| Plan Review Notes For Permit 08080616 |
| Permit Number |
08080616 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-12-01 08:30:04 | REDLINED PLANS. | | | | | | | | | 1) NOTE: EQUIPMENT GROUNDING CONDUCTOR SHWON BEFORE THE | | | FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED. | | | 250.6,250.24 | | | | | | 2) NOTE: PLANS STATE ASTRONOMICAL TIME CLOCK HOWEVER | | | NOT BACK UP. A MINIMUM OF 10HR BACK UP IS REQUIRED PER | | | 13-415.1.ABC.1.4. |
|