| 2008-11-04 16:57:30 | BUILDING PLAN REVIEW |
| | PERMIT: 08080664 |
| | ADD: 1801 N FLAGLER DR |
| | CONT: SEACREST SERVICES |
| | TEL: (561)346-8449 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | NOV.04/2008 |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) 2ND REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS, |
| | REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL |
| | REQUIRE A THRESHOLD BUILDING REQUIRING A THRESHOLD |
| | INSPECTOR THEN (3) THREE SETS OF ALL SAID DOCUMENTS |
| | WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* /2004 |
| | SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE |
| | CODE. |
| | |
| | 1C) COMPLIED. |
| | |
| | 1D)2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME |
| | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| | 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.SHEET S-2 |
| | NEEDS UP DATING TO THE 2007 SUPPLEMENTS. |
| | |
| | 1E) 2ND REQUEST, PLANS FAIL TO INDICATE DESIGNED TO THE |
| | 2004 EXISTING BUILDING CODE, CHAPTER 9 ADDITIONS. |
| | |
| | 2) ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | |
| | B) COMPLIED. |
| | |
| | C) 2ND REQUEST, THE TYPE OF CONSTRUCTION AS DEFINED IN |
| | TABLE 503, CHAPTER 6 & TABLE 601.SHEET S-2 INDICATES |
| | THIS IS AN ADDITION TO A HIGH RISE. PLEASE REVIEW |
| | EXISTING BUILDING CODE 901.2 AN ADDITION SHALL NOT |
| | CREATE OR EXTEND A NONCONFORMITY. BY TRYING TO CLASSIFY |
| | THE ADDITION AS A TYPE V-B BUILDING YOU ARE ALSO |
| | DECLARING THE HIGHRISE AS A TYPE V-B BUILDING. THE |
| | HIGHRISE IS CONSIDERED EITHER A TYPE I-A OR I-B |
| | DEPENDING ON THE HEIGTH OF THE BUILDING SEE TABLE 503. |
| | IF THE ADDITION DID NOT COMMUNICATE WITH THE HIGHRISE |
| | NO DOOR LEADING INTO THE HIGHRISE AND WAS ACTUALLY TWO |
| | SEPERATE BUILDINGS WE WOULD STILL HAVE TO CONSIDER THE |
| | CLOSENESS OF THE TWO BUILDINGS SEE TABLE 602 FOR WALL |
| | RATINGS. |
| | |
| | D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED WITHIN |
| | THE HIGHRISE? AREA INCREASES MAY OF BEEN TAKEN FOR THE |
| | HIGHRISE, EXISTING BUILDING CODE, 902.2 |
| | |
| | E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | . |
| | H) NUMBER OF FLOORS FOR THE HIGHRISE THIS WILL ACTUALLY |
| | PROVIDE TTHE BUILDING TYPE CLASSIFICATION TABLE 503FBC, |
| | BUILDING .902.1 EXISTING BUILDING CODE. |
| | |
| | I ) SQ. FT. FOOTPRINT OF EXISTING BUILDING, TABLE 503 |
| | FBC, BUILDING & 902.2 EXISTING BUILDING CODE. |
| | |
| | 3) THIS BUILDING IS A 9 STORY BUILDING OR CONSIDERED A |
| | THRESHOLD BUILDING REQUIRING : |
| | FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 3A) 2ND REQUEST, THRESHOLD INSPECTION PLAN 105.13.1 THE |
| | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| | THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 3B)2ND REQUEST, THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN |
| | CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| | (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT |
| | MAY BE ISSUED. |
| | |
| | 3C) 2ND REQUEST, THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF |
| | WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS |
| | LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION |
| | CERTIFICATE WILL BE REQUIRED BEFORE A CERTIFICATE OF |
| | COMPLETION WILL BE AWARDED.. PLEASE INDICATE THE |
| | ELEVATION OF THE FLOOR SLAB. THE MINIMUM SLAB ELEVATION |
| | IS 7'-6". |
| | |
| | 5) PLEASE PROVIDE 3 ORIGINAL SIGNED & SEALED SOILS |
| | REPORTS. 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 6) COMPLIED. |
| | |
| | |
| | 7) 2ND REQUEST,THIS BUILDING TYPE WILL BE A MINIMUM OF |
| | TYPE IB PLEASE REVIEW COMBUSTIBLE/ NONCOMBUSTIBLES |
| | MATERIALS ALLOWED IN 603.1 FBC. WALL ASSEMBLIES ROOF |
| | FRAMING AND ROOF DECKS. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) 2ND REQUEST, 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| | WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED "IN WRITING" BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) SHEET S-1 ROOF FRAMING PLANS INDICATES THE USE OF |
| | 2X10'S BUT THERE IS NO INFORMATION AS TO HOW THEY WILL |
| | ATTACH TO THE EXISTING BUILDING, LEDGERS, BUCKETS ETC? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 11) FLAT ROOF REVIEW: THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT |
| | IN FEET OF BUILDING NOT ADDITION..MEAN ROOF HEIGTH IS |
| | TAKEN FROM THE TOP OF THE HIGHRISE NOT THE ADDITION, |
| | NEGATIVE PRESSURES ARE TAKEN AT ROOF LEVEL, POSISTIVE |
| | PRESSURES BUILD UP FROM GRADE. |
| | |
| | __XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| | USED. |
| | |
| | _XX___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | |
| | _XX__ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | MAYBE NO SUBSYSTEM HIGHLIGHTED: |
| | _XX__ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 12) ROOFING ASSEMBLIES, METROTILE MANUFACTURING WHICH |
| | SYSTEM NOT IDENTIFIED, NOR TYPE OF FASTENING |
| | SYSTEM.1609.6.2.2 COMPONENTS AND CLADDING. |
| | |
| | 13) PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 14) PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL |
| | BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 15) 2ND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |