| Plan Review Notes For Permit 08080615 |
| Permit Number |
08080615 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-03 13:08:27 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR | | | DEVICES AND EQUIPMENT TO BE INSTALLED UNDER THIS | | | PERMIT, ALL THAT'S SHOWN IS TWO LIGHT FIXTURES AND ONE | | | SWITCH IN THE STORAGE ROOM INDICATE IF | | | NEW OR EXISTING. 106.3.5 FBC. | | | | | | 2} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED | | | UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY | | | IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS | | | AMENDED. | | | | | | 3} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B).. | | | INDICATE COMPLIANCE ON THE PLAN, IF EXISTING LOCATE | | | SAME. | | | | | | AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF WORK | | | PURPOSED. 105.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|