Plan Review Notes
Plan Review Notes For Permit 08080615
Permit Number 08080615
Review Stop P
Sequence Number 1
Notes
Date Text
2008-09-11 08:54:39PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007
 REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT
 IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE -
 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY..
  
 4. SHEET 2 OF 3, "B" TRENCH DRAIN DETAIL: CLEARLY
 INDICATE ON THE RESUBMITTED PLANS THE FOLLOWING
 INFORMATION PER THE FOLLOWING FBC-2004 PLUMBING
 SECTIONS.
  
 A} CLEARLY INDICATE THE SIZE OF THE TRENCH DRAIN. IS
 THIS A PREFABRICATED TRENCH DRAIN? IF THIS IS A
 PREFABRICATED TRENCH DRAIN CLEARLY INDICATE THE MAKE
 AND MODEL NUMBER ON THE DETAIL. PER SECTION 1101.1
 SCOPE.
  
 B} CLEARLY INDICATE WHERE THE DISCHAGE OF THE STORM
 WATER FOR THE TRENCH DRAIN IS LOCATED AND THE SIZE OF
 THE DRAIN PIPE ON THE RESUBMITTED PLANS. WILL THE
 TRENCH DRAIN DISCHARGE INTO AN EXISTING CATCH BASIN OR
 UNDERGROUND STORM PIPE? PLEASE CLARIFY THIS PER SECTION
 1101.1 SCOPE.
  
 5. SHEET 2 OF 3, 1ST FLOOR PLAN IS INDICATING A STORAGE
 ROOM ADDITION. PLEASE PROVIDE A ROOF PLAN THAT
 INDICATES HOW THE ROOF WILL BE PITCHED TO PROPERLY
 DRAIN, AND INDICATE THE FOLLOWING INFORMATION PER THE
 FOLLOWING CODE REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF AND
 VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS AND
 SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 PLUMBING,
 SECTION 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 6. SHEET 2 OF 3, COVER ENTRY AND BALCONY DETAIL DOES
 NOT CLEARLY INDICATE HOW THE BALCONY WILL DRAIN STORM
 WATER. PLEASE CLARIFY THE DETAILAND CLEARLY INDICATE
 HOW THE BALCONY WILL DISCHARGE STORM WATER. PRIMARY AND
 SECONDARY DRAINS MAY BE REQUIRED FOR THE BALCONY. PER
 FBC-2004 PLUMBING SECTION 1101.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER