Plan Review Notes
Plan Review Notes For Permit 08080658
Permit Number 08080658
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-02 08:42:13 
  
  
  
  
 ** DENIED *
  
  
 ** PLEASE COMPLETE RISER.
  
 1) NOTE: PLEASE SEE RISER AS NO CONDUCTORS ARE SHOWN
 FROM METER TO GUTTER AND FROM GUTTER TO EACH SERVICE
 DISCONNECT/PANEL.
 PLEASE SEE 240.4,310.16.
 FBC 106.3.5.1.2, 106.1.1 FOR ADDITIONAL INFORMATION AND
 CLARITY
  
 2) NOTE: PLEASE INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66 ( NO ALUMINUM IS
 PERMITTED)
  
 3) NOTE: PLEASE INDICATE A MINIMUM OF TOW GROUNDING
 ELECTRODES (GROUND RODS) AND SIZE OF GROUND RODS.
 250.50-250.56
  
 4) NOTE: THE EQUIPMENT GROUNDING CONDUCTOR TO THE SUB
 PANEL NEEDS TO BE COPPER. 90.4, 110.11
  
 5) NOTE: PLANS MAY NOT CONTAIN ANY TITLE BLOCKS FROM
 ENGINEERING FIRM UNLESS THOSE PLANS ARE SIGNED, DATED
 AND SEALED BY THE SAID ENGINEER. FS 471.025, FAC
 61G15-23.002
 ** THE SCOPE OF WORK DOES NOT REQUIRE AN ENGINEER.
  
 6) NOTE: PLEASE SEE THE APPLIED VALUE SHALL INCLUDE ALL
 LABOR AND MATERIALS WHETHER OR NOT ANY IS OWNER
 SUPPLIED.
 FBC 108.3
 THE EQUIPMENT ON THIS RISER CAN NOT BE PURCHASED FOR
 THE APPLIED VALUE.
  
 7) NOTE: PLEASE STATE AIC RATINGS FOR SERVICE EQUIPMENT
 PER 110.9.
  
 8) NOTE: PLEASE INDICATE THE SIZE OF THE METER CAN.
 230.2, 230.70
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  