOF TILE IN PLACE.
  
 8) COMPLIED.
  
 9) 3D REQUEST, 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED "IN WRITING" ( SHOP DRAWING STAMP BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 10) COMPLIED.
  
 11) FLAT ROOF REVIEW: THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 COMPLIED. __XX(1)_ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT IN FEET OF BUILDING NOT ADDITION..MEAN ROOF
 HEIGTH IS TAKEN FROM THE TOP OF THE HIGHRISE NOT THE
 ADDITION, NEGATIVE PRESSURES ARE TAKEN AT ROOF LEVEL,
 POSISTIVE PRESSURES BUILD UP FROM GRADE.
  
 __XX(2)__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO
 BE USED. NOTE THERE IS NO PRODUCT APPROVAL SUBMITTED
 FOR THE FLAT ROOF.
  
 _XX(3) ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR
 ZONE _2&3__ . AGAIN THERE IS NO PRODUCT APPROVAL FOR
 THE FLAT DECK.
  
 _XX__(4) THE SYSTEM PROVIDED STATES LIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 MAYBE NO SUBSYSTEM HIGHLIGHTED:
 _XX__ (5)THE SYSTEM PROVIDED INDICATES LIMITATION# 9,
 NO ENHANCED FASTENING ALLOWED.
  
 12) ROOFING ASSEMBLIES, METROTILE MANUFACTURING WHICH
 SYSTEM NOT IDENTIFIED, NOR TYPE OF FASTENING
 SYSTEM.1609.6.2.2 COMPONENTS AND CLADDING.
  
 13) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 14) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 15) 3RD REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.