Plan Review Notes
Plan Review Notes For Permit 08080664
Permit Number 08080664
Review Stop M
Sequence Number 1
Notes
Date Text
2008-09-09 11:14:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MECHANICAL NOTES CALL FOR NEW SUPPLY DUCT FROM
 EXISTING SYSTEM. THERE ARE NO PROVISIONS FOR RETURN AIR
 FROM THIS SPACE. SHOW HOW BALANCED RETURN IS TO BE
 ACHIEVED IN ACCORDANCE WITH FBCM 601.4.
  
 2. SHOW HOW THE REQUIRED RATE OF VENTILATION IS TO BE
 PROVIDED IN ACCORDANCE WOTH FBCM 403.
  
 3. THE ENGINEERING BUSINESS CERTIFICATE OF
 AUTHORIZATION NUMBER SHALL APPEAR IN THE TITLE BLOCK IN
 ACCORDANCE WITH FAC RULE 61G15-23.002.
  