| Date |
Text |
| 2008-09-10 13:01:47 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE FLORIDA STATUTES 481.229, AND |
| | 471.003/ PLANS FOR COMMERCIAL SCOPE OF WORK AS |
| | SUBMITTED IS NOT PERMITTED TO BE DONE BY *DESIGNER* |
| | WHICH IS NOT LICENSED UNDER CHAPTER 471 AND 481. |
| | PLEASE BE SURE TO SEE STATUTES AS NOTED AND PLEASE BE |
| | SURE TO COMPLY. |
| | |
| | 2) NOTE: PLEASE SEE SCOPE OF WORK FOR OTHER TRADES BY |
| | THE STRUCTURAL ENGINEER NEEDS TO BE VERIFIED. |
| | 471.025 (PART 2) |
| | |
| | 3) NOTE: PLANS SHALL COMPLY WITH FBC 13-415.1.ABC.1.4 |
| | FOR LIGHTING CONTROLS FOR NEW SCOPE OF WORK. |
| | |
| | 4) NOTE: PLANS SHALL COMPLY WITH FBC 13-415.2.ABC.2.3 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS FOR EXTERIOR |
| | LIGHTING. |
| | |
| | 5) NOTE: PLANS NEED TO SHOW CIRCUITING, PANEL SCHEDULE, |
| | LOADS, CONDUCTORS, BREAKER(S) SIZES ETC. |
| | 408.4, 240.4,310.16, ETC |
| | FBC 106.3.5.1.2, 106.1.1 |
| | |
| | 6) NOTE: PLEASE SEE NFPA-101 7.8.1.3, 7.9.2 FOR EGRESS |
| | LIGHTING REQUIREMENTS TO PUBLIC RIGHT OF WAY. |
| | |
| | 7) NOTE: PLANS ARE REQUIRED TO INDICATE THE FOLLOWING |
| | MINIMUM CODES. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 8) NOTE: PLANS ARE REQUIRED TO BE DONE BY A LICENSED |
| | DESIGN PROFESSIONAL AS STATED IN 481.229, 471.003. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |