| Date |
Text |
| 2008-09-10 11:33:47 | 2007 FBC W/2007 REVISIONS |
| | ENCLOSE CARPORT |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE VALUE OF THE WORK IS TOO LOW. FOR PERMITTING |
| | PURPOSES, THE VALUE INCLUDES LABOR, MATERIAL, DESIGN |
| | FEES, OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A |
| | CONTRACTOR. PLEASE REVISE VALUE ON APPLICATION AND PAY |
| | ADDITIONAL PERMIT FEES WHEN PERMIT IS RE-SUBMITTED. FBC |
| | 108.3* CITY AMENDMENTS |
| | |
| | 2) SUBMIT 2 COPIES OF A SURVEY OR SITE PLAN INDICATING |
| | THE DISTANCE TO PROPERTY LINES. IF CARPORT WALL IS LESS |
| | THAN 6 FEET TO THE PROPERTY LINE, SPECIFY THE DISTANCE |
| | TO ADJACENT STRUCTURES OR SHOW COMPLIANCE WITH FBC |
| | R302.1 EXTERIOR WALLS. |
| | EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| | SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| | RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| | NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| | AN ADJACENT PROJECTION OR WALL. |
| | |
| | 3) SPECIFY THE APPLICABLE CODE AND DESIGN DATA ON THE |
| | PLANS. SEE 2004 FBC W/2007 REVISIONS RESIDENTIAL CODE |
| | CHAPTER R301 AND ASCE7-02. SPECIFY WIND SPEED (140MPH 3 |
| | SEC GUST), EXPOSURE CATEGORY, WIND IMPORTANCE FACTOR, |
| | ETC. |
| | |
| | 4) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1/8 |
| | INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | |
| | 5) SUBMIT 2 COPIES OF THE ENERGY CALCULATION FORM WITH |
| | THE CORRECT INFORMATION IN THE PROPER LOCATIONS. FBC |
| | CHAPTER 13-600. MUST BE SIGNED AND DATED BY THE |
| | PREPARER AND THE OWNER/AGENT. |
| | |
| | 6) SPECIFY THE CEILING INSULATION ON THE PLANS. THE |
| | MINIMUM CEILING INSULATION IS R-30 WHEN USING THE |
| | PRESCRIPTIVE METHOD TO COMPLY WITH THE ENERGY CODE. FBC |
| | 13-600 |
| | |
| | 7) REVISE THE EXTERIOR FRAME WALL INSULATION TO R-19 TO |
| | COMPLY WITH THE ENERGY CODE. FBC 13-600 |
| | |
| | 8) SPECIFY THE LENGTH OF THE ROOF OVERHANG ON THE PLANS |
| | IN ORDER TO DETERMINE COMPLIANCE WITH ENERGY CODE. FBC |
| | 13-600 |
| | |
| | 9) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. |
| | ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 |
| | INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | |
| | 10) FBC R319.1(5) REQUIRES WOOD SHEATHING AND WALL |
| | FRAMING ON THE EXTERIOR OF A BUILDING HAVING A |
| | CLEARANCE OF LESS THAN 6 INCHES FROM THE GROUND TO BE |
| | PRESSURE TREATED OR DECAY-RESISTANT LUMBER. SHOW |
| | COMPLIANCE. |
| | |
| | 11) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR |
| | TERMITES. |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | EXCEPTIONS: |
| | 1. PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN 5 |
| | / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| | MASONRY FOUNDATION SIDEWALL. |
| | 2. ACCESS OR VEHICLE RAMPS WHICH RISE TO THE INTERIOR |
| | FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH RAMPS |
| | ONLY. |
| | 3. A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND |
| | GARAGE SLABS AND ENTRY AREAS. |
| | 4. IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, THE |
| | FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR FINISH |
| | FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| | 5. MASONRY VENEERS. |
| | |
| | 12) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | OUTSWING DOOR. DCA RULE 9B-72 |
| | |
| | 14) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE SINGLE |
| | HUNG WINDOW THAT ARE NOT EXPIRED. DCA RULE 9B-72 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |