Plan Review Notes
Plan Review Notes For Permit 08080615
Permit Number 08080615
Review Stop E
Sequence Number 1
Notes
Date Text
2008-09-03 13:08:27 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND EQUIPMENT TO BE INSTALLED UNDER THIS
 PERMIT, ALL THAT'S SHOWN IS TWO LIGHT FIXTURES AND ONE
 SWITCH IN THE STORAGE ROOM INDICATE IF
 NEW OR EXISTING. 106.3.5 FBC.
  
 2} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS
 AMENDED.
  
 3} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B)..
 INDICATE COMPLIANCE ON THE PLAN, IF EXISTING LOCATE
 SAME.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  