| Plan Review Notes For Permit 08080658 |
| Permit Number |
08080658 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-23 11:46:46 | ** DENIED 2 REVIEW ** | | | | | | | | | 1) NOTE: EQUIPMENT GROUNDING CONDUCTORS ARE NOT | | | PERMITTED BEFORE THE FIRST MEANS OF DISCONNECT. 250.6, | | | 250.24. THERE ARE EQUIPMENT GROUNDS ARE SHOWN FROM | | | METER TO GUTTER AND GUTTER TO EACH FIRST MAIN. | | | | | | | | | 2) NOTE: THE RISER SHOWS CONDUCTORS HOWEVER HOW MANY OF | | | EACH TYPE ETC.? | | | 240.4, 310.16. | | | | | | 3) NOTE: VALUE FOR SCOPE OF WORK WAS NOT REVISED. FBC | | | 108.3. | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|