Plan Review Notes
Plan Review Notes For Permit 08080616
Permit Number 08080616
Review Stop ENG
Sequence Number 6
Notes
Date Text
2009-09-30 12:56:29FAILED.
 REVIEWER: DEAN LAUDERMILK, ENGINEERING PLAN REVIEWER,
 EMAIL: [email protected], OFFICE: 494-1083 (ENG.),
 805-6716 (CONSTRUCTION SERVICES)
 1-NEEDS FIRE REVIEW, ADDED FIRE HYDRANT. WATER AND
 SEWER PLAN ONLY COVERS THIS ITEM SO IT WILL NOT BE
 REVIEWED BY ESD.
 2-SHEET S-1: DUMPSTER CAN NOT BE BUILT INSIDE THE FP&L
 UTILITY EASEMENT, RELOCATE IT.
 3-SHEET S-1: STREET LIGHT IS SHOWN IN THE AREA BEHIND
 THE WHEEL STOP WHERE THE CAR OVERHANGS, RELOCATE TO THE
 NORTH.
 4-SHEET S-2: DUMPSTER IS NOT THE REQUIRED SIZE. THE
 INTERNAL DIMENSIONS NEED TO BE A MINIMUM OF 12.5??? BY
 12.5???. USE MEASUREMENTS IN CITY DETAIL GC-9 FOUND AT
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/STANDARDS/2007_DET
 AILS_PDFS/GENERAL_CONSTRUCTION/GC-9.PDF
 5-NEW IMPERVIOUS AND PERVIOUS CALCULATIONS ARE
 REQUIRED. AERIAL OF SITE SHOWS EXISTING PARKING LOT IN
 THE SOUTH END OF THE PROPERTY IS EXISTING AND IS NOT
 SHOWN TO BE REMOVED.
 6-POLLUTION CONTROL PLAN DOES NOT COVER THE PROTECTION
 OF THE EXISTING AND NEW CATCH BASINS BEFORE, DURING AND
 AFTER CONSTRUCTION. IT MAY BE INCLUDED IN THE NINE PAGE
 POLLUTION CONTROL DOCUMENT LISTED AS NOTE 5 ON THE
 PLAN, BUT IT WAS NOT INCLUDED WITH THESE PLANS.
 7-12' UTILITY EASEMENT ON THE SOUTH SIDE OF THE
 PROPERTY THAT RUNS FROM OKEECHOBEE SOUTH THAT HAS TREES
 IN IT, THIS IS NOT ALLOWED UNLESS THE UTILITY (FP&L)
 SIGNS OFF.
 8-PLANTING THREE TREES ON TOP OF THE WATER AND SEWER
 LINES TO THE EXISTING BUILDING, THIS IS NOT ALLOWED.
 THE ROOT BALL OF TREES NEED TO BE 5??? FROM THE
 UTILITY.
  
  