| 2008-09-10 14:46:53 | |
| | |
| | |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE FAC 61G15-23.022 FOR MISSING |
| | INFORMATION REQUIRED ON TITLE BLOCKS. PLEASE SEE FS |
| | 471.023 AS THE CERTIFICATE OF AUTHORIZATION NUMBER AS |
| | REQUIRED IS MISSING. |
| | |
| | 2) NOTE: PLANS ARE REQUIRED TO STATES THE CODES IN |
| | AFFECT AT THE TIME OF APPLICATION AND DESIGN. |
| | THE FOLLOW SHALL BE STATED ON THE PLANS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | |
| | 3) NOTE: PLEASE COMPLETE PLANS WITH ALL CIRCUITING, |
| | CONDUCTORS, PANEL, LOADS, FEEDS, GROUNDING/BONDING |
| | SYSTEM ETC. |
| | PLANS ARE NOT COMPLETE AT THIS TIME WITH SEVERAL ITEMS |
| | AS REQUIRED PER THE FOLLOWING SECTIONS OF THE NEC. |
| | . |
| | 250.50, 250.110 ETC GROUNDING/BONDING SYSTEM AND |
| | GROUNDING. |
| | 408.4, 310.16, 240.4 FOR CONDUCTORS, BREAKERS, PANEL |
| | SCHEDULE ETC |
| | 215.5,240.4,310.16, 220.87 FOR LOADS, FEEDERS, PANEL |
| | ETC |
| | |
| | |
| | ** PLANS STATE CIRCUITS TO EXISTING PANEL HOWEVER HOW |
| | CAN THIS PANEL BE EXISTING WHEN THE STRUCTURE HAS NOT |
| | BEEN BUILT AT THIS TIME. PLEASE BE SURE TO SECTIONS OF |
| | CODE GIVEN ABOVE. |
| | ** AS PLANS ARE NOT COMPLETE AT THIS TIME, THERE MAY |
| | VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-413.1.ABC.1.1, .1.2 FOR |
| | MINIMUM REQUIRED FOR VOLTAGE DROP. |
| | |
| | 5) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2 AND .1.3 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS. |
| | |
| | 6) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.4 FOR EXTERIOR |
| | LIGHTING ON THIS STRUCTURE. AT THIS TIME THE PLANS DO |
| | NOT INDICATE ANY LIGHTING FOR DRIVE UP, GATE AREAS ETC. |
| | |
| | 7) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 FOR |
| | LIGHTING CONTROLS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH |
| | INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK |
| | WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE |
| | REVIEW. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |