| Plan Review Notes For Permit 08080626 |
| Permit Number |
08080626 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-29 10:59:54 | 2004 FBC W/2007 REVISIONS | | | REPLACE PLYWOOD AND REROOF | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVAL NOA # 07-1219.09 THAT WAS | | | SUBMITTED FOR THE GAF BUR REQUIRES RAS 117 CALCULATIONS | | | FROM AN ARCHITECT, ENGINEER OR REGISTERED ROOF | | | CONSULTANT. SUBMIT SIGNED AND SEALED RAS 117 | | | CALCULATIONS. SEE PAGE 19 OF THE NOA. FAC RULE 9B-72 | | | AND R 301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|