Notes
Date Text
2008-09-10 14:46:53 
  
  
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE FAC 61G15-23.022 FOR MISSING
 INFORMATION REQUIRED ON TITLE BLOCKS. PLEASE SEE FS
 471.023 AS THE CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED IS MISSING.
  
 2) NOTE: PLANS ARE REQUIRED TO STATES THE CODES IN
 AFFECT AT THE TIME OF APPLICATION AND DESIGN.
 THE FOLLOW SHALL BE STATED ON THE PLANS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
  
 3) NOTE: PLEASE COMPLETE PLANS WITH ALL CIRCUITING,
 CONDUCTORS, PANEL, LOADS, FEEDS, GROUNDING/BONDING
 SYSTEM ETC.
 PLANS ARE NOT COMPLETE AT THIS TIME WITH SEVERAL ITEMS
 AS REQUIRED PER THE FOLLOWING SECTIONS OF THE NEC.
 .
 250.50, 250.110 ETC GROUNDING/BONDING SYSTEM AND
 GROUNDING.
 408.4, 310.16, 240.4 FOR CONDUCTORS, BREAKERS, PANEL
 SCHEDULE ETC
 215.5,240.4,310.16, 220.87 FOR LOADS, FEEDERS, PANEL
 ETC
  
  
 ** PLANS STATE CIRCUITS TO EXISTING PANEL HOWEVER HOW
 CAN THIS PANEL BE EXISTING WHEN THE STRUCTURE HAS NOT
 BEEN BUILT AT THIS TIME. PLEASE BE SURE TO SECTIONS OF
 CODE GIVEN ABOVE.
 ** AS PLANS ARE NOT COMPLETE AT THIS TIME, THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 4) NOTE: PLEASE SEE FBC 13-413.1.ABC.1.1, .1.2 FOR
 MINIMUM REQUIRED FOR VOLTAGE DROP.
  
 5) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2 AND .1.3
 FOR LIGHTING PERFORMANCE CALCULATIONS.
  
 6) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.4 FOR EXTERIOR
 LIGHTING ON THIS STRUCTURE. AT THIS TIME THE PLANS DO
 NOT INDICATE ANY LIGHTING FOR DRIVE UP, GATE AREAS ETC.
  
 7) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 FOR
 LIGHTING CONTROLS.
  
  
  
  
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved