| Plan Review Notes For Permit 08080664 |
| Permit Number |
08080664 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-11-24 16:02:27 | ***DENIED*** | | | | | | COMMENTS WERE TAKEN DIRECTLY FROM THE FIRST FIRE | | | REVIEW: | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 2) ILLUSTRATE EXISTING DRIVE WIDTH AND OTHER PERTINENT | | | DIMENSIONS AS IT APPLIES TO THE NEW GUARD HOUSE. | | | | | | 3) PROVIDE INFORMATION REGARDING NEW GATE ARMS. IE | | | FAILSAFE MECHANISM IN EVENT OF POWER LOSS, WIDTH OF | | | ARMS, POWER SOURCE ETC. PROVIDE MANUFACTURER | | | SPECIFICATION SHEETS. | | | | | | 4) PLANS ILLUSTRATE A NEW CONCRETE WALK WITH SLOPE. | | | INDICATE LENGTH OF WALK AND DIMENSIONS OF SLOPE. | | | | | | 5) WILL THE GUARD HOUSE BE STAFFED? | | | | | | | | | ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER | | | INDICATING HOW AND WHERE ON THE PLANS EACH COMMENT WAS | | | ADDRESSED WOULD HELP TO EXPEDITE THE PLAN REVIEW | | | PROCESS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|