| 2008-09-11 08:54:39 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007 |
| | REVISIONS). PER (W.P.B. AS AMENDED) SECTION 106.5 |
| | RETENTION OF CONSTRUCTION DOCUMENTS. |
| | |
| | 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| | EXISTING BUILDING CHAPTER 3. |
| | |
| | 3. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT |
| | IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE - |
| | 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY.. |
| | |
| | 4. SHEET 2 OF 3, "B" TRENCH DRAIN DETAIL: CLEARLY |
| | INDICATE ON THE RESUBMITTED PLANS THE FOLLOWING |
| | INFORMATION PER THE FOLLOWING FBC-2004 PLUMBING |
| | SECTIONS. |
| | |
| | A} CLEARLY INDICATE THE SIZE OF THE TRENCH DRAIN. IS |
| | THIS A PREFABRICATED TRENCH DRAIN? IF THIS IS A |
| | PREFABRICATED TRENCH DRAIN CLEARLY INDICATE THE MAKE |
| | AND MODEL NUMBER ON THE DETAIL. PER SECTION 1101.1 |
| | SCOPE. |
| | |
| | B} CLEARLY INDICATE WHERE THE DISCHAGE OF THE STORM |
| | WATER FOR THE TRENCH DRAIN IS LOCATED AND THE SIZE OF |
| | THE DRAIN PIPE ON THE RESUBMITTED PLANS. WILL THE |
| | TRENCH DRAIN DISCHARGE INTO AN EXISTING CATCH BASIN OR |
| | UNDERGROUND STORM PIPE? PLEASE CLARIFY THIS PER SECTION |
| | 1101.1 SCOPE. |
| | |
| | 5. SHEET 2 OF 3, 1ST FLOOR PLAN IS INDICATING A STORAGE |
| | ROOM ADDITION. PLEASE PROVIDE A ROOF PLAN THAT |
| | INDICATES HOW THE ROOF WILL BE PITCHED TO PROPERLY |
| | DRAIN, AND INDICATE THE FOLLOWING INFORMATION PER THE |
| | FOLLOWING CODE REFERENCES. |
| | A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF AND |
| | VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS AND |
| | SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 PLUMBING, |
| | SECTION 1106. |
| | B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004 |
| | PLUMBING, SECTION 1106.2 |
| | C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION |
| | 1106.4 |
| | D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING, |
| | SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004 |
| | PLUMBING, TABLE 1106.7. |
| | E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004 |
| | PLUMBING, SECTION 1107. |
| | A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING, |
| | SECTION 1107.1. |
| | B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING, |
| | SECTION 1107.2. |
| | |
| | 6. SHEET 2 OF 3, COVER ENTRY AND BALCONY DETAIL DOES |
| | NOT CLEARLY INDICATE HOW THE BALCONY WILL DRAIN STORM |
| | WATER. PLEASE CLARIFY THE DETAILAND CLEARLY INDICATE |
| | HOW THE BALCONY WILL DISCHARGE STORM WATER. PRIMARY AND |
| | SECONDARY DRAINS MAY BE REQUIRED FOR THE BALCONY. PER |
| | FBC-2004 PLUMBING SECTION 1101.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |