Plan Review Notes
Plan Review Notes For Permit 08080664
Permit Number 08080664
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-18 11:49:45 
  
  
 ** FAILED 2ND REVIEW **
  
 ** PLEASE SEE THAT MANY NOTES FORM PREVIOUS REVIEW ARE
 STILL NOT ADDRESSED.
  
  
 1) NOTE: PLEASE SEE TITLE BLOCKS ARE STILL MISSING
 REQUIRED LICENSING UNDER FS 471.023, FAC61G15-23.002.
 PLEASE INCLUDE INFORMATION. PLEASE KNOW WORKING AS A
 FIRM WITHOUT LICENSING IS REQUIRED TO BE FORWARDED TO
 BE SENT TO THE FLORIDA BOARD OF ENGINEERS. PLEASE
 SUPPLY INFORMATION OR THIS OFFICE WILL HAVE NO CHOICE
 BUT TO FORWARD AS STATED.
  
 2) NOTE: PLEASE INCLUDE ALL REQUIRED CODES FOR MINIMUM
 DESIGN FOR THIS TRADE REVIEWER AS FOLLOWS.
 2004 FBC W/2007 REVISION.
 2003 NFPA-101
 2005 NFPA-70
  
 3) NOTE: PLEASE SUBMIT LIGHTING INFORMATION FOR FBC
 CHAPTER 13. 13-415.2.ABC.1.1,.1.2, .1.3.
 PLEASE SEE THAT INFORMATION ABOUT ENERGY CALCULATIONS
 PER 13-400.3
  
 4) NOTE: PLEASE COMPLETE CIRCUITING, COMPLETE WIRING
 METHODS FOR ALL RECEPTACLES, GROUNDING, BONDING,
 BREAKERS, ETC PANEL SCHEDULE, FEEDERS, LOADS ETC.
 408.4,240.4,310.16,220.87,225.31-225.39
  
 5) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2, .1.3 AND
 .1.4 FOR REQUIRED MINIMUM LIGHTING CONTROLS.
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS A
 STATUTORY REQUIREMENT AND ONLY A NOTICE GIVEN AT THIS
 TIME AS THERE ARE SEVERAL REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  