Plan Review Notes
Plan Review Notes For Permit 08080616
Permit Number 08080616
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-10 14:16:33 
  
  
  
  
 ** DENIED **
  
 1) NOTE: PLANS SHALL COMPLY WITH FBC 13-415.1.ABC.1.4
 FOR LIGHTING CONTROLS FOR NEW SCOPE OF WORK.
  
 2) NOTE: PLANS SHALL COMPLY WITH FBC 13-415.2.ABC.2.3
 FOR LIGHTING PERFORMANCE CALCULATIONS FOR EXTERIOR
 LIGHTING.
  
 3) NOTE: PLANS NEED TO SHOW CIRCUITING, PANEL SCHEDULE,
 LOADS, CONDUCTORS, BREAKER(S) SIZES ETC.
 408.4, 240.4,310.16, ETC
 FBC 106.3.5.1.2, 106.1.1
  
 4) NOTE: PLEASE SEE 13-413.1.ABC.1.2 FOR VOLTAGE DROP
 REQUIRED.
  
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  