Plan Review Notes
Plan Review Notes For Permit 08080615
Permit Number 08080615
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-10 15:29:499-10-08
 BUILDING PLAN REVIEW
 PERMIT: 08080615
 ADD: 2616 E TAMARIND AVE.
 CONT: YAVEL CONSTRUCTION
 TEL: (561)512-9341
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) THE PLANS NEED TO INDICATE THE TYPE OF BUILDING PER
 FBC CHAPTER 6, THE USE AND OCCUPANCY PER CHAPTER 3 AND
 THE OCCUPANT LOAD PER TABLE 1004.1.2.
  
 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6) THE PLANS SHALL CLEARLY SHOW THE EXISTING STRUCTURAL
 AND FLOOR LAYOUT AND THE PROPOSED CHANGES SHALL BE
 CLEARLY SHOWN ON THE DRAWINGS. THE DRAWINGS SUBMITTED
 SHOW NO DISTENTION BETWEEN THE EXISTING LAYOUT AND THE
 PROPOSED LAYOUT. PRODUCT APPROVALS WERE SUBMITTED FOR
 TWO DOORS HOWEVER, THE DRAWINGS DO NOT SHOW WHICH DOORS
 WILL BE CHANGED. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE CODE. FBC 106.1.1
  
 7) PROVIDE A DETAIL WALL LEGEND SHOWING THE DIFFERENT
 TYPES OF WALLS TO BE CONSTRUCTED AND THE EXISTING
 WALLS. SHOW THE SLOPE OF THE NEW SLAB LEADING TO THE
 LOADING DOCK AREA ON SHEET 2 OF 3. SOME THE DETAIL
 INFORMATION PERTAINING TO THE COVERED ENTRY IS NOT
 LEGIBLE.
  
 8) THE PLANS NEED TO STATE THE POINT LOAD, FLOOR LOAD
 AND CONCENTRATED LOAD OF THE DECK PER FBC 1604.8.3 AND
 1607. FOR THE GUARD RAILS SEE 1607.7.1/1607.7.1.1 AND
 TABLE 1607.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726