| Plan Review Notes For Permit 08080664 |
| Permit Number |
08080664 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-09 11:14:19 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. MECHANICAL NOTES CALL FOR NEW SUPPLY DUCT FROM | | | EXISTING SYSTEM. THERE ARE NO PROVISIONS FOR RETURN AIR | | | FROM THIS SPACE. SHOW HOW BALANCED RETURN IS TO BE | | | ACHIEVED IN ACCORDANCE WITH FBCM 601.4. | | | | | | 2. SHOW HOW THE REQUIRED RATE OF VENTILATION IS TO BE | | | PROVIDED IN ACCORDANCE WOTH FBCM 403. | | | | | | 3. THE ENGINEERING BUSINESS CERTIFICATE OF | | | AUTHORIZATION NUMBER SHALL APPEAR IN THE TITLE BLOCK IN | | | ACCORDANCE WITH FAC RULE 61G15-23.002. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|