| 2008-09-17 14:12:52 | 2004 FBC W/2007 REVISIONS |
| | R-3 ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) THE EXPOSURE CATEGORY FOR THE STRUCTURE IS |
| | INCORRECTLY SPECIFIED AS CATEGORY B ON SHEETS A1 AND |
| | A4. SEE R301.2.1.4 EXPOSURE CATEGORY. 3. EXPOSURE C. |
| | OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, INCLUDING |
| | SURFACE UNDULATIONS OR OTHER IRREGULARITIES, HAVING |
| | HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING |
| | MORE THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE |
| | IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY |
| | BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE |
| | THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF |
| | EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE |
| | OF MORE THAN 600 FEET (182.9 M). PLEASE CORRECT AND |
| | REVISE COMPONENT AND CLADDING PRESSURES ON A4. |
| | |
| | 3) THE MINIMUM WALL INSULATION IS SPECIFIED AS R-4.1 ON |
| | THE WALL SECTION ON SHEET A4. THE ENERGY CALCULATION |
| | FORM LISTS A MINIMUM OF R-5. IF YOU USE THE |
| | PRESCRIPTIVE METHOD C OF THE ENERGY CODE, THE MINIMUM |
| | INSULATION FOR MASONRY WALLS IS R-5. PLEASE CORRECT. |
| | FBC 13-600. |
| | |
| | 4) THE WINDOW BUCK DETAILS ON A4 SHOW THE DRYWALL |
| | SUPPORTING A PORTION OF THE WINDOW FRAMES. PLEASE |
| | REVISE. SEE R613.6.1.1 MASONRY, CONCRETE OR OTHER |
| | STRUCTURAL SUBSTRATE. UNLESS OTHERWISE TESTED, BUCKS |
| | SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR |
| | DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS |
| | PROVIDED. |
| | |
| | 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR 8" WIDE |
| | LINTELS. THE NOA THAT WAS SUBMITTED IS FOR 4", 6" AND |
| | 12" LINTELS. FAC RULE 9B-72. |
| | |
| | 6) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF |
| | COVERING. FAC RULE 9B-72. |
| | |
| | 7) THE VALUATION OF THE WORK HAS BEEN INCREASED TO |
| | $40,509.00, ADDITIONAL PERMIT FEES OF $174.02 ARE DUE. |
| | |