2008-12-01 08:30:04REDLINED PLANS.
  
  
 1) NOTE: EQUIPMENT GROUNDING CONDUCTOR SHWON BEFORE THE
 FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 250.6,250.24
  
 2) NOTE: PLANS STATE ASTRONOMICAL TIME CLOCK HOWEVER
 NOT BACK UP. A MINIMUM OF 10HR BACK UP IS REQUIRED PER
 13-415.1.ABC.1.4.