2008-11-22 13:15:09 
  
 REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. MINI-SPLIT OK. HOWEVER, THE FOLLOWING ITEMS SHALL BE
 ADDRESSED AS A RESULT OF THE ADDITION OF THE MINI-SPLIT
 SYSTEM FROM PREVIOUS PLANS:
  
 A) PLEASE SHOW ON PLANS THE MEANS AND LOCATION OF
 CONDENSATE DISPOSAL. CONDENSATE FROM ALL COOLING COILS
 SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN
 APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
 CONDENSATE SHALL NOT DISCHARGE INTO A SANITARY SEWER
 SYSTEM PER CITY ORDINANCE.
  
 B) PROVIDE WIND RESISTANCE INFORMATION FOR THE OUTDOOR
 CONDENSING UNIT. MECHANICAL APPLIANCES AND SUPPORTS
 THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM
 301.13. SHOW HOW THE APPLIANCE IS TO BE SECURED TO
 RESIST WIND PRESSURES AND PROVIDE MANUFACTURER'S DATA
 SHOWING THE APPLIANCE IS DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THIS SECTION.
  
 C) THERE ARE NO PROVISIONS ON ELECTRICAL PLANS TO
 PROVIDE POWER FOR THE INDOOR OR OUTDOOR PORTIONS OF
 THIS SYSTEM. PLEASE CLARIFY IN ACCORDANCE WITH FBCM
 304.1.
  
 2. **NOT ADDRESSED** SHOW HOW THE REQUIRED RATE OF
 VENTILATION IS TO BE PROVIDED IN ACCORDANCE WOTH FBCM
 403.
  
 3. **NOT ADDRESSED** THE ENGINEERING BUSINESS
 CERTIFICATE OF AUTHORIZATION NUMBER SHALL APPEAR IN THE
 TITLE BLOCK IN ACCORDANCE WITH FAC RULE 61G15-23.002.
 **THERE IS STILL NO CERTIFICATE OF AUTHORIZATION NUMBER
 IN THEE ENGINEERING BUSINESS TITLE BLOCK. PLEASE SEE
 FAC RULE 61G15-23.002 FOR ENGINEERING BUSINESS TITLE
 BLOCK REQUIREMENTS IN ACCORDANCE WITH F.S. 471.
  