2008-08-28 11:51:39GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC IS NOT INDICATING
 CORRESPONING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 ON THE ISOMETRIC WITH NO CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC IS NOT INDICATING THE
 ABOVE GROUND PIPING MATERIAL BY THE METER, GRILL,
 GENERATOR, AND POOL HEATER. ALSO THERE IS A 10' OF 3/4"
 PIPE GOING TO THE FIRE PLACE THAT DOES NOT CLEARLY
 INDICATE THE PIPING MATERIAL. IT LOOKS LIKE PE, HOWEVER
 PE PIPING CAN'T BE USED IN THIS LOCATION PER FBC-2004
 FUEL GAS SECTION 403.6 PLASTIC PIPE AND FITTING OUTSIDE
 UNDERGROUND ONLY. PLEASE CLARIFY THESE AREAS ON THE
 RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: REFERENCE COMMENT #1 AND COMPLY.
  
 4. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATORS
 (2PSI TO 0.5PSI) TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC
 402.2. MANUFACTURE SPECIFICATION SHEETS SHALL CLEARLY
 INDICATE THE REGULATOR MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY, AND A LISTING FROM A RECOGNIZED TESTING
 LABORATORY (LISTING EXAMPLES= AGA, CSA, UL).
  
 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 (W.P.B. AS AMENDED) SECTION *106.3.4.3.
  
 7. PER FS 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2):
 IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF
 NO FURTHER EFFECT.
  
 8. NOTE: THE SUBMITTEDOMEGA FLEX TRACPIPE TABLE IS
 UNACCEPTABLE DUE TO FLORIDA PUBLIC UTILITIES COMPANY
 PROVIDES A 12" WC WITH A 0.5 INCH PRESSURE DROP. WE
 WILL BE USING FBC-2004 FUEL GAS TABLE 402.4(14) FOR
 CSST PIPE.
  
 9. PER THE NOTE: GENERATOR PERMIT TO BE PULLED
 SEPERATE BY THE ELECTRICIAN. THIS FOR LINES AND CONNECT
 ONLY.
 *PLEASE KNOW THAT THE GENERATOR NEEDS TO BE INDICATED
 AS "FUTURE" AND THAT ALL PIPING TO THE GENERATOR IS AT
 CONTRACTORS OWN RISK DUE TO ZONING APPROVAL OF THE
 GENERATORS LOCATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]