| 2008-09-05 16:57:20 | BUILDING PLAN REVIEW |
| | PERMIT: 08080629 |
| | ADD: 5423 LAKE AVENUE |
| | CONT: R. O. VIAMONTE CONSTRUCTION CO. |
| | TEL: (561)827-7965 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | SEPTEMBER 05,2008 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. 106.1* /2004 |
| | SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE |
| | CODE. |
| | |
| | 1C)INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS & 2004 |
| | EXISTING BUILDING CODE. |
| | |
| | 2) JOHN D. HOLT P. E. PLANS ARE NOT SIGNED NOR SEALED. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 3) PLANS INDICATE ADVERTISEMENT OF CANALES & ASSOCIATES |
| | RESIDENTIAL DESIGN. WORKING OUT OF SCOPE OF LICENSURE. |
| | THIS IS A COMMERCIAL PROJECT AND MUST NOT HAVE THIS |
| | INFORMATION IN THE TITLE BLOCK. SEE |
| | CASE NO 03-0489STATE OF FLORIDA DIVISION OF |
| | ADMINISTRATIVE HEARINGS , DPBR VS LEE MABIRE AND LEE |
| | MABIRE COMPANY. |
| | |
| | 4) SHEET A1 INDICATES TYPE IV CONSTRUCTION (HEAVY |
| | TIMBER) SCOPE OF WORK NOTE # 3 INDICATES TO PROVIDE NEW |
| | TRUSSES OVER EXISTING BUILDING. NOTE PLEASE SEE SECTION |
| | 602.4 THE INTERIOR BUILDING ELEMENTS ARE TO SOLID OR |
| | LAMINATED WOOD WITHOUT CONCEALED SPACES. SHEET A-3 |
| | TRUSS PROFILE DOES INDICATE CONCEALED SPACE PLEASE |
| | RE-DEFINE BUILDING TYPE OF CONSTRUCTION. |
| | |
| | 5) SHEET A-1 ALSO FAILS TO DECLARE TYPE OF ASSEMBLY |
| | OCCUPANCY 303.1, TABLE 502 AS FAR AS AREA AND ALLOWABLE |
| | STORY HEIGHT.. |
| | |
| | 6) IS THE BUILDING FIRE SPRINKLERED, THE EXISTING |
| | BUILDING DOES HAVE A 2 STORY PORTION AND IN RE-DEFINING |
| | THE MINIMUM BUILDING TYPE THE FIRE SPRINKLERS WILL ADD |
| | ANOTHER STORY 504.2 AND TABLE 503. |
| | |
| | 7) THE ELEVATION SHEETS INDICATE APPROXIMATELY 50% OF |
| | THE WINDOWS BEING REMOVED BUT NO INFORMATION AS TO HOW |
| | THEY WILL TIE BACK INTO THE EXISTING WALL. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | 1609.6 & 2109.7.2.3 & 2109.7.2.5. |
| | |
| | 8) SHEET A-3 DISCREPANCIES DETAIL OF TRUSS PROFILE |
| | INDICATES THAT DOUBLE 2X12'S ARE TO BE THROUGH BOLTED W |
| | /2- 2/8" THRU BOLTS INTO EXISTING WOOD BEAM. IF |
| | EXISTING WOOD BEAM HOW LARGE WASHERS ARE TO BE ON THE |
| | 5/8" THROUGH BOLTS? |
| | |
| | 9) SHEET D-1 INDICATES THE 2 STORY PORTION OF THE |
| | BUILDING HAS A FLAT ROOF, BUT SHEET A-3 HAS NO TRUSS |
| | PROFILE FOR THIS PORTION, IS THERE A PARAPET AROUND |
| | THIS PORTION OF THE BUILDING? |
| | |
| | 10) BOTH SHEETS A-1 AND A-2 INDICATE NEW GABLE ENDS BUT |
| | THERE IS NO INFORMATION AS THE NEW GABLE WALL |
| | CONSTRUCTION ON THE CBS PORTION OF THE BUILDING. |
| | CONCRETE. 1918.3.1 GENERAL. GABLE END WALLS SHALL BE |
| | STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL |
| | SUPPORT. |
| | MASONRY. 2115.1.1 GENERAL. GABLE END WALLS SHALL BE |
| | STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL |
| | SUPPORT. |
| | STEEL STUD2115.1.1 GENERAL. GABLE END WALLS SHALL BE |
| | STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL |
| | SUPPORT. |
| | WOOD STUDS2304.3.4.1 GENERAL. GABLE END WALLS SHALL BE |
| | STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL |
| | SUPPORT. |
| | PLEASE PROVIDE A CUT SECTION THROUGH THIS WALL |
| | PROVIDING THE WALL CONSTRUCTION, TYPE OF ANCHORS AND |
| | COMPONENTS. |
| | |
| | 11) THE TWO STORY SECTION OF THIS CBS BUILDING WITH A |
| | NEW SLOPED ROOF CREATING ATTIC SPACE. 1209.2 ATTIC |
| | SPACES. AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES |
| | (559 MM BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA |
| | HAVING A CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A |
| | 30-INCH (762 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC |
| | SPACE SHALL BE PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| | |
| | 12) IN BOTH AREAS THE NEW 2 STORY PORTION AS WELL AS |
| | THE LARGER NEW SLOPED ROOF WILL NEED TO INDICATE : |
| | 1203.2 ATTIC SPACES. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH |
| | SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED |
| | AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING |
| | SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE |
| | MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF |
| | AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND |
| | THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL |
| | NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE |
| | VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING |
| | AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER |
| | PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET |
| | (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE |
| | OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE |
| | VENTS. |
| | |
| | 13) THE NEW OVERHANG OR COVERED WALKWAY DOES NOT |
| | INDICATE THE TYPE OF FINISH THAT WILL BE APPLIED TO THE |
| | UNDER SIDE OF THE BOTTOM CHORD OF THE HORIZONTAL |
| | FRAMING MEMBER OF THE TRUSS. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION AS WELL AS TYPE OF EAVE VENTS THAT WILL BE |
| | USED. ADDITIONAL INFORMATION REQUIRED. 1203.2/ 106.1.2 |
| | & 1609.6. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |