| 2008-11-22 13:15:09 | |
| | |
| | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. MINI-SPLIT OK. HOWEVER, THE FOLLOWING ITEMS SHALL BE |
| | ADDRESSED AS A RESULT OF THE ADDITION OF THE MINI-SPLIT |
| | SYSTEM FROM PREVIOUS PLANS: |
| | |
| | A) PLEASE SHOW ON PLANS THE MEANS AND LOCATION OF |
| | CONDENSATE DISPOSAL. CONDENSATE FROM ALL COOLING COILS |
| | SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN |
| | APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT |
| | DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO |
| | CAUSE A NUISANCE IN ACCORDANCE WITH FBCM 307.2.1. |
| | CONDENSATE SHALL NOT DISCHARGE INTO A SANITARY SEWER |
| | SYSTEM PER CITY ORDINANCE. |
| | |
| | B) PROVIDE WIND RESISTANCE INFORMATION FOR THE OUTDOOR |
| | CONDENSING UNIT. MECHANICAL APPLIANCES AND SUPPORTS |
| | THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT |
| | AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM |
| | 301.13. SHOW HOW THE APPLIANCE IS TO BE SECURED TO |
| | RESIST WIND PRESSURES AND PROVIDE MANUFACTURER'S DATA |
| | SHOWING THE APPLIANCE IS DESIGNED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH THIS SECTION. |
| | |
| | C) THERE ARE NO PROVISIONS ON ELECTRICAL PLANS TO |
| | PROVIDE POWER FOR THE INDOOR OR OUTDOOR PORTIONS OF |
| | THIS SYSTEM. PLEASE CLARIFY IN ACCORDANCE WITH FBCM |
| | 304.1. |
| | |
| | 2. **NOT ADDRESSED** SHOW HOW THE REQUIRED RATE OF |
| | VENTILATION IS TO BE PROVIDED IN ACCORDANCE WOTH FBCM |
| | 403. |
| | |
| | 3. **NOT ADDRESSED** THE ENGINEERING BUSINESS |
| | CERTIFICATE OF AUTHORIZATION NUMBER SHALL APPEAR IN THE |
| | TITLE BLOCK IN ACCORDANCE WITH FAC RULE 61G15-23.002. |
| | **THERE IS STILL NO CERTIFICATE OF AUTHORIZATION NUMBER |
| | IN THEE ENGINEERING BUSINESS TITLE BLOCK. PLEASE SEE |
| | FAC RULE 61G15-23.002 FOR ENGINEERING BUSINESS TITLE |
| | BLOCK REQUIREMENTS IN ACCORDANCE WITH F.S. 471. |
| | |