| 2008-11-18 11:49:45 | |
| | |
| | |
| | ** FAILED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THAT MANY NOTES FORM PREVIOUS REVIEW ARE |
| | STILL NOT ADDRESSED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE TITLE BLOCKS ARE STILL MISSING |
| | REQUIRED LICENSING UNDER FS 471.023, FAC61G15-23.002. |
| | PLEASE INCLUDE INFORMATION. PLEASE KNOW WORKING AS A |
| | FIRM WITHOUT LICENSING IS REQUIRED TO BE FORWARDED TO |
| | BE SENT TO THE FLORIDA BOARD OF ENGINEERS. PLEASE |
| | SUPPLY INFORMATION OR THIS OFFICE WILL HAVE NO CHOICE |
| | BUT TO FORWARD AS STATED. |
| | |
| | 2) NOTE: PLEASE INCLUDE ALL REQUIRED CODES FOR MINIMUM |
| | DESIGN FOR THIS TRADE REVIEWER AS FOLLOWS. |
| | 2004 FBC W/2007 REVISION. |
| | 2003 NFPA-101 |
| | 2005 NFPA-70 |
| | |
| | 3) NOTE: PLEASE SUBMIT LIGHTING INFORMATION FOR FBC |
| | CHAPTER 13. 13-415.2.ABC.1.1,.1.2, .1.3. |
| | PLEASE SEE THAT INFORMATION ABOUT ENERGY CALCULATIONS |
| | PER 13-400.3 |
| | |
| | 4) NOTE: PLEASE COMPLETE CIRCUITING, COMPLETE WIRING |
| | METHODS FOR ALL RECEPTACLES, GROUNDING, BONDING, |
| | BREAKERS, ETC PANEL SCHEDULE, FEEDERS, LOADS ETC. |
| | 408.4,240.4,310.16,220.87,225.31-225.39 |
| | |
| | 5) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2, .1.3 AND |
| | .1.4 FOR REQUIRED MINIMUM LIGHTING CONTROLS. |
| | |
| | 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS A |
| | STATUTORY REQUIREMENT AND ONLY A NOTICE GIVEN AT THIS |
| | TIME AS THERE ARE SEVERAL REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |